IMPORTANT!
Please read before installation

This air conditioning system meets strict safety and operating
standards.
For the installer or service person, it is important  to install or
service the system so that it operates safely and efficiently.

For safe installation and trouble-free operation, you must:

• Carefully read this instruction booklet before beginning.
• Follow each installation or repair step exactly as shown.
• Observe all local, state and national electrical  codes.
• Pay close attention to all warning and caution notices given in

this manual.

•The unit must be supplied with a dedicated electrical line.

This symbol refers to a hazard or unsafe practice which can result
in severe personal injury or death.

This symbol refers to a hazard or unsafe practice which can result
in personal injury or product or property damage.

If necessary, get help

These instructions are all you need for most installation sites and
maintenance conditions.
If you require help for a special problem, contact our sale/service
outlet or your certified dealer for additional instructions.

In case of improper installation

The manufacturer shall in no way be responsible for improper
installation or maintenance service, including failure to follow the
instructions in this document.

SPECIAL PRECAUTIONS

• During installation, connect before the refrigerant system and

then the wiring one; proceed in the reverse orden when removing
the units.

When wiring

ELECTRICAL

SHOCK CAN CAUSE SEVERE

PERSONAL INJURY OR DEATH. ONLY QUALIFIED,
EXPERIENCED ELECTRICIANS SHOULD ATTEMPT
TO WIRE THIS SYSTEM.

• Do not supply power to the unit until all wiring and tubing are

completed or reconnected and checked, to ensure the grounding.

• Highly dangerous electrical voltages are used in this system.

Carefully refer to the wiring diagram and these instructions when
wiring.
Improper connections and inadequate grounding can cause

accidental injury and death

.

Ground the unit 

following local electrical codes.

• The Yellow/Green wire cannot be used for any connection

different from the ground connection.

• Connect all wiring tightly. Loose wiring may cause overheating

at connection points and a possible fire hazard.

• Do not allow wiring to touch the refrigerant tubing, compressor,

or any moving parts of the fan.

• Do not use multi-core cable when wiring the power supply and

control lines. Use separate cables for each type of line.

When transporting

Be careful when picking up and moving the indoor and outdoor
units. Get a partner to help, and bend your knees when lifting to
reduce strain on your back. Sharp edges or thin aluminium fins on
the air conditioner can cut your fingers.

When installing...

• Keep all tubing runs as short as possible.
• Use the flare method for connecting tubing.
• Apply refrigerant lubricant to the matching surfaces of the flare

and union tubes before connecting them;  screw by hand and
then tighten the nut with a torque wrench for a leak-free
connection.

• Check carefully for leaks before starting the test run.

NOTE:

Depending on the system type, liquid and gas lines may be either
narrow or wide. Therefore, to avoid confusion, the refrigerant
tubing for your particular model is specified as narrow tube for
liquid, wide tube for gas.

When servicing

• Turn the power OFF at the main power board  before opening

the unit to check or repair electrical parts and wiring.

• Keep your fingers and clothing away from any moving parts.
• Clean up the site after the work, remembering to check that no

metal scraps or bits of wiring have been left inside the unit being
serviced.

• Ventilate the room during the installation or test

i

ng the refrigeration

system; make sure that, after the installation, no gas leaks are
present, because this could produce toxic gas and dangerous
if in contact with flames or heat-sources.

WARNING

CAUTION

WARNING

… In a ceiling

Make sure the ceiling is strong enough to hold the unit-weight.
It may be necessary to build a strong wooden or metal frame to
provide added support.

… In a room

Properly insulate any tubing run inside a room to prevent
"sweating", which can cause dripping and water damage to
walls and floors.

... In moist or uneven locations

Use a raised concrete base to provide a solid level foundation
for the outdoor unit. This prevents damage and abnormal
vibrations.

... In area with strong winds

Securely anchor the outdoor unit down with bolts and a metal
frame. Provide a suitable air baffle.

... In a snowy area (for heat pump-type systems)

Install the outdoor unit on a raised platform that is higher then
drifting snow. Provide snow vents.

When connecting refrigerant tubing

2

Содержание ECO-i SPW-UMR124EXH56

Страница 1: ...YSTEM AIR CONDITIONER SM940046 SPW UMR94EXH56 854 0 2264 SPW UMR224EXH56 854 0 2267 0 8180 439 0 June 2005 SPW UMR124EXH56 SPW UMR164EXH56 SPW UMR184EXH56 854 0 2266 Model No Product Code No SPW UMR74EXH56 854 0 2301 854 0 2263 854 0 2265 ...

Страница 2: ...ow wiring to touch the refrigerant tubing compressor or any moving parts of the fan Do not use multi core cable when wiring the power supply and control lines Use separate cables for each type of line When transporting Be careful when picking up and moving the indoor and outdoor units Get a partner to help and bend your knees when lifting to reduce strain on your back Sharp edges or thin aluminium...

Страница 3: ...CB 17 5 2 How to replace PCB 18 5 3 How to replace EEPROM with EEPROM included in PCB service pack 19 5 4 Table of setting 21 6 SERVICING AND MAINTENANCE FUNCTIONS 22 6 1 Indoor unit refrigerant noise countermeasures 22 6 2 Outdoor unit noise countermeasures EEPROM 05 22 7 TROUBLE DIAGNOSIS 23 7 1 Contents of remote controller switch alarm display 23 7 2 Outdoor unit control panel led display 25 7...

Страница 4: ...Refrigerant Refrigerant control Dimensions Weight Dimensions Height mm Width mm Depth mm Package dimensions Height mm Width mm Depth mm Volume m3 Weight Net kg Shipping kg DATA SUBJECT TO CHANGE WITHOUT NOTICE Power noise level measured at operating conditions 5mmH20 external static pressure 266 Electronic expansion valve Washable 54 52 49 Flare type 6 35 1 4 12 7 1 2 R410A 220 240V 50Hz 230V Cool...

Страница 5: ...ter Wide tube mm in Refrigerant Refrigerant control Dimensions Weight Dimensions Height mm Width mm Depth mm Package dimensions Height mm Width mm Depth mm Volume m3 Weight Net kg Shipping kg DATA SUBJECT TO CHANGE WITHOUT NOTICE 54 47 42 Electronic expansion valve Flare type 39 365 745 1292 0 35 35 220 240V 50Hz 230V Cooling Heating See catalogue with the requested matching Microprocessor I C the...

Страница 6: ... Wide tube mm in Refrigerant Refrigerant control Dimensions Weight Dimensions Height mm Width mm Depth mm Package dimensions Height mm Width mm Depth mm Volume m3 Weight Net kg Shipping kg DATA SUBJECT TO CHANGE WITHOUT NOTICE 571 266 RCS SH80AG RCS KR1AG Washable 9 52 3 8 R410A 15 88 5 8 3 and Auto See catalogue with the requested matching Microprocessor I C thermostat 1000 700 600 RCS BH80AG WL ...

Страница 7: ...BLK 37 BLK GRY 15 GRY VLT 15 WLT RED 30 RED YEL 101 Safety devices Type Operating temp Open C Run capacitor µF VAC Electronic expansion valve Coil Valve body Heat Exch Coil Coil Rows Fin pitch mm face area m2 DATA SUBJECT TO CHANGE WITHOUT NOTICE 0 45 110 Centrifugal fan 3RGB CO 45 30 5V 1 1 4 1060 2 Ø 160 L 240 UKV 18D31 1 8 Internal thermal protector 7AM 037 A 5 150 5K 450 UKV U030E Microprocess...

Страница 8: ...VLT 18 VLT RED 18 BRN YEL 105 Safety devices Type Operating temp Open C Close C Run capacitor µF VAC Electronic expansion valve Coil Valve body Heat Exch Coil Coil Rows Fin pitch mm face area m2 DATA SUBJECT TO CHANGE WITHOUT NOTICE UKV 25D32 0 168 1 6 3 Aluminium plate fin Copper tube 2 0 450 CR CRP50A B Centrifugal fan UKV U030E Microprocessor 2 Ø 160 L 240 3FGB CO 65 38 5V 1 1 4 1106 0 6 138 In...

Страница 9: ...T 18 VLT RED 18 BRN YEL 105 Safety devices Type Operating temp Open C Close C Run capacitor µF VAC Electronic expansion valve Coil Valve body Heat Exch Coil Coil Rows Fin pitch mm face area m2 DATA SUBJECT TO CHANGE WITHOUT NOTICE UKV U030E Microprocessor 2 Ø 160 L 240 3FGB CO 65 38 5V 1 1 4 1161 0 57 136 Internal thermal protector 7AM 037 A 5 150 5K CR CRP50A B Centrifugal fan 3 450 UKV 25D32 0 1...

Страница 10: ...sensor E3 Resistance kΩ Thermistor Room sensor TA TF BL Resistance kΩ Drain pump Model Rating Voltage Input Flow rate Safety float switch Model Contact rating 0 4 l min BI 1300 2725 230V AC DC 0 5A PC 309564003 220 240V 50Hz 14W ATR IIJ225A VAC 230V 50Hz AC 20V 0 2A AC 14V 0 3A PBC 41E S26 AC 10 2V 1 4A 136 C 0 C 15 0 5 PBC 41E S42 2 0 C 15 0 4 42 25 C 5 0 4 DHKTEC 35 S85N 10 ...

Страница 11: ...2 DIMENSIONAL DATA SPW UMR74 94 124EXH56 11 ...

Страница 12: ...SPW UMR164 184 224EXH56 12 ...

Страница 13: ...3 ELECTRICAL DATA 3 1 Electric Wiring Diagram 7P terminal board 1 L 2 N U1 U2 R1 R2 wiring remote controller power supply inter unit control 13 ...

Страница 14: ...the unit to be operated by the remote controller even if it is not CN072 connected to an outdoor unit In this case alarm E04 which indicates trouble in the serial communication between the indoor and outdoor unit does not occur CHK 2P plug white Test pin Short circuiting this pin allows the indoor FM H fan speed drain pump CN071 flap motor F1 position and electronic expansion valve full open posit...

Страница 15: ...4 FUNCTIONS 4 1 Room temperature control 15 ...

Страница 16: ...4 2 Automatic control for heating and cooling 16 ...

Страница 17: ... Read Only Memory EEPROM is a component in which the various information necessary for functionning can be electronically written or erased This component holds informations that is essential for the running of the unit and must be handled with care D002 led lamp red 17 ...

Страница 18: ...5 2 How to replace PCB 18 ...

Страница 19: ...5 3 How to replace EEPROM with EEPROM included in PCB service pack 19 ...

Страница 20: ...20 ...

Страница 21: ...5 4 Table of settings 21 ...

Страница 22: ...6 SERVICING AND MAINTENANCE FUNCTIONS 22 ...

Страница 23: ...7 TROUBLE DIAGNOSIS 7 1 Contents of remote controller switch alarm display 23 ...

Страница 24: ...24 ...

Страница 25: ...7 2 Outdoor unit control panel LED display 25 ...

Страница 26: ...7 3 Trouble indications and inspection points 26 ...

Страница 27: ...27 ...

Страница 28: ...7 4 Remote controller servicing functions 28 ...

Страница 29: ...7 5 Super W Multi alarm codes 29 ...

Страница 30: ...30 ...

Страница 31: ...31 ...

Страница 32: ...32 ...

Страница 33: ...33 ...

Страница 34: ...34 ...

Страница 35: ...7 6 Inspection of parts 35 ...

Страница 36: ...36 ...

Страница 37: ...37 ...

Страница 38: ...SANYO Airconditioners Europe S r l Via Bisceglie No 76 20152 Milano Italy ...

Отзывы: