12
When connecting each power wire to the corresponding termi-
nal, follow the instructions “How to connect wiring to the termi-
nal” and fasten the wire securely tight with the fixing screw of
the terminal plate.
How to connect wiring to the terminal
a) For Indoor Unit
(1) Cut the wire end with a cutting pliers, then strip the insu-
lation to expose the wire about 9/32 in. (7 mm). See the
label (Fig. 28) near the terminal plate.
(2) Using a screwdriver, loosen the terminal screw on the ter-
minal plate.
(3) Insert the wire and tighten the terminal screw completely
using a screwdriver.
b) For Outdoor Unit
■
For solid core wiring (or F-cable)
(1) Cut the wire end with a cutting pliers, then strip the insu-
lation to expose the solid wire about 15/16 in. (25 mm).
(Fig. 29)
(2) Using a screwdriver, remove the terminal screw(s) on the
terminal plate.
(3) Using the pliers, bend the solid wire to form a loop suit-
able for the terminal screw.
(4) Shape the loop wire properly, place it on the terminal
plate and fix it securely with the removed terminal screw
using a screwdriver.
■
For stranded wiring
(1) Cut the wire end with a cutting pliers, then strip the insu-
lation to expose the stranded wiring about 3/8 in. (10 mm)
and tightly twist the wire ends. (Figs. 30 and 31)
(2) Using a screwdriver, remove the terminal screw(s) on the
terminal plate.
(3) Using a ring connector fastener or pliers, securely clamp
each stripped wire end with a ring connector. (Fig. 30)
(4) Place the ring connector wire, and replace and tighten the
removed terminal screw using a screwdriver. (Fig. 32)
Solid wire
Loop
Insulation
Strip 15/16" (25 mm)
Fig. 29
STRIP
SIZE
(ACTUAL
SIZE)
9/32" (7 mm)
Fig. 28
Stranded wire
Ring
Connector
Strip 3/8" (10 mm)
Fig. 30
Screw
Ring connector
Terminal plate
Wire
Special
washer
Fig. 32
Screw and
special washer
Ring
connector
Wire
WARNING
Loose wiring may cause the termi-
nal to overheat or result in unit mal-
function. A fire hazard may also
exist. Therefore, be sure all wiring
is tightly connected.
Twist wire ends
Fig. 31
01-385 AirCon 12/11/01 4:42 PM Page 12