When a Buzzer Sounds
36
§
§
1
1
0
0
.
.
W
W
h
h
e
e
n
n
a
a
B
B
u
u
z
z
z
z
e
e
r
r
S
S
o
o
u
u
n
n
d
d
s
s
The buzzer sounds to indicate a UPS status error or change.
Check the sound pattern and see the following table for the countermeasure to be taken.
Sound Pattern
LCD Indication
LED Status
UPS Status
Countermeasure
Total Unit# Err
Fatal Error
Red
ALARM
: On
Red
WARNING
: On
The number of connected
UPS Units and the
setting value differ.
Set the number of connected UPS Units properly.
See Ҥ3.19 Setting Number of UPS Units Connected in
Parallel” in the LCD Panel Operating Manual.
Check that the unit-to-unit interface cable is connected
properly. See “§6.3.1 Wiring Between UPS Units.”
Fatal Error
Red
ALARM
: On
Red
WARNING
: On
The UPS has
malfunctioned.
Contact your sales representative or SANYO DENKI.
Byp Fuse Error
Red
ALARM
: On
Red
WARNING
: On
[During bypass power
supply]
MAIN MCCB
has
tripped (OFF).
Check the load capacity and whether there is a short
circuit.
If the load capacity is high, reduce the number of
connected load devices and set
MAIN MCCB
to “ON. ”
See “§9.4 Resetting the Main Breaker.”
AUX2 Error
Red
ALARM
: On
Red
WARNING
: On
The auxiliary power
supply has failed.
Contact your sales representative or SANYO DENKI.
LCD Error
Red
WARNING
: On
The LCD panel has
malfunctioned.
Contact your sales representative or SANYO DENKI.
Continuous tone
*
Batt Vol End
Red
ALARM
: On
Red
WARNING
: On
Battery discharge has
ended.
When the utility power is restored, the UPS will restart
automatically depending on the setting value of “UPS
Operation Upon Power Recovery” in the LCD panel setting
menu. See Ҥ3.7 Setting UPS Operation Upon Power
Recovery” in the LCD Panel Operating Manual.
Input Error
Input Freq Err
Input Vol Hi
Input Vol Low
Green
INPUT
:
Blinking
Green
BACKUP
: On
Power is being supplied
from the batteries
because of an input
voltage or input
frequency error.
Check that the input voltage and input frequency are
within rated ranges.
See “§12.4 Specifications.”
Is
MAIN MCCB
set to “OFF”? If it is set to “OFF,” set
it to “ON.”
2 sec.
** **
2 beeps 2 beeps
Test Condition
Testing
-
The UPS is performing a
battery test.
Wait for the battery test to end.
To stop the battery test, see “§4.1 Running Battery Test”
in the LCD Panel Operating Manual.
Continuous beeps
**********
・・・
Batt Vol Low
Green
INPUT
:
Blinking
Green
BACKUP
: On
The battery voltage is
low.
Check that the input voltage and input frequency are
within rated ranges.
See “§12.4 Specifications.”
Is
MAIN MCCB
set to “OFF”? If it is set to “OFF,” set
it to “ON.”
2 sec.
**** ****
・・・
4 beeps 4 beeps
Over Load
-
The load capacity of the
devices connected to the
terminal block of the
UPS exceeds the rated
capacity of the UPS.
Reduce the number of load devices connected to the
terminal block of the UPS.
Batt Vol Error
-
[When UPS starts]
The batteries are not
connected.
See Ҥ6.2 Installing the Battery Packs and Attaching
the Front Panel” and securely install the battery packs.
2 sec.
******* *******
・・
7 beeps 7 beeps
Last Result
BATTST: NG
BATTST:
Suspended
-
[When performing
battery test]
The battery check result
was an error.
See “§7.2 Charging the UPS,” charge the batteries for at
least 12 hours, and then see Ҥ4.1 Running Battery
Test” in the LCD Panel Operating Manual and perform
the battery test again. If the result is the same, the
batteries need to be replaced. Contact your sales
representative or SANYO DENKI.
Batt Life Warn
-
The remaining battery
service life is six months.
Battery replacement is recommended.
Contact your sales representative or
SANYO DENKI
early.
Press
to stop the buzzer.
The buzzer will sound again each time you start the
UPS. This will continue until you replace the batteries.
2 sec.
***** *****
・・・
5 beeps 5 beeps
Batt Life End
-
The battery service life
has ended.
The batteries need to be replaced.
Contact your sales representative or
SANYO DENKI.
Press
to stop the buzzer.
The buzzer will sound again each time you start the
UPS. This will continue until you replace the batteries.
If any other trouble occurs or you think there is a malfunction, contact your sales representative or SANYO DENKI.
Note
Press
to stop the buzzer.
Tip