16
5-4. Connecting Tubing between Indoor and
Outdoor Units
a)
Tightly connect the indoor side refrigerant tubing exten-
ded from the wall with the outdoor side tubing. (Fig. 21)
b)
To fasten the flare nuts, apply specified torque as:
Table 5
5-5. Insulation of Refrigerant Tubing
To prevent heat loss and wet floors due to dripping of con-
densation,
both tubes must be well insulated with a
proper insulation material.
The thickness of the insulation should be a minimum 5/16"
(8 mm). (Fig. 22)
IMPORTANT
Tube Dia.
Tightening Torque
1/4" (6.35 mm)
Approx. 120 – 160 lbs·in (140 – 180 kgf·cm)
3/8" (9.52 mm)
Approx. 300 – 360 lbs·in (340 – 420 kgf·cm)
1/2" (12.70 mm)
Approx. 430 – 540 lbs·in (490 – 610 kgf·cm)
5/8" (15.88 mm)
Approx. 590 – 710 lbs·in (680 – 820 kgf·cm)
Fig. 21
Fig. 22
I
nsu
latio
n
Mi
n
.
5/16"
(
8
mm)
Thick
n
e
ss
:
mi
n
. 5/16"
(
8
mm)
Taping the flare nuts
Wind the insulation tape around the flare nuts at the
tube connections. Secondly cover up the tubing connec-
tions with the flare insulation (1/8" (T3, supplied)). Then
wind the other flare insulation (3/16" (T5, supplied)).
Finally, fasten the insulation at both ends with the sup-
plied vinyl ties. (Fig. 23)
Insulation material
The material used for insulation must have good insula-
tion characteristics, be easy to use, be age resistant,
and must not easily absorb moisture.
After a tube has been insulat-
ed, never try to bend it into a
narrow curve because it can
cause the tube to break or
crack.
CAUTION
Fig. 23
Fig. 24
Never grasp the drain or refrigerant connecting out-
lets when moving the unit.
Indoor unit
Outdoor unit
Spanner
Torque wrench
Insulation tape (supplied)
Flare insulation (3/16"(T5, supplied) )
Flare insulation (1/8"(T3, supplied) )
Tube insulation
(not supplied)
Vinyl tie (supplied)
Flare nut
The procedure used for installing
the insulation for both wide and
narrow tubes are the same.
Flare
insulation
Vinyl tie (supplied)
Insulation tape
Refrigerant tubing
and insulation
(not supplied)
Drain pipe and insulation
(not supplied)
Drain hose insulation
and vinyl tie
(supplied)
Drain hose
and hose band
(supplied)
08-193 XHS1271 9/12/08 2:58 PM Page 16
Содержание CH1271
Страница 68: ...INSTRUCTION MANUAL XHS1271 PNR XS1872 CH1271 XHS1872 PNR XS1872 CH1872 OI 852 6 4181 107 00 0 APPENDIX A A 1 ...
Страница 108: ...INSTRUCTION MANUAL STK RCS 7TWSU OI 852 6 4181 119 00 0 APPENDIX C A 3 ...