Sanuvox S300 VOC Скачать руководство пользователя страница 3

Page 

3

 of 

5

 

 

 

VOC CONTROLLER 

(see also VOC controller detailed operation on page 4) 

Remove the cover. 
Connect the wires with the marrettes supplied: 

CONTROLER

  

 

WIRING SET

 

BLACK (2) 

 

BLACK 

RED 

 

 

RED 

BLUE   

 

ORANGE 

The detector is factory set at 3.0 V DC; If you wish to set up a 
higher sensitivity, please proceed as follow. 

SETTINGS (if necessary) 

You will need a voltmeter with alligator type probes. 

Place the probes one on the positive terminal, the other on the neutral terminal. 

Use a small screwdriver to turn the adjustment screw to increase the sensitivity of the controller. 

Increase --- clockwise   decrease ---- counter clockwise 
 
The default setting is 3.0 v dc. The closer your setting is to 3.0 vdc, the faster the triggering of the lamp 
will be. 

 

CHECKING IF IT WORKS 

1.

 

Start the S300 unit: inside the polycarbonate box, the GREEN LED will flash. It will take 5 minutes 
to initializes the board. 

2.

 

After this period, the GREEN LED will turn solid.  Either blow cigarette smoke or propane gas into 
the controller: the RED LED lights up and the relay will trigger on the oxidizing lamp (all UVV). 
This sequence reproduce itself every minute or so. When there is no more smoke (VOC), the 
RED LED will turn off at the same time as the lamp. Screw back the cover of the controller. When 
the unit is powered the GREEN LED on the cover will light up The RED LED on the cover will 
power up when the UVV lamp is activated. 

MAINTENANCE INSTRUCTIONS

 

 

MONTHLY:

 Change the pre-filter that protects the motor (part # 

MSCFTR10

) to ensure the 

optimal performance of the unit. Check the lamps: if there is a cloudy residue please clean then 
off with denatured alcohol. 

 

YEARLY

: Change lamps (parts -see below) to maintain performance: make sure to put the same 

lamp in the same clamp. Do not interchange the lamps as the blue end cap lamp works only with 
the VOC controller. 

o

 

LMPHGXJ105-1 

 lamp UVC/UVV 

2’’ exposed

 (yellow end cap)  

o

 

LMPHXJ105

 

 lamp all UVV (blue end cap)  

 

3-5 years

: Change VOC controller (

MSC1A)

 

Positive 

 

setting screw: 

triggers at  

 3.0 V DC 

Sensor

 

Neutral  

 

Содержание S300 VOC

Страница 1: ...ield o One 1 VOC controller part MSC1A factory s pre set Two 2 replacement pre filters part MSCFTR10 LAMP INSTALLATION 1 Remove the 6 screws on the front cover The one with the SANUVOX logo Put aside 2 Remove the BLUE END CAP lamp from packaging Use the gloves provided 3 Insert the lamp in the second clamp and tighten furthest clamp from opening 4 Holding the cap with one hand plug the white conne...

Страница 2: ...u can replace it with BX cable with 3 wires WORKING INSTRUCTION The VOC controller analyzes the air every 90 seconds A 20 foot wire set connects it via a relay to activate the second oxidizing lamp on demand The S300 unit runs continuously so its regular lamp purifies the air constantly This dual zone lamp UVC UVV is enough when there are only one or two smokers However when the cigarette smoke in...

Страница 3: ...REEN LED will turn solid Either blow cigarette smoke or propane gas into the controller the RED LED lights up and the relay will trigger on the oxidizing lamp all UVV This sequence reproduce itself every minute or so When there is no more smoke VOC the RED LED will turn off at the same time as the lamp Screw back the cover of the controller When the unit is powered the GREEN LED on the cover will ...

Страница 4: ...ired concentration for the specific Volatile Organic Compound being sensed Note The value ofR8 can be changed to vary the range of the sensor A lower value decreases sensitivity increases range and a higher value increases sensitivity decreases range 6 2 red LEDs Led Lo D3 and Led Hi D2 are used to indicate the relay condition a Led Lo is ON when Relay Lo is ON and OFF when Relay Lo goes OFF b The...

Страница 5: ...ects it via a relay to the device to activate the second oxidizing lamp on demand The S300 VOC unit runs continuously so its regular lamp purifies the air constantly This dual zone lamp UVC UVV is enough when there are only one or two smokers However if there is much smoke in the room the VOC controller that samples the air on a regular basis will then trigger the second all UVV lamp for a period ...