Outdoor Unit : CMH2472A
Indoor Unit
: X XM XMHS1272
Power Supply : 230V Single Phase 60Hz
< Heating Capacity >
TH : Total Heating Capacity (BTU/h)
1. Rating conditions (#) : Indoor Unit Entering Air Temp. 70 °F (21.1 °C) D.B.
: Outdoor Ambient Temp. 47 °F (8.3 °C) D.B. / 43 °F (6.1 °C) W.B.
2.
3. Above data represents the value when the operation frequency of a compressor is fixed.
Above data does not take Defrost Operation, Overload Prevention Protection, and/or Cold Air
Prevention Protection during heating operation into account. For this reason, the value may vary
from the actual heating characteristics.
NOTE
M
F
C
8
1
9
:
E
T
A
R
W
O
L
F
R
I
A
h
/
U
T
B
0
0
4
,
8
2
:
Y
T
I
C
A
P
A
C
G
N
I
T
A
R
R
O
O
D
N
I
R
O
O
D
T
U
O
ENT. TEMP.
o
F (
o
.
P
M
E
T
T
N
E
I
B
M
A
)
C
o
F (
o
C)
0
8
5
7
0
7
5
6
0
6
.
B
.
W
(15.6)
(18.3)
(21.1)
(23.9)
(26.7)
0 (-17.8)
TH
16,030
16,040
16,050
16,040
16,020
CI
1.45
1.52
1.60
1.67
1.74
3 (-16.1)
TH
16,550
16,560
16,570
16,560
16,540
CI
1.47
1.54
1.62
1.69
1.77
8 (-13.3)
TH
17,790
17,810
17,820
17,810
17,790
CI
1.50
1.59
1.67
1.75
1.84
13 (-10.6)
TH
19,080
19,100
19,110
19,100
19,090
CI
1.55
1.64
1.73
1.82
1.90
18 (-7.8)
TH
20,500
20,520
20,530
20,530
20,510
CI
1.59
1.69
1.79
1.89
1.98
23 (-5.0)
TH
21,990
22,010
22,020
22,010
22,000
CI
1.64
1.75
1.85
1.96
2.06
28 (-2.2)
TH
23,530
23,560
23,570
23,560
23,540
CI
1.69
1.80
1.92
2.03
2.14
33 (0.6)
TH
25,130
25,150
25,160
25,150
25,130
CI
1.74
1.86
1.99
2.11
2.23
38 (3.3)
TH
26,700
26,730
26,740
26,730
26,090
CI
1.79
1.92
2.05
2.18
2.26
43 (6.1)
TH
28,360
28,390
#
28,400
28,390
26,750
CI
1.85
1.98
2.12
2.26
2.26
48 (8.9)
TH
30,050
30,070
30,080
30,070
27,350
CI
1.90
2.05
2.20
2.34
2.26
53 (11.7)
TH
31,740
31,770
31,780
31,190
27,890
CI
2.11
2.27
2.27
2.38
2.26
58 (14.4)
TH
33,370
33,400
33,410
31,730
28,330
CI
2.02
2.18
2.35
2.38
2.26
63 (17.2)
TH
35,050
35,080
35,090
32,170
28,700
CI
2.09
2.26
2.43
2.38
2.26
65 (18.3)
TH
35,700
35,730
35,740
32,310
28,810
CI
2.12
2.29
2.47
2.38
2.26
56