9-2. Electrical Wiring
B1
Indoor unit PCB
CRV
(CN91: WHT)
2P terminal base
Indoor unit
System controller
Accessary connector
Wire joint connection
2044_M_I
B2
B3
B4
B5
B6
U1
U2
How to connect electrical wiring
(1)
Connect B1, B2 to indoor PCB CRV connector
using accessary 2P connector. (*No polarity)
Total wire legth is less than 985 ft. and size is
AWG#18.
(2)
Connect B5, B6 to indoor unit 2P terminal base.
(*No polarity). Wire size is AWG#18.
●
Basic wiring
B1:
B2:
B3:
Not be used
B4:
Auxiliary of inter-unit control wiring
B5:
B6:
●
Terminals for remote monitoring
A1:
Input for turning on air conditioners concurrently.
A2:
Input for turning off air conditioners concurrently.
A3:
Common input for turning air conditioners on or off.
A4:
On operation state indicator output.
A5:
Alarm indicator output.
A6:
Common indicator output.
Basic wiring diagram of control wiring
●
Max. 64 indoor units and 30 outdoor units can be
connected in 1 system.
●
Up to 10 system controller can be connected in 1
system.
Fig. 9-3
Power supply: DC12V *No polarity
To CRV connector (CN91) on indoor PCB
Inter-unit control wiring. (Low voltage)
To indoor unit 2P terminal base (U1, U2)
*No polarity
Inter-unit
control wiring
System controller
RC1
1-1
2045_M_I
RC2
RC3
1-2
1-3
2-1
2-2
2-3
3-1
Fig. 9-4
A1
<Back side of system controller>
A2
A3
A4
A5
A6
B6
B5
B4
B3
B2
B1
Connector for
weekly timer
(Under the terminal)
3005_M_I