20
English
5. How to Test Run the Air Conditioner
I
For indoor unit types
(SAP-KMRV74EH, KMRV94EH, KMRV124EH,
KRV184EH, KRV244EH)
After turning on the power of the air conditioner, use
the remote controller and follow the steps below to
conduct the test run.
(1) Set the remote controller in Test Run mode.
(Fig. 59a)
a)Press and hold the ION button and the 1HR.
TIMER button.
b)Then press and hold the ACL (Reset) button
with a pointed object such as the tip of a pen.
After 5 seconds, release the ACL button first.
c) Then release the ION and 1HR. TIMER buttons.
d)
appears and “oP-1” blinking in the remote
controller clock display area. (Fig. 59b)
(2) Start Cooling mode test run by pressing the
ON/OFF operation button of the remote controller.
(Fig. 59a)
• This starts the fan producing uncooled forced air
with the 4 indicator lamps (OPERATION lamp,
TIMER lamp, QUIET lamp, and ION lamp) on
the main unit blinking. (Fig. 60)
• After 3 minutes, the system shifts into cooling
operation, and cool air will start to be felt. Cool-
ing mode test run is unaffected by the room tem-
perature.
(3) Press the ON/OFF operation button of the remote
controller again to stop the test run. (Fig. 59a)
(4) Finally press the ACL (Reset) button of the remote
controller to release it from Test Run mode to
return to normal mode. (Fig. 59a)
• “
” and “oP-1” will disappear from the remote
controller clock display area.
After the test run is completed, be sure to press
the ACL (Reset) button to return to normal mode.
The air conditioner will not operate correctly if
this is not done.
IMPORTANT
Fig. 59a
Fig. 59b
Fig. 60
1HR.
TIMER
ON/OFF
operation
ACL
(Reset)
ION
button
button
button
button
OPERATION lamp
ION lamp
TIMER lamp
QUIET lamp
OPERATION
OPERATION
TIMER
QUIET
ION
07-370 CMRV3146EH_IU ENG 2/6/08 1:31 PM Page 20