background image

General Installation Manual 
 

General  Installation Manual  for  SANYO 
HIT Photovoltaic Modules.  Please read 
this 

manual 

completely 

before 

installation  or  use  of  SANYO  modules.  
This  manual  applies  to  the  following 
products:   
HIP-215NKHE5, HIP-210NKHE5, 
HIP-205NKHE5, HIP-200NKHE5,  
HIP-215NKHE5-2, HIP-210NKHE5-2, 
HIP-205NKHE5-2, HIP-200NKHE5-2 
 
Introduction
 
Thank  you  for  choosing  SANYO  HIT* 
photovoltaic  (PV)  modules.  With  proper 
operation  and  maintenance,  SANYO  HIT 
PV  modules  will  provide  you  with  clean, 
renewable solar electricity for many years. 
This 

manual 

contains 

important 

installation, 

maintenance 

and 

safety 

information. The word “module” as used in 
this  manual  refers  to  one  or  more  PV 
modules.    Retain  this  manual  for  future 
reference.  
 
Disclaimer of Liability
 
SANYO  does  not  assume  responsibility 
and  expressly  disclaims  liability  for  loss, 
damage,  or  expense  arising  out  of,  or  in 
any  way  connected  with  installation, 
operation,  use,  or  maintenance  by  using 
this manual.   
SANYO assumes no responsibility for any 
infringement  of  patents  or  other  rights  of 
third parties, which may result from use of 
modules.  
No  license  is  granted  by  implication  or 
under  any  patent  or  patent  rights.  The 
information  in  this  manual  is  believed  to 
be  reliable,  but  does  not  constitute  an 
expressed and/or implied warranty.  
SANYO  reserves  the  right  to  make 
changes  to  the  product,  specifications,  or 
manual without prior notice. 
 
General Information
  
The  installation  of  solar  modules  requires 
a great degree of skill and should only be 
performed 

by 

qualified 

licensed 

professionals, including, without limitation, 
licensed 

contractors 

and 

licensed 

electricians.  
 

  Warning 

• 

All instructions should be read and 
understood  before  attempting  to 
install,  wire,  operate,  and  maintain 
the  photovoltaic  module.  Contact 
with  electrically  active  parts  of the 
module  such  as  terminals  can 
result  in  burns,  sparks,  and  lethal 
shock  whether  the  module  is 
connected or disconnected. 

• 

The  installer  assumes  the  risk  of 
all  injury  that  might  occur  during 
installation, 

including, 

without 

limitation, the risk of electric shock. 

• 

PV modules generate DC electrical 
energy  when  exposed  to  sunlight 

or  other  light  sources.    Although 
single modules produce only a low 
voltage  and  current,  shocks  and 
burns are still a potential hazard.   

• 

To  avoid  the  hazard  of  electric 
shock  and  injury,  cover  the  entire 
front  surface  of  the  PV  modules 
with a dense, opaque material such 
as 

cardboard 

box, 

during 

installation  and  handling  of  the 
modules. 

• 

The  shock  hazard  increases  as 
modules  are  connected  in  parallel, 
producing  higher  current,  and  as 
modules  are  connected  in  series, 
producing higher voltages. 

• 

The  shock  hazard  increases  as

 

  

 

modules  with  nominal  open-circuit 
voltage  (Voc)  in  excess  of  50  V, 
and/or modules rated for maximum 
system voltage in excess of 50 V. 

• 

To  avoid  the  hazard  of  electric 
shock, work only in dry conditions, 
with dry modules and dry tools. 

• 

Do  not  stand  or  step  on  a  module 
to  avoid  the  hazard  of  injury  and 
damage to the module. 

• 

Do  not  puncture  or  damage  the 
back  sheet  of  a  module,  to  avoid 
the  hazard  of  electric  shock  and 
fire. 

• 

To  avoid  the  hazard  of  electric 
shock  and  injury,  children  and 
unauthorized  persons  should  not 
be  allowed  near  the  installation  of 
PV modules. 

• 

To  avoid  the  hazard  of  electric 
shock  and  injury,  be  sure  to 
completely ground all modules. 

• 

To  avoid  the  hazard  of  electric 
shock,  fire,  and  injury,  do  not 
disassemble 

the 

module, 

or 

remove  any  part  installed  by  the 
manufacturer. 

• 

Unauthorized  persons—except  the 
qualified  licensed  professional—
should  not  open  the  cover  of  the 
junction box to avoid the hazard of 
electric shock. 

 

• 

Do  not  touch  terminals  while  a 
module is exposed to light. Provide 
suitable guards to prevent yourself 
from direct contact with 30 VDC or 
greater  to  avoid  the  hazard  of 
electric shock or injury. 

• 

When  carrying  a  module,  two  or 
more  people  should  carry  it  by  its 
frame and wear non-slip gloves (to 
avoid  injury  by  a  slipping  module, 
to  a  foot,  or  cuts  by  the  edge  of  a 
frame, and so on). 

• 

Do not carry  a module by its wires 
or  junction  box,  to  avoid  the 
hazard  of  electric  shock,  injury  or 
damage to the module. 

• 

Do  not  drop  anything  on  the 
surfaces  of  a  module,  to  avoid  the 

hazard  of  electric  shock,  injury, 
and damage. 

• 

To  avoid  the  hazard  of  electric 
shock  and  fire,  be  sure  that  all 
other  system  components  are 
compatible,  and  they  do  not 
subject  the  module  to  mechanical 
or electrical hazards. 

• 

Since  sparks  may  occur,  do  not 
install 

the 

module 

where 

flammable  gases  or  vapors  are 
present. 

• 

Never leave a module unsupported 
or unsecured.   

• 

Do not drop a module.   

• 

Do  not  use  or  install  broken 
modules to avoid the hazard of fire, 
electric shock, and injury. 

• 

Do 

not 

artificially 

concentrate 

sunlight  on  a  module  to  avoid  the 
hazard of fire or damage. 

• 

Do  not  touch  the  junction  box 
terminals  to  avoid  the  hazard  of 
electric shock and injury. 

• 

Do  not  change  the  wiring  of 
bypass  diodes  to  avoid the hazard 
of electric shock and injury. 

• 

Do  not  disconnect  terminals  while 
PV  modules  generate  electricity 
and  connect  electrical  load  to 
avoid  the  hazard  of  electrical 
shock. 

 

  Cautions 

• 

Use  a  module  for  its  intended 
purpose only. 

• 

Do not treat the back sheet or front 
surface  with  paint or adhesives,  to 
avoid  reducing  its’  functionality, 
damage, 

inoperable 

conditions, 

and other unknown troubles. 

 
General Safety
 
Follow  all  permission,  installation  and 
inspection requirements.  

• 

Before installing modules, contact the 
appropriate  authorities  to  determine 
permissions, 

installation 

and 

inspection 

requirements, 

which 

should be followed.  

• 

Be  sure  that  the  construction  or 
structure  (roof,  etc.)  where  the 
modules  are  being  installed  has 
enough strength.  

• 

For  modules  mounted  on  roofs, 
special construction or structures may 
be  required  to  help  provide  proper 
installation support.   

• 

Both  roof  construction  and  module 
installation  design  have  an  effect  on 
the  fire  resistance  of  a  building. 
Improper  installation  may  contribute 
to  fire  hazards.    Additional  devices 
such  as  ground  fault,  fuses,  and 
disconnects may be required.  

• 

Do  not  use  modules  of  different 
specifications in the same system.  

Содержание HIP-215NKHE5

Страница 1: ...le to avoid the hazard of injury and damage to the module Do not puncture or damage the back sheet of a module to avoid the hazard of electric shock and fire To avoid the hazard of electric shock and injury children and unauthorized persons should not be allowed near the installation of PV modules To avoid the hazard of electric shock and injury be sure to completely ground all modules To avoid th...

Страница 2: ... and use of PV modules Operating Conditions SANYO recommends that modules be operated within the following Operating Conditions An installation location with conditions beyond the Operating Conditions or with other Special Conditions see below should be avoided Operating Conditions of SANYO modules are as follows 1 The modules should be operated only in terrestrial applications No space or other S...

Страница 3: ...maximum possible system open circuit voltage Check your local codes for requirements Earth Ground Wiring The kind of the earth construction shall conform to IEC61730 1 Bonding shall be by a positive means such as clamping riveting bolted or screwed connections or welding soldering or brazing The bonding connections shall penetrate all non conductive coatings such as paint anodized coatings or vitr...

Страница 4: ...injury The return of any modules will not be accepted by SANYO unless prior written authorization has been given by SANYO As part of our policy of continuous improvement SANYO reserves the right to change product specifications at any time without prior notice For further information please visit www sanyo solar eu or www sanyo com or contact a SANYO Authorized Representative 2008 Nov SANYO Electr...

Страница 5: ...1 5 57 5 54 5 50 Cell Type HIT HIT HIT HIT Maximum System Voltage Voc V 1000 1000 1000 1000 Maximum over current protection rating A 15 15 15 15 Factory Installed Bypass Diodes 3 3 3 3 HIT Hetero junction with Intrinsic Thin layer Mechanical Specifications Model HIP 215NKHE5 HIP 215NKHE5 2 HIP 210NKHE5 HIP 210NKHE5 2 HIP 205NKHE5 HIP 205NKHE5 2 HIP 200NKHE5 HIP 200NKHE5 2 Length mm Width mm Height...

Страница 6: ...mm Optional Mounting Range Dimension in mm Optional Mounting Range Note Fixing span is 1040mm or less Note Fixing span is 1040mm or less Figure 2 2 Optional Mounting Range Figure 2 3 Optional Mounting Range Figure 3 Configuration of Junction Box ...