background image

Be sure to use a manifold valve for
air purging. If it is not available, use
a stop valve (field supply) for this
purpose. The “Hi” knob of the mani-
fold valve must always be kept closed.

Insulated tubes

Drain hose

Clamp

Hi

Lo

I

n

door 

un

it

O

u

tdoor 

un

it

Ma

n

ifold valve

(Excl

us

ively for R410A)

Pre

ssu

re

g

a

ug

e

Vac

uu

m p

u

mp

Char

g

i

ng

 ho

s

e

(Excl

us

ively for R410A)

Vac

uu

m p

u

mp adapter

(Excl

us

ively for R410A)

(with rever

s

e flow preve

n

tio

n

)

17

(1) At this time, the 2 refrigerant tubes (and electrical wire

if local codes permit) should be taped together with
armoring tape. The drain hose may also be included
and taped together as 1 bundle with the tubing.

(2) Wrap the armoring tape from the bottom of the outdoor

unit to the top of the tubing where it enters the wall. As
you wrap the tubing, overlap half of each previous tape
turn. (Fig. 25)

(3) Clamp the tubing bundle to wall, using 1 clamp approx.

every 47" (120 cm).

Do not wind the armoring tape too tightly, since this will
decrease the heat insulation effect. Also, be sure the con-
densation drain hose splits away from the bundle and drips
clear of the unit and the tubing.

5-7.  Finishing the Installation

After finishing insulating and taping over the tubing, use
sealing putty to seal off the hole in the wall to prevent rain
and draft from entering. (Fig. 26)

NOTE

5-6.  Taping the Tubes

Fig. 25

6.  Air Purging

Air and moisture remaining in the refrigerant system have
undesirable effects as indicated below. Therefore, they must
be purged completely.

G

pressure in the system rises

G

operating current rises

G

cooling (or heating) efficiency drops

G

moisture in the air may freeze and block capillary tubing

G

water may lead to corrosion of parts in the refrigerant system

I

Air Purging with a Vacuum Pump (for Test Run)

(1) Check that each tube (both narrow and wide tubes)

between the indoor and outdoor units have been proper-
ly connected and all wiring for the test run has been
completed. Note that both narrow and wide tube service
valves on the outdoor unit are kept closed at this stage.

(2) Using an adjustable wrench or box wrench, remove the

valve caps from the service valve on both narrow and
wide tubes.

(3) Connect a vacuum pump and a manifold valve (with

pressure gauges) to the service port on the wide tube
service valve. (Fig. 27)

CAUTION

CAUTION

The service port on the wide tube service valve
uses a Schrader core valve to access the
refrigerant system. The valve core is similar to
those used in automobile tires. Therefore, be
sure to use a vacuum hose connector which
has a push-pin inside.

Fig. 27

Fig. 26

Apply p

u

tty here

T

u

bi

ng

08-193 XHS1271  9/12/08  2:58 PM  Page 17

Содержание CH1271

Страница 1: ...TALL THE OUTDOOR UNIT 14 4 1 Wiring Instructions for the Outdoor Unit 5 REFRIGERANT TUBING 15 5 1 Use of the Flaring Method 5 2 Flaring Procedure with a Flare Tool 5 3 Caution before Connecting Tubes Tightly 5 4 Connecting Tubing between Indoor and Outdoor Units 5 5 Insulation of Refrigerant Tubing 5 6 Taping the Tubes 5 7 Finishing the Installation 6 AIR PURGING 17 I Air Purging with a Vacuum Pum...

Страница 2: ...orting Be careful when picking up and moving the indoor and out door units Get a partner to help and bend your knees when lifting to reduce strain on your back Sharp edges or thin alu minum fins on the air conditioner can cut your fingers When Installing In a Ceiling or Wall Make sure the ceiling wall is strong enough to hold the unit s weight It may be necessary to construct a strong wood or meta...

Страница 3: ...for the indoor and outdoor units and make sure all accessory parts listed are with the system before beginning 1 1 Tools Required for Installation not supplied 1 Standard screwdriver 2 Phillips head screwdriver 3 Knife or wire stripper 4 Tape measure 5 Carpenter s level 6 Sabre saw or key hole saw 7 Hacksaw 8 Core bits 9 Hammer 10 Drill 11 Tube cutter 12 Tube flaring tool 13 Torque wrench 14 Adjus...

Страница 4: ...etailed in Table 3 and Fig 2 G install the indoor unit more than 3 3 1 m away from any antenna or power lines or connecting wires used for television radio telephone security system or intercom Electrical noise from any of these sources may affect operation Fig 1 3 3 ft 1m 1m 1m 3 3 ft 1m 3 3 ft 3 3 ft 3 3 ft 1m Fig 2 Tubing length L Elevation difference H Outdoor unit Indoor unit WARNING To preve...

Страница 5: ... life Figs 5a and 5b Outdoor unit Hot air Heat source Exhaust fan NO Fig 3 Air intake Min 2 5 cm Air discharge Min 2 5 cm Min 8 20 cm Valve side Min 10 25 cm Min 7 2 m Min 7 2 m Ground Obstacle Obstacle above Air discharge Min 2 5 cm Air intake Air intake Concrete or equal About 4 10 cm Min 4 10 cm Anchor bolts 4 pcs About 1 4 40 cm Cushion rubber Fig 5a Drain holes CAUTION A solid base must not c...

Страница 6: ...m The dia gram shows the relationship between the positions of the suspension fitting unit and panel Fig 6 2 3 3 Placing the Unit Inside the Ceiling 1 Be sure to remove the fan protection 4pcs for transportation before hanging up the indoor unit 2 When placing the unit inside the ceiling determine the pitch of the suspension bolts using the supplied full scale installation diagram Fig 6 3 Tubing a...

Страница 7: ... drain hose first place 1 of the 2 hose bands over the unit drain port and the other hose band over the hard PVC pipe not supplied Then connect both ends of the supplied drain hose Fig 6 5 3 On the unit drain side grasp the hose band with pliers and insert the drain hose all the way to the base G If other commercially available hose bands are used the drain hose may become pinched or wrinkled and ...

Страница 8: ...osition 1 Check that the ceiling hole is 23 5 8 600 mm 23 5 8 600 mm Fig 6 11 2 Confirm that the position of the indoor unit and the ceiling as shown in the diagram If the positions of the ceiling sur face and unit do not match air leakage water leakage flap operation failure or other problems may occur Fig 6 11 The drain pump will continue to operate for a minimum of 6 min utes after the FS 3P co...

Страница 9: ...en the unit and the ceiling panel or between the ceiling panel and the ceiling surface G If there is a gap between the panel and the ceiling leave the ceiling panel attached and make fine adjustments to the installation height of the unit to eliminate the gap with the ceiling CAUTION Fig 6 17 Fig 6 18 Fig 6 19 Corner cover Indicator cover Press Pull up 2 1 latch Temporary latches Temporary DRAIN m...

Страница 10: ...l will not be received G If the connectors are not connected the auto flap will not operate Be sure to connect them securely A Attaching the corner cover 1 Check that the safety strap from the corner cover is fas tened to the ceiling panel pin as shown in the figure Fig 6 23 2 Use the supplied screws to attach the corner cover to the ceiling panel B Attaching the air intake grille G To install the...

Страница 11: ... 4 lists recommended wire lengths and diameters for power supply systems Refer to the wiring system diagram Fig 7a or Fig 7b for the meaning of A B and C in Table 4 Refer to your local codes or in the absence of local codes see the National Electric Code ANSI NFPA70 NOTE 11 3 6 5 Checking After Installation G Check that there are no gaps between the unit and the ceiling panel or between the ceilin...

Страница 12: ...may affect the operation G To avoid the risk of electric shock each air con ditioner unit must be grounded G For the installation of a grounding device please observe local electrical codes G Grounding is necessary especially for units using inverter circuits in order to release charged electricity and electrical noise caused by high tension Otherwise electrical shock may occur G Place a dedicated...

Страница 13: ... fix it securely with the removed terminal screw using a screwdriver Loose wiring may cause the ter minal to overheat or result in unit malfunction A fire hazard may also exist Therefore be sure all wiring is tightly connected WARNING Fig 9 STRIP SIZE 9 32 7 mm ACTUAL SIZE Fig 8 Fig 10 Solid wire Loop Insulation Strip 15 16 25 mm 1 3 2 Earth screw Clamping strap Conduit Inter unit Power wiring Loc...

Страница 14: ...e Outdoor Unit First refer to Section 2 Installation Site Selection 4 1 Wiring Instructions for the Outdoor Unit Regulations on wire size differ from locality to locality For field wiring requirements please refer to your local electrical codes Make sure that the installation fully complies with all local and national regulations 1 Remove access panel C Fig 14 2 Connect the inter unit and power su...

Страница 15: ... tool Figs 17 and 18 Use RIDGID or equivalent A good flare should have the following characteristics G inside surface is glossy and smooth G edge is smooth G tapered sides are of uniform length 5 3 Caution before Connecting Tubes Tightly a Be sure to apply a sealing cap or water proof tape to prevent dust or water from getting into the tubes before they are used b Be sure to apply refrigerant lubr...

Страница 16: ... tubing connec tions with the flare insulation 1 8 T3 supplied Then wind the other flare insulation 3 16 T5 supplied Finally fasten the insulation at both ends with the sup plied vinyl ties Fig 23 Insulation material The material used for insulation must have good insula tion characteristics be easy to use be age resistant and must not easily absorb moisture After a tube has been insulat ed never ...

Страница 17: ...tubing use sealing putty to seal off the hole in the wall to prevent rain and draft from entering Fig 26 NOTE 5 6 Taping the Tubes Fig 25 6 Air Purging Air and moisture remaining in the refrigerant system have undesirable effects as indicated below Therefore they must be purged completely G pressure in the system rises G operating current rises G cooling or heating efficiency drops G moisture in t...

Страница 18: ...valve stem on the narrow tube service valve counter clockwise by 90 degrees 1 4 turn for 10 seconds and then turn the stem clockwise to close it again Fig 28 7 Leak test all joints at the tubing both indoor and outdoors with soapy water Bubbles indicate a leak Tighten the joint more when leaks then check if there is no leak Be sure to wipe off the soap with a clean cloth 8 With the hex wrench turn...

Страница 19: ...utes the system shifts into cooling operation and cool air will start to be felt Cooling mode test run is unaffected by the room tempera ture 3 Press the ON OFF operation button of the remote controller again to stop the test run Fig 29 4 Finally press the ACL Reset button of the remote controller to release it from Test Run mode to return to normal mode Fig 29 and oP 1 will disappear from the rem...

Страница 20: ...tube valve stem Then quickly stop the unit 5 Disconnect all gauges and hoses and replace the valve caps as they were before I Basic Functions of the Service Valves The basic functions of the service valves are given in Table 7 below Action Narrow Tube Service Valve 2 Way Wide Tube Service Valve 3 Way CLOSED Fully OPEN Fully OPEN Shipping Operating and test running the air conditioner Measuring pre...

Страница 21: ... to make sure that the air conditioner operates from that location The indoor unit should make a beeping sound to indicate that it has received the signal Fig 36 To take out the remote control unit pull it forward I Service Valve Connections a Temporary connection Screw in 3 5 turns by hand Fig 34 b To fasten the flare nuts apply specified torque as Table 8 and Fig 35 Table 8 Fig 34 Fig 35 CAUTION...

Страница 22: ...press and hold the ACL Reset button with a pointed object such as the tip of a pen After 5 seconds release the ACL button first then release the HIGH POWER and 1HR TIMER but tons oP 1 Test Run appears blinking in the remote controller clock display area 4 Each time the 1HR TIMER button is pressed the display changes as shown below Press this but ton 2 times to change the display to oP 7 Address se...

Страница 23: ... Filaire This wired remote controller is designed for both the COOL DRY HEAT Model and COOL DRY Model indoor unit Before using the remote controller be sure to confirm the model type specified on the front cover of the INSTRUCTION MANUAL supplied with the indoor unit Save These Instructions Conserver ce mode d emploi ...

Страница 24: ...ound or earth wire or through the supply wiring 3 Wiring must be done by a qualified electrician SAFETY INSTRUCTIONS Read this Instruction Manual carefully before using this air conditioner If you still have any difficulties or problems consult your dealer for help This air conditioner is designed to give you comfortable room conditions Use this only for its intended purpose as described in this I...

Страница 25: ...ing 60 86 F When set to 80 F temperature indication 4 Timer 24 hour clock with ON OFF program Timer ON Timer OFF Timer 1 hour OFF Timer 5 NIGHT SETBACK 6 Flap angle indication Sweep indication Displayed when indoor unit sensor is in use Displayed when operating NIGHT SETBACK mode Displayed when setting temperature Displayed when temperature is shown Displayed when setting timer Symbols OI 119 3 EG...

Страница 26: ...e The temperature setting changes by 2 F each time one of the TEMP buttons is pressed NIGHT SETBACK button For details see 5 Night Setback Mode When you press this button in the HEAT DRY or COOL mode the mark appears in the display and the remote control unit will automatically adjust the set temperature to save energy Timer and Present Time setting buttons First press the SET button to select the...

Страница 27: ...itioner works only as a circulation fan The indoor fan runs continuously when the system is in normal operation It does not turn off when the desired room temperature is reached If Night Set Back mode is selected the fan will turn off intermittently during cooling operation in order to control air flow NOTE SENSOR button When you press this button use a small tipped object such as a ballpoint pen ...

Страница 28: ...desired STEP 1 Press the MODE selector button and select the desired mode For heating operation For dehumidifying operation For cooling operation For fan only operation STEP 2 To start the air conditioner press the ON OFF operation button STEP 3 Press the TEMP setting buttons to change the temperature setting to the desired temperature Adjustable temperature range 86 F max 60 F min STEP 4 Set the ...

Страница 29: ...ontrol follow these steps STEP 1 Press the MODE selector button to switch to the fan mode STEP 2 Press the ON OFF operation button STEP 3 Press the FAN SPEED selector button to select the fan speed of your choice or STEP 2 STEP 1 STEP 3 When the night setback mode is selected the air conditioner automatically raises the temperature setting 2 F when 30 minutes have passed after the selection was ma...

Страница 30: ...hange automatically back to show the present time after about 10 sec 3 Press the ON OFF button to start the air conditioner The present time is displayed 4 Press the TIMER SELECT button twice to set OFF time The present time and are displayed OFF TIME Present time Operation Indication 1 Press the SET button once The timer indication alone flashes and the previous set time is only displayed 2 Press...

Страница 31: ...nstructions supplied with the indoor unit 5 Remove the terminal cover screws then remove the cover At this time take care not to drop the cover Fig 8 6 Pull in the wire harness from the remote controller as shown in Fig 8 b Remove the putty before wiring After wiring make sure to restore the putty 7 Insert the wire harness 4P terminal into the control box PCB connector RC Fig 8 a 8 Install the ter...

Страница 32: ...n operates the OFF Timer is cancelled and the unit will stop operating one hour later 2 Operation together with the daily ON OFF repeat timer The 1 Hour OFF Timer setting is given priority over the DAILY ON OFF REPEAT setting ADJUSTING THE AIRFLOW DIRECTION The vertical airflow can be adjusted by moving the flap with the remote control unit Do not move the flap with your hands Confirm that the rem...

Страница 33: ... The remote controller is set to Cool Dry Heat model at the time of shipment from the factory If the purchased air conditioner is a COOL DRY model follow the instructions on the label and change the switch on the reverse side of the remote controller unit to Cool Dry model Fig 1 The remote controller is also set to Single at the time of shipment from the factory For multiple use set the switch on ...

Страница 34: ...5 tab locations and disconnect the back plate of the remote controller by lift ing up slightly Fig 2 b The tabs are thin take care not to chip them 2 Use tapping screws to directly fasten the remote con troller back plate onto the wall Fig 6 3 Insert the connector into the PCB of the remote con troller unit and wrap the wire harness around the hook Fig 4 4 Use nippers or a similar tool to cut out ...

Страница 35: ... remote controller Fig 9 This starts the fan producing uncooled forced air with the 3 indicator lamps OPERATION lamp TIMER lamp and HIGH POWER lamp on the main unit blinking Fig 11 After 3 minutes the system shifts into cooling operation and cool air will start to be felt Cooling mode test run is unaffected by the room tempera ture 3 Press the ON OFF operation button of the remote controller again...

Страница 36: ...YO Commercial Solutions A Division of SANYO North America Corporation 1300 Michael Drive Suite A Wood Dale IL 60191 U S A Sanyo Canada Inc 1 300 Applewood Crescent Concord Ontario L4K 5C7 CANADA Oct 2008 T ...

Отзывы: