9-4. Air Conditioner Operates, but Abnormalities are Observed
9-4-1. Only indoor fan does not run
9-4-2. Excessive cooling
Clean filter.
Air filter is clogged.
Fan speed is set to LOW.
•
NO
YES
Review cooling load estimate,
if performance of air conditioner is
normal.
•
Insulate both wide and
narrow tubes
separately and then
tape together.
Reduce cooling load
or replace the air
conditioner with
larger capacity.
Temperature
difference
is small.
YES
Charge
refrigerant
gas (R22).
•
•
Temperature difference between
suction and discharge air is
large enough (approx. 10 deg. or more).
Check for clogging of air filter.
Measure temperature of suction
and discharge air of air conditioner.
Wide and narrow tubes between
indoor unit and outdoor unit are
insulated.
•
Possibility of
gas shortage.
Set fan speed to either
HIGH or MEDIUM.
Check position of remote control unit.
Cool air from air conditioner
reaches position directly.
YES
Change position of
remote control unit.
•
•
Set temperature is suitable.
•
Remote control unit is placed
where it can detect room
temperature properly.
•
Change position of
remote control unit.
NO
Set temperature to
higher value using
temperature setting
buttons of the remote
control unit.
NO
000-215 SM (1-56) 7/5/00 2:49 PM Page 51
Содержание C0951
Страница 36: ...33 7 Printed circuit board POW KS095A POW KS095B for KS0951 ...
Страница 37: ...34 8 Printed circuit board POW KS125A POW KS095B for KS1251 ...
Страница 38: ...35 9 Printed circuit board POW KS1852 for KS1852 ...
Страница 39: ...36 10 Printed circuit board POW CL125 for CL0951 CL1251 and CL1852 ...
Страница 58: ...55 INSTRUCTION MANUAL KS0951 C0951 CL0951 KS1251 C1251 CL1251 KS1852 C1852 CL1852 APPENDIX ...