For the removal of the following components, perform any work after removing the indoor
unit (main body) from the ceiling.
Main body lower section
Heat exchanger sensor
Drain pump
Float switch
Turbo fan
Fan motor
Heat exchanger
1. Perform the work after draining the water to prevent the water leakage from the drain pan.
•
Put a bucket, etc., under the drain cap and remove the drain cap to drain the water.
(Fig. 16)
2. Refer to the installation instructions for recovery of refrigerant or removal of the power
cable or tubing.
7-3-6. Remove the main body lower section.
(1) Remove the 4 screws. (Fig. 16)
(2) Remove the 2 screws. (Fig. 17)
(3) Disconnect the connector CN03 (DCM 6P) in the power box. (Fig. 18)
(4) Lift the main body lower section and remove it from the main body upper section.
Screw
Fig.16
Fig.18
Fig.17
Drain cap
Main body lower section
Main body lower section
Screw
Screw
Main body lower section
Main body
upper section
Screw
CN03
Screw
NOTE
43