5
INSTALLATION GUIDE
Ensure that the site where the SRMax will be located
can be supplied with the necessary power requirements
(120-240V @ 50-60Hz). To ind out the power consump-
tion of the SRMax refer to the marking label on your unit.
Make sure that there is adequate clearance for service.
Any plastic components in direct line-of-sight of the
UV lamp should be shielded from direct UV exposure
with aluminum foil or removed when possible.
he Sanuvox wire-set is Telon coated which makes it
resistant to UV exposure.
he SRMax relecting chamber has to be installed parallel
to the airlow with the turbulator upstream to slow
down the air as it moves in front of the UV lamp.
he suggested operating temperature range is 10 to
50°C (50 to 120°F). Operating the SRMax outside this
range will result in decreased performance. For optimal
performance, air temperature moving through the reaction
chamber should be in the range of 15 to 20°C (60 to 70°F).
he SRMax is not weatherproof. Do not install outdoors
WARNING
Follow all the Safety Instructions outlined in this document and respect all local and national codes applicable.