Electrical Specifications

HIP-205BE11, -205BE11-BO2, -200BE11, -200BE11-BO2, -195BE11, 

-195BE11-BO2, -190BE11, -190BE11-BO2, -186BE11, -186BE11-BO2, 

-180BE11, -180BE11-BO2 )

Model

HIP

- 205BE11,

- 205BE11- BO2

HIP

- 200BE11,

- 200BE11- BO2

HIP

- 195BE11,

- 195BE11- BO2

HIP

- 190BE11,

- 190BE11- BO2

HIP

- 186BE11,

- 186BE11- BO2

HIP

- 180BE11,

- 180BE11- BO3

Cell Number in Series [Pieces]

96

96

96

96

96

96

Maximum Power (Pmax) [W]

205

200

195

190

186

180

Maximum Power Voltage (Vmp) [V]

56.7

55.8

55.3

54.8

54.4

54.0

Maximum Power Current (Imp) [A]

3.62

3.59

3.53

3.47

3.42

3.33

Open Circuit Voltage (Voc) [V]

68.8

68.7

68.1

67.5

67.0

66.4

Short Circuit Current (Isc) [A]

3.84

3.83

3.79

3.75

3.71

3.65

Cell Type

Maximum System Voltage [V]

1000

1000

1000

1000

1000

1000

Factory Installed Bypass Diode

Yes

Yes

Yes

Yes

Yes

Yes

Weight [kg]

14

14

14

14

14

14

HIT* (hybrid of a- Si and mono c- Si)

Electrical Specification

*HIT= Hetero junction with Intrinsic Thin-layer

Note: The values in the above table are nominal.

4

Printed in Europe 20.10.2006

Module wiring

> The maximum number of HIP- xxxNHE5, xxxNHE5-BO2 

modules that can be wired in series is seventeen (17).

> The maximum number of HIP-

BE11, xxxBE11-BO2

modules that can be wired in series is thirteen (13).

> When your PV system includes other components 

(batteries, charge controllers, inverters, etc.), be sure to 

follow the safety recommendations of their manufactures.

> These modules contain factory installed bypass diodes. 

If these modules are incorrectly connected to each other, 

the bypass diodes or cable or junction box may be 

damaged.

Array Wiring

The term “array” is used to describe the assembly of 

several modules on a support structure with associated 

wiring. 

Use copper wire that is sunlight resistant and is insulated 

to withstand the maximum possible system open circuit 

voltage. Check your local codes for requirements.

Electrical Protection

The HIP- xxxNHE5, -xxxNHE5-BO2, 

--xxxBE11, -xxxBE11-BO2 Module complies with the 

requirements of Electrical protection Class II.

If necessary, the module or array can be grounded. 

Module Terminations

A junction box as terminal enclosure is equipped for 

electrical connections on SANYO modules.

The HIP- xxxNHE5, -xxxNHE5-BO2, -xxxBE11, -

xxxBE11-BO2 modules are equipped with MC plugs as 

terminal enclosure. 

Use these MC plugs for electrical connections.

Please contact your local dealer with questions 

regarding other electrical connections for modules.

negative ( - )

positive ( + )

Figure3: Configuration of 

junction box

Connector

(MC Plug)

Cable

Junction box configuration and 

description of terminals (for reference)

Modules equipped with one junction box contain 

terminals for both positive and negative polarity, and 

bypass diodes.

Two terminals are dedicated to each polarity (with the 

polarity symbols engraved onto the body of the junction 

box ) (see Fig3).

Содержание HIP-215NHE5

Страница 1: ...s and burns are still a potential hazard To avoid the hazard of electric shock and injury cover all over the front surface of PV modules with a dense opaque material such as the cardboard box during installing and handling modules The shock hazard increases as modules are connected in parallel producing higher current The shock hazard increases as modules are connected in series producing higher v...

Страница 2: ...les please contact your local dealer GENERAL SAFETY Follow all permission installation and inspection requirements Before installing module contact appropriate authorities to determine permission installation and inspection requirements that should be followed This should be done not only for installations in conjunction with buildings but also for marine and motor vehicle applications for which a...

Страница 3: ... protected to help ensure personal safety and to prevent its damage All modules connected in series should be of the same model number type Do not connect modules in parallel without using a connection box 3 Printed in Europe 20 10 2006 Metal fitting Spring washer Flat washer Module Mounting Structure Rail M6 Bolt setscrew M6 Nut Metal fitting 4 places Mounting Structure Rail Between Modules Mount...

Страница 4: ... to follow the safety recommendations of their manufactures These modules contain factory installed bypass diodes If these modules are incorrectly connected to each other the bypass diodes or cable or junction box may be damaged Array Wiring The term array is used to describe the assembly of several modules on a support structure with associated wiring Use copper wire that is sunlight resistant an...

Страница 5: ...or the systems within the specified system voltage so that you don t need any other additional bypass diodes Contact your authorized SANYO distributor or dealer for proper diode type if necessary to add or change diodes due to system specification MAINTENANCE Some maintenance is recommended to maintain optimal output performance of solar cell modules If the module surface becomes dirty it may caus...

Страница 6: ... Corporation TEL 82 2 777 6468 FAX 82 2 777 5997 SANYO Energy Taiwan Co Ltd TEL 886 2 8780 8810 FAX 886 2 8780 8850 SANYO Thailand Co Ltd TEL 66 2 248 3491 FAX 66 2 246 7250 SANYO Sales Marketing Corporation TEL 81 6 6992 1482 FAX 81 6 6992 1553 Africa SANYO South Africa Pty Ltd TEL 27 11 448 2929 FAX 27 11 448 2860 Middle East SANYO Gulf Fze TEL 971 4 8873939 FAX 971 4 8873969 The return of any m...

Отзывы: