Outdoor Unit : CMH3172A
Indoor Unit
: KMHS0972
×
4
Power Supply : 230V Single Phase 60Hz
< Heating Capacity >
TH : Total Heating Capacity (BTU/h)
1. Rating conditions (#) : Indoor Unit Entering Air Temp. 70 °F (21.1 °C) D.B.
: Outdoor Ambient Temp. 47 °F (8.3 °C) D.B. / 43 °F (6.1 °C) W.B.
2.
3. Above data represents the value when the operation frequency of a compressor is fixed.
Above data does not take Defrost Operation, Overload Prevention Protection, and/or Cold Air
Prevention Protection during heating operation into account. For this reason, the value may vary
from the actual heating characteristics.
NOTE
RATING CAPACITY:
32,000 BTU/h
AIR FLOW RATE:
1,130 CFM
OUTDOOR
INDOOR
ENT. TEMP. °F (°C)
AMBIENT TEMP. °F (°C)
W.B.
60
65
70
75
80
(15.6)
(18.3)
(21.1)
(23.9)
(26.7)
0 (-17.8)
TH
18,270
18,260
18,230
18,200
18,150
3 (-16.1)
TH
18,860
18,850
18,820
18,790
18,740
8 (-13.3)
TH
20,260
20,250
20,230
20,200
20,150
13 (-10.6)
TH
21,720
21,710
21,680
21,650
21,600
18 (-7.8)
TH
23,310
23,300
23,280
23,240
23,190
23 (-5.0)
TH
24,970
24,960
24,940
24,910
24,850
28 (-2.2)
TH
26,690
26,690
26,660
26,630
26,570
33 (0.6)
TH
28,460
28,450
28,430
28,400
28,340
38 (3.3)
TH
30,190
30,190
30,170
30,140
30,080
43 (6.1)
TH
32,020
32,020
# 32,000
31,960
31,900
48 (8.9)
TH
33,850
33,850
33,840
33,800
33,740
53 (11.7)
TH
35,680
35,680
35,670
35,630
35,570
58 (14.4)
TH
37,420
37,430
37,420
37,380
37,320
63 (17.2)
TH
39,190
39,200
39,190
39,160
39,100
65 (18.3)
TH
39,870
39,880
39,880
39,850
39,790