X
26
3. HOW TO INSTALL THE INDOOR UNIT
4-Way Air Discharge Semi-Concealed Type
(X Type)
3-1. Suspending the Indoor Unit
This unit uses a drain pump. Use a carpenter’s level to
check that the unit is level.
3-2. Preparation for Suspending
(1) Fix the suspension bolts securely in the ceiling
using the method shown in the diagrams (Figs. 3-1
and 3-2), by attaching them to the ceiling support
structure, or by any other method that ensures that
the unit will be securely and safely suspended.
(2) Follow Fig. 3-2 and Table 3-1 to make the holes in
the ceiling.
(3) Determine the pitch of the suspension bolts using
the supplied full-scale installation diagram. The
diagram and table (Fig. 3-3 and Table 3-2) show
the relationship between the positions of the sus-
pension fitting, the unit, and the panel.
Ty
p
e
Len
g
th
Ta
b
le
3
-2
U
n
it: i
n
ch (mm)
XH(W)2672R
(PNR-XH2442)
XH(W)3672R, XH(W)4272R
(PNR-XH3632)
A
6-3/16
(157)
6-3/16
(157)
7-5/32
(182)
7-5/32
(182)
10-9/32
(261)
11-15/32
(291)
12-1/8
(308)
13-1/16
(338)
4-7/8
(124)
4-7/8
(124)
D
E
B
C
Hole-in-anchor
Hole-in-plug
Concrete
Insert
Suspension bolt (M10 or 3/8")
(field supply)
Fig. 3-1
)
g
n
i
n
e
p
o
g
n
ili
e
C(
2
3
/
9-
2
3
Grille ce
n
ter
ns
io
n
bolt pitch)
e
p
s
u
S
(
6
1/
3
1-
9
2
X
Refri
g
era
n
t
t
u
bi
ng
s
ide
Drai
n
ho
s
e
s
ide
B
(
Sus
pe
ns
io
n
bolt pitch)
A (Ceili
ng
ope
n
i
ng
)
Fig. 3-2
C
D
6
1/
3
-
1
B
A
E
Sus
pe
ns
io
n
l
ug
Refri
g
era
n
t t
u
bi
ng
joi
n
t (
g
a
s
t
u
be
s
ide)
Refri
g
era
n
t t
u
bi
ng
joi
n
t
(liq
u
id t
u
be
s
ide)
Drai
n
co
nn
ectio
n
(other
s
ide)
(VP25)
Len
g
th
Ty
p
e
Ta
b
le
3
-1
U
n
it: i
n
ch (mm)
XH(W)2672R
(PNR-XH2442)
XH(W)3672R, XH(W)4272R
(PNR-XH3642)
A
32-9/32
(820)
43-11/16
(1,110)
22-9/32
(566)
33-11/16
(856)
B
Unit: inch
Fig. 3-3
Unit: inch
07-115 SSHP_II 5/7/07 3:59 PM Page 26