GENERAL INSTALLATION 

Unit could be  

 

Suspended from ceiling with 
angles and suspension rods (not 
included).  

 

Hung on wall with supplied angle 
iron (included). 

Using 8

’’

 collars, attach rigid or flex duct to the return side of 

the unit above the area where smoke accumulates in order to 
remove as much smoke as possible. Attach duct (metal or flex) 
to the supply side of the unit to discharge clean air over door 
or entryway. This is done to prevent odors from escaping the 
room. It is through recirculation that the odors will be 
removed.  If the room is longer , you may use multiple inlets 
to pull the smoke to the unit. 

The VOC controller should be installed on the ceiling or wall -where the smoke will accumulate. The 
S300 VOC unit comes with 20ft of wire to link the controller box to the unit. If 20 ft is not long 
enough, you can replace it with BX cable with 3 wires.  

WORKING INSTRUCTION 

The VOC controller analyzes the air every 90 seconds. A 20-foot wire set connects it via a relay to 
activate the second oxidizing lamp on demand. 
 
The S300 unit runs continuously, so its regular lamp purifies the air constantly. This dual zone lamp 
(UVC / UVV) is enough when there are only one or two smokers. 
 
However, when the cigarette smoke increases in the room, the VOC controller that samples the air 
at regular intervals, then triggers the 2nd UVV lamp for periods of 90 seconds. This cycle is repeated 
if the controller detects smoke in the room: when there is no more, it then turns off the 2nd lamp, 
leaving the 1st lamp to continue the cleaning cycle. 
 
 

 

SIMPLIFIED PROCESS

:  

 

Ashes in the “white” smoke will be trapped onto the filter

  

 

Nicotine molecules will be dried by the UVC rays than trapped in the filters without the tar like 
material that coats everything. 

 

VOC will be oxidised by the UVV, reducing substantially their olfactory perception.

 

 

 

Suggested installation 

Содержание S300 VOC

Страница 1: ...ield o One 1 VOC controller part MSC1A factory s pre set Two 2 replacement pre filters part MSCFTR10 LAMP INSTALLATION 1 Remove the 6 screws on the front cover The one with the SANUVOX logo Put aside 2 Remove the BLUE END CAP lamp from packaging Use the gloves provided 3 Insert the lamp in the second clamp and tighten furthest clamp from opening 4 Holding the cap with one hand plug the white conne...

Страница 2: ...u can replace it with BX cable with 3 wires WORKING INSTRUCTION The VOC controller analyzes the air every 90 seconds A 20 foot wire set connects it via a relay to activate the second oxidizing lamp on demand The S300 unit runs continuously so its regular lamp purifies the air constantly This dual zone lamp UVC UVV is enough when there are only one or two smokers However when the cigarette smoke in...

Страница 3: ...REEN LED will turn solid Either blow cigarette smoke or propane gas into the controller the RED LED lights up and the relay will trigger on the oxidizing lamp all UVV This sequence reproduce itself every minute or so When there is no more smoke VOC the RED LED will turn off at the same time as the lamp Screw back the cover of the controller When the unit is powered the GREEN LED on the cover will ...

Страница 4: ...ired concentration for the specific Volatile Organic Compound being sensed Note The value ofR8 can be changed to vary the range of the sensor A lower value decreases sensitivity increases range and a higher value increases sensitivity decreases range 6 2 red LEDs Led Lo D3 and Led Hi D2 are used to indicate the relay condition a Led Lo is ON when Relay Lo is ON and OFF when Relay Lo goes OFF b The...

Страница 5: ...ects it via a relay to the device to activate the second oxidizing lamp on demand The S300 VOC unit runs continuously so its regular lamp purifies the air constantly This dual zone lamp UVC UVV is enough when there are only one or two smokers However if there is much smoke in the room the VOC controller that samples the air on a regular basis will then trigger the second all UVV lamp for a period ...