8. FUNCTION
8-1. Room Temperature Control
●
Room temperature control is obtained by cycling the compressor ON and OFF under control of the room
temperature sensor in the remote control unit.
●
The room temperature (and other information) is transmitted every 5 minutes by the remote control unit to the
controller in the indoor unit.
●
Once the compressor starts, it keeps running for 5 minutes.
●
Once the compressor stops, it will not start running again for 3 minutes.
●
Thermo ON :
When room temperature rises 1°C above the set temperature T˚C.
Compressor
➞
ON
●
Thermo. OFF : When the room temperature decreases below the set temperature T°C.
Compressor
➞
OFF
●
Whenever the compressor is running, the indoor unit always generates negative ions. (ION lamp lights up.).
NOTE
ON
OFF
ON
OFF
ON
OFF
Compressor
ON
OFF
ON
OFF
ON
OFF
Outdoor fan
T+1
°
C
T
°
C
Set temp.
Thermo.
OFF
Thermo.
OFF
Thermo.
ON
Thermo.
OFF
Thermo.
ON
Thermo.
ON
Thermo.
ON
Room temp.
5 minutes
5 minutes
5 minutes
5 minutes
5 minutes
5 minutes
5 minutes
Signal from remote control unit
29