4. Service procedures
1
2
3
4
Section
– 67 –
SM830076
11) Symptoms: LCD on the remote controller displays “CHECK P03”.
(Alarm for unusual discharge temp. of compressor)
12) Symptom: LCD on the remote controller displays “CHECK P04”.
(High-pressure switch activation warning)
0343_M_I
Start
Unusual discharge gas temperature
• Refrigerant shortage
• Clogged refrigerant circuit
• Electronic refrigerant control
valve defect (indoor unit)
No
Yes
No
Yes
0344_M_I
Start
Are there connection defects in
the wiring?
High-pressure switch defect
Repair the wiring.
The system does not operate again.
High-pressure switch activation
(Both cooling and heating)
• Electronic refrigerant control valve
defect
• Refrigerant over-charged
(Cooling)
• Outdoor unit, heat exchanger dirty,
clogged
• Outdoor unit air short
• Outdoor fan stopped
(Heating)
• Outdoor unit air short
• Indoor unit, heat exchanger dirty,
clogged
• Large pipe side service valve
closed
• Indoor fan stop
• Air filter clogged