install the indoor unit more than 1 meter away from any
antenna or power lines or connecting wires used for tele-
vision, radio, telephone, security system, or intercom.
Electrical noise from any of these sources may affect
operation.

!

install in a sturdy manner to avoid increased operating
noise.

Table 3

unit: mm

*  If total tubing length becomes 45 to 60 m (max.) or 45 to 70 m (max.), charge additional refrigerant (R410A) by 20 g/m.

No additional charge of compressor oil is necessary.

2-2. Connecting Indoor Units

(1) Connecting indoor unit for SAP-CMRV1926

Fig. 4a

ø12.70

Union

ø9.52

Flare

A joint for connecting tubes of

different sizes

(ø9.52       ø12.70) Supplied Reducer

ø9.52

ø6.35

ø12.70

ø6.35

ø9.52

B

ø9.52

A

Outdoor unit

Indoor unit

(SAP-KMRV74EH, KMRV94EH, KMRV124EH)

(SAP-KMRV76EH, KMRV96EH, KMRV126EH)

(SAP-KRV96EHDS, KRV126EHDS)
(SAP-KRV184EH)

(SAP-KRV186EH)

ø9.52

ø6.35

ø9.52

ø6.35

ø9.52

B

ø9.52

A

Outdoor unit

Indoor unit

(SAP-KMRV74EH, KMRV94EH, KMRV124EH)

(SAP-KMRV76EH, KMRV96EH, KMRV126EH)

(SAP-KRV96EHDS, KRV126EHDS)
(SAP-KMRV74EH, KMRV94EH, KMRV124EH)

(SAP-KMRV76EH, KMRV96EH, KMRV126EH)

(SAP-KRV96EHDS, KRV126EHDS)

(A)

(B)

Max. Allowable 

Max. Allowable Total 

Limit of 

Limit of Elevation

Required Amount

Tubing Length 

Tubing  Length 

Total Tubing Length

Difference 

of Additional

Model

per unit 

at shipment

(L1+L2) or (L1+L2+L3)

(H1, H2, H3, H4)

Refrigerant

(m)

(L1+L2) or (L1+L2+L3)

or (L1+L2+L3+L4)

(m)

(g/m)

*

or (L1+L2+L3+L4)

(m)

(m)

CMRV1926

25

45 (L1+L2)

45 (L1+L2)

15

CMRV1936

25

45 (L1+L2+L3)

45 (L1+L2+L3)

15

CMRV2446

25

45 (L1+L2+L3+L4)

60 (L1+L2+L3+L4)

15

20

CMRV3146

30

45 (L1+L2+L3+L4)

70 (L1+L2+L3+L4)

15

20

Fig. 4

08-253 CMRV3146EH_OU EN  10/14/08  2:39 PM  Page 5

Содержание SAP-CMRV1926EH

Страница 1: ...ING A HOME AUTOMATION DEVICE 24 8 INSTALLATION CHECK SHEET 24 9 ELECTRIC WIRING DIAGRAM 24 INSTALLATION INSTRUCTIONS Model Combinations Combine indoor and outdoor units only as listed below Indoor Unit Outdoor Unit Combine indoor and outdoor units only as listed in the combination tables for 2 room 3 room or 4 room outdoor unit as shown in its respective manual Power Source 50 Hz single phase 220 ...

Страница 2: ...shock can occur When Transporting Be careful when picking up and moving the indoor and outdoor units Get a partner to help and bend your knees when lifting to reduce strain on your back Sharp edges or thin aluminum fins on the air conditioner can cut your fin gers When Installing In a Ceiling or Wall Make sure the ceiling wall is strong enough to hold the unit s weight It may be necessary to const...

Страница 3: ...erial If you wish to purchase these materials separately from a local source you will need 1 Deoxidized annealed copper tube for refrigerant tubing as detailed in Table 2 Cut each tube to the appropriate lengths 30 cm to 40 cm to dampen vibration between units Table 2 2 Foamed polyethylene insulation for the specified copper tubes as required to precise length of tub ing Wall thickness of the insu...

Страница 4: ...elect a location that will hold the weight of the unit select a location where tubing and drain hose have the shortest run to the outside Fig 1 allow room for operation and maintenance as well as unrestricted air flow around the unit Fig 2 install the unit within the maximum elevation difference H1 H2 H3 H4 above or below the outdoor unit and within a total tubing length L1 L2 L1 L2 L3 L1 L2 L3 L4...

Страница 5: ... ø12 70 ø6 35 ø9 52 B ø9 52 A Outdoor unit Indoor unit SAP KMRV74EH KMRV94EH KMRV124EH SAP KMRV76EH KMRV96EH KMRV126EH SAP KRV96EHDS KRV126EHDS SAP KRV184EH SAP KRV186EH ø9 52 ø6 35 ø9 52 ø6 35 ø9 52 B ø9 52 A Outdoor unit Indoor unit SAP KMRV74EH KMRV94EH KMRV124EH SAP KMRV76EH KMRV96EH KMRV126EH SAP KRV96EHDS KRV126EHDS SAP KMRV74EH KMRV94EH KMRV124EH SAP KMRV76EH KMRV96EH KMRV126EH SAP KRV96EHD...

Страница 6: ...ø9 52 ø6 35 ø9 52 ø6 35 ø9 52 ø6 35 C ø9 52 B ø9 52 A Outdoor unit Indoor unit SAP KMRV74EH KMRV94EH KMRV124EH SAP KMRV76EH KMRV96EH KMRV126EH SAP KRV96EHDS KRV126EHDS SAP KMRV74EH KMRV94EH KMRV124EH SAP KMRV76EH KMRV96EH KMRV126EH SAP KRV96EHDS KRV126EHDS SAP KMRV74EH KMRV94EH KMRV124EH SAP KMRV76EH KMRV96EH KMRV126EH SAP KRV96EHDS KRV126EHDS B Fig 4c ø12 70 Union ø9 52 Flare A joint for connecti...

Страница 7: ...AP KMRV74EH KMRV94EH KMRV124EH SAP KMRV76EH KMRV96EH KMRV126EH SAP KRV96EHDS KRV126EHDS ø9 52 ø9 52 ø6 35 D Outdoor unit Indoor unit SAP KMRV74EH KMRV94EH KMRV124EH SAP KMRV76EH KMRV96EH KMRV126EH SAP KRV96EHDS KRV126EHDS SAP KRV244EH SAP KRV246EH ø12 70 Union ø9 52 Flare ø9 52 ø12 70 Locally purchased C Fig 4f ø15 88 Union ø12 70 Flare ø12 70 ø15 88 Locally purchased ø9 52 ø9 52 ø6 35 ø9 52 ø6 35...

Страница 8: ... ø12 70 Flare ø12 70 ø9 52 Supplied Reducer ø9 52 ø9 52 ø6 35 ø9 52 ø6 35 ø12 70 ø6 35 C ø12 70 B ø12 70 A SAP KMRV74EH KMRV94EH KMRV124EH SAP KMRV76EH KMRV96EH KMRV126EH SAP KRV96EHDS KRV126EHDS SAP KMRV74EH KMRV94EH KMRV124EH SAP KMRV76EH KMRV96EH KMRV126EH SAP KRV96EHDS KRV126EHDS ø9 52 ø9 52 ø6 35 D Outdoor unit Indoor unit SAP KMRV74EH KMRV94EH KMRV124EH SAP KMRV76EH KMRV96EH KMRV126EH SAP KR...

Страница 9: ...4EH KMRV94EH KMRV124EH SAP KMRV76EH KMRV96EH KMRV126EH SAP KRV96EHDS KRV126EHDS SAP KRV244EH SAP KRV246EH ø9 52 Union ø12 70 Flare ø12 70 ø9 52 Supplied Reducer E Fig 4l ø15 88 Union ø12 70 Flare ø12 70 ø15 88 Locally purchased ø9 52 ø9 52 ø6 35 ø12 70 ø6 35 ø15 88 ø6 35 C ø12 70 B ø12 70 A SAP KRV184EH SAP KRV186EH SAP KMRV74EH KMRV94EH KMRV124EH SAP KMRV76EH KMRV96EH KMRV126EH SAP KRV96EHDS KRV1...

Страница 10: ...level concrete pad concrete block 15 40 cm beams or equal a minimum of 15 cm above ground level to reduce humidity and protect the unit against possible water damage and decreased service life Fig 5c install cushion rubber under unit s feet to reduce vibration and noise Fig 5d use lug bolts or equal to bolt down unit reducing vibration and noise install in a location where no antenna of a televisi...

Страница 11: ... 75 73 70 70 70 70 A Service valve on narrow tube side Outer diameter ø6 35 Service valve on wide tube side Outer diameter ø12 70 Service valve on wide tube side Outer diameter ø9 52 A 608 136 12 900 345 320 369 85 740 18 150 72 70 51 113 75 70 114 A Service valve on narrow tube side Outer diameter ø6 35 Service valve on wide tube side Outer diameter ø9 52 A Fig 6d unit mm Fig 6c Fig 6b 1 SAP CMRV...

Страница 12: ...e below are spaces that are required in order to maintain performance Install in a location where the dimensions indicated by are ensured and where 2 or more faces of the unit are unobstructed In principle the top direction should be unobstructed Indoor unit C Indoor unit B Indoor unit A Indoor unit D Service space Power breaker Ground wire not provided Ensure 15cm of space if a drain hose is to b...

Страница 13: ... outdoor units In this method the copper tubes are flared at each end and connected with flare nuts 3 4 Flaring Procedure with a Flare Tool 1 Cut the copper tube to the required length with a tube cutter It is recommended to cut approx 30 50 cm longer than the tubing length you estimate 2 Remove burrs at the end of the copper tube with a tube reamer or file This process is important and should be ...

Страница 14: ...oper connection align the union tube and flare tube straight with each other then screw in the flare nut lightly at first to obtain a smooth match Fig 13 3 6 Tubing Connections a Temporary connection Screw in 3 5 rotations by hand Fig 14 b To fasten the flare nuts apply specified torque as Table 4 NOTE NOTE Reamer Copper tubing Fig 9 Flare tool Flare nut Copper tubing Fig 11 Apply refrigerant lubr...

Страница 15: ...p the tubing bundle to wall using 1 clamp approx every 120 cm Do not wind the armoring tape too tightly since this will decrease the heat insulation effect Also be sure the con densation drain hose splits away from the bundle and drips clear of the unit and the tubing 3 9 Finishing the Installation After finishing insulating and taping over the tubing use sealing putty to seal off the hole in the ...

Страница 16: ...service valve Fig 20 Fig 20 Fig 21 CAUTION Be sure to use a manifold valve for air purging If it is not available use a stop valve for this purpose The Hi knob of the manifold valve must always be kept closed CAUTION CAUTION Before using the vacuum pump adapter read the vacuum pump adapter manual and use the adapter correctly In order to prevent charging errors with the air conditioner that uses R...

Страница 17: ...k then apply the vacuum again 6 With a hex wrench turn the valve stem on the nar row tube service valve counter clockwise by 90 degrees 1 4 turn for 10 seconds and then turn the stem clockwise to close it again 7 With a standard screwdriver turn the wide tube service valve stem counterclockwise to fully open the valve 8 Turn the narrow tube service valve stem counter clockwise to fully open the va...

Страница 18: ...blem 4 Disconnect the manifold gauge and the inter unit tubes and attach the caps and flare nuts At this point pump down is completed If the caps and flare nuts are not reattached there is the danger of gas leakage Refer to Fig 24 If pump down is not possible If the Air Conditioner cannot be operated because of a malfunction or other cause use a refrigerant recovery device to recover the refrigera...

Страница 19: ... moving parts of the fan 6 Unauthorized changes in the internal wiring can be very dangerous The manufacturer will accept no responsibility for any damage or misoperation that occurs as a result of such unauthorized changes 5 2 Recommended Wire Length and Diameter Regulations on wiring diameter differ from locality to locality For field wiring requirements please refer to your local elec trical co...

Страница 20: ...rical noise caused by high tension Otherwise electrical shock may occur Place a dedicated ground more than 2 meters away from other grounds and do not have it shared with other electric appliances WARNING Fig 25b 4 indoor units with SAP CMRV2446 CMRV3146 INDOOR UNIT 4 3 2 1 3 2 1 2 1 UNIT A Terminal L N A B C Terminal 9P Terminal 2P OUTDOOR UNIT Grounding line INDOOR UNIT 4 3 2 1 6 5 4 UNIT B Term...

Страница 21: ...minal screw 4 Shape the loop wire properly place it on the termi nal plate and fix it securely with the removed termi nal screw using a screwdriver For stranded wiring 1 Cut the wire end with a cutting pliers then strip the insulation to expose the stranded wiring about 10 mm and tightly twist the wire ends Figs 28 and 29 2 Using a screwdriver remove the terminal screw s on the terminal plate 3 Us...

Страница 22: ...t tubing that is connected to service valve A bottom of the outdoor unit B is the indoor unit with refrigerant tubing that is connected to service valve B second from the bottom of the outdoor unit C is the indoor unit with refrigerant tubing that is connected to service valve C third from the bottom of the outdoor unit refrigerant tubing that is connected to service valve D top of the outdoor uni...

Страница 23: ... indoor unit If 2 units are operated simultaneously it is not possible to correctly check for errors in tubing and wiring If the room temperature is 15 C or below it may not be possible to check for tubing errors with cooling operation If this occurs perform heating operation for each unit individually and check that warm air is dis charged from each unit If there is cold air mixed in with the war...

Страница 24: ...lose the hole in the wall All service valves are fully open Remote controller signals are being positively received 9 Electric Wiring Diagram Diagrama de cableado eléctrico Diagramme de câblage électrique Elektrisches Schaltbild Diagramma dei circuiti elettrici Diagrama da fiação elétrica È È Á ÁÚ Ú Ì ÌÌ Ì Ë ËÏ Ï ÂÎ ÎÙ ÙÚ ÚÈ ÈÎ Î Î Î Ï Ïˆ ˆ ˆ ˆÛ ÛË Ë Indoor Unit Unidad interior Appareil intérieur...

Страница 25: ...5 1 1 2 2 3 3 4 4 5 5 WHT BLU BLU BLU BLU SW ASSY WHT FLAP3 PANEL MOTOR 1 1 2 2 3 3 4 4 5 5 1 2 3 4 1 1 2 2 3 3 4 4 5 5 PANEL WHT WHT WHT GRY GRY GRY GRY FLAP1 FLAP MOTOR UPPER FLAP MOTOR LOWER 1 1 2 2 3 3 4 4 5 5 6 6 7 7 8 8 9 9 10 10 1 1 2 2 3 3 4 4 5 5 FLAP1 WHT WHT WHT RED WHT FLAP2 WHT GRY GRY GRY GRY FM DC FAN MOTOR DCM BLU BLU RED BLK YEL BLU WHT WHT 1 1 2 2 3 3 4 4 5 5 6 6 WHT RED BLK YEL ...

Страница 26: ...10 2 1 3 4 W W SICOM2 SICOM2 SI C W BLK GRY RED ORG YEL 1 2 3 4 1 2 3 4 5 5 MV2 MAGNETIC COIL 1 2 3 4 1 2 3 4 5 5 MV2 1 2 3 4 1 2 3 4 C TH YEL YEL YEL YEL CW THERMISTOR CN THERMISTOR W W W W W 1 2 3 E 1 RED PNK 8FA 2 5257 57000 0 Fig 34b WHT WHT L2 L1 WHT WHT WHT 2P CONNECTOR 2 1 2 1 REACTANCE COIL THERMISTOR COMP COIL OUTDOOR A TH B TH COMPRESSOR THERMISTOR OUTDOOR THERMISTOR AW THERMISTOR W W DE...

Страница 27: ...LK YEL GRY BLK YEL GRY BLK YEL GRY BLK YEL GRY 8FA 2 5257 57100 0 Fig 34c WHT WHT L2 L1 WHT WHT WHT 2P CONNECTOR 2 1 2 1 REACTANCE W W HEATER1 HEATER0 CRANKCASE HEATER COIL THERMISTOR COMP COIL OUTDOOR A TH B TH COMPRESSOR THERMISTOR OUTDOOR THERMISTOR AW THERMISTOR W W DEF1 DEF0 W W RV1 RV0 DEF COIL DEFROST VALVE 2 1 2 1 RV COIL 4WAY VALVE AN THERMISTOR BN THERMISTOR BW THERMISTOR BLK 2P CONNECTO...

Страница 28: ...des abréviations Italiano Português EÏÏËÓÈÎ EÏÏËÓÈÎ 1 2 3 4 5 6 7 8 9 10 11 BLK BLU BRN GRN YEL GRY ORG PNK RED VLT WHT YEL BEDEUTUNG SCHWARZ BLAU BRAUN GRAU ORANGE ROSA ROT VIOLETT WEISS GELB Bedeutung der Abkürzungen ABKÜRZUNG GRÜN GELB 1 2 3 4 5 6 7 8 9 10 11 BLK BLU BRN GRN YEL GRY ORG PNK RED VLT WHT YEL Significato delle abbreviazioni ABBREV SIGNIFICATO NERO BLU MARRONE VERDE GIALLO GRIGIO A...

Отзывы: