ECO MULTI SYSTEM Unit Spesifications
SM830052
I - 8
1
1. Outdoor Unit
Unit specifications (F)
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Rated conditions
Cooling: Indoor air temperature 27
°
C DB / 19.0
°
C WB
, Outdoor air temperature 35
°
C DB
* Full load conditions at Indoor / outdoor capacity ratio 130 %
Cooling: Indoor air temperature 32
°
C DB / 22.5
°
C WB , Outdoor air temperature 43
°
C DB / 25.5
°
C WB
MODEL No.
Outdoor Unit
SPW – C903GY8
POWER SOURCE
380 - 400 - 415 V / 3 phase / 50Hz
PERFORMANCE
Cooling
Capacity
kW
28.0
BTU / h
95,500
Air circulation (Hi)
m
3
/min(cu. ft/min)
150 (5,300)
ELECTRICAL RATINGS
Voltage rating
V
380 - 400 - 415
Available voltage range
V
342 – 456
Running amperes
A
17.6 - 17.1 -
16.8
Max. running amperes*
A
24.2 - 23.6 -
23.1
Power input
kW
10.9 - 11.0 -
11.1
Max. power input*
kW
15.0 - 15.2 -
15.3
Power factor
%
94 -
93 -
92
C.O.P.
W/W
2 .57 - 2.55 -
2.52
Compressor locked rotor amperes
A
62 - 65 -
67
FEATURES
Controls
Microprocessor
Defrost control
Reverse cycle, microprocessor control
Service function
Sensor temp. recall function
Past service warnings recall function
Refrigerant amount at shipment
kg
R22 - 11.0
Refrigerant control
Electronic Refrigerant Control Valve
Operation sound (Hi)
dB-A
58
REFRIGERANT TUBING
Limit of tubing length
m(ft.)
100 (328)
Limit of elevation difference
m(ft.)
Outdoor unit is higher than indoor unit : 50 (165)
between the two units
Outdoor unit is lower than indoor unit : 30 (100)
Refrigerant tube
Narrow tube mm (in)
12.7 (
1 / 2 )
outer diameter
Wide tube
mm (in)
28.58 ( 1-1 / 8 )
Refrigerant tubing kit / joint kit
Optional
DIMENSIONS & WEIGHT
Unit dimensions
Package dimensions
Unit dimensions
Height
mm(in)
1,218 (48
-
)
1,351 (53 -
1 / 4)
Width
mm(in)
883 (34 - 3 / 4)
1,047 (41 -
1 / 4)
Depth
mm(in)
883 (34 - 3 / 4)
1,005 (39 -
5 / 8)
Net weight
kg(lb)
222 (
489
)
Shipping weight
kg(lb)
237 (
522
)
Shipping volume
m
3
(cu. ft.)
1.42 ( 50.1
)