OI-332-021EG
21
Adjusting the Airflow Direction
1. Horizontal
The horizontal airflow can be adjusted by moving the vertical vanes
with your hands to the left or right.
When the humidity is high, the vertical vanes should be in the front
position during the cooling or dehumidifying operation. If the vertical
vanes are positioned all of the way to the right or left, condensation
may begin to form around the air vent and drip down.
2. Vertical
The vertical airflow can be adjusted by moving the flap with the remote
control unit. Do not move the flap with your hands. Confirm that the
remote control unit has been turned on. Use the FLAP button to set
either the sweep function or one of the six airflow direction settings.
A. Sweep function
B. Setting the Airflow Manually
•
The flap automatically closes when the unit is off.
•
During the heating operation, the fan speed will be very low and the
flap will be in the horizontal position (position 6) until the air being
blown out of the unit begins to warm. Once the air warms up, the
flap position and fan speed change to the settings specified with the
remote control.
•
Use the FLAP button on the remote control to adjust the position of
the flap. If you move the flap by hand, the flap position according to
the remote control and the actual flap position may no longer
match. If this should happen, shut off the unit, wait for the flap to
close, and then turn on the unit again; the flap position will now be
normal again.
•
Do not have the flap pointed down during cooling operation.
Condensation may begin to form around the air vent and drip
down.
NOTE
CAUTION
CAUTION
The flap starts moving up and down to
deliver air over the sweep range.
Referring to the above illustration, use
the FLAP button to set the airflow
direction within the range used during
the heating, cooling, or dehumidifying
operation.
COOL
and
DRY
SWEEP
1
2
3
4
5
6
SWEEP
HEAT