Introduction 

Thank you for choosing the SANUPS A11J. 

SAVE THESE INSTRUCTIONS

 

This manual describes the functions and setting operations of the LCD panel menus. To operate correctly, 

read this manual when setting or changing the LCD panel menus of the UPS. Please be sure to also read 

the 

A11J Instruction Manual 

for details about UPS installation and operation. Store this manual together 

with the 

A11J Instruction Manual

 in a safe place for convenient reference. 

UPS is an abbreviation for Uninterruptible Power Supply.

 

 

 

Table of Contents 

 
§1. Identifying LCD Panel ...............................................................................................................   1 

§1.1 Names of LCD Panel Parts ..............................................................................................     1 
§1.2 Functions of Home Menus ...............................................................................................     2 
§1.3 How to Operate LCD Panel .............................................................................................     3 

 

§2. Viewing UPS Information .........................................................................................................   4 

§2.1 Viewing UPS Operation Status .......................................................................................     4 
§2.2 Viewing UPS Measurements ...........................................................................................     5 

 

§3. Setting UPS ...............................................................................................................................   6 

§3.1 Setting Voltage .................................................................................................................   8 
§3.2 Setting Synchronous Frequency Tracking Range ...........................................................   9 
§3.3 Setting Frequency ...........................................................................................................   10 
§3.4 Setting Voltage for Measurement Display ......................................................................   11 
§3.5 Setting PC Interface .......................................................................................................   12 
§3.6 Setting Baud Rate ...........................................................................................................   13 
§3.7 Setting UPS Operation Upon Power Recovery...............................................................   14 
§3.8 Setting Buzzer Condition...............................................................................................     15 
§3.9 Setting UPS Shutdown Operation.................................................................................     16 
§3.10 Setting Overload Recovery Operation .........................................................................     17 
§3.11 Setting UPS Operation at 

 

OFF ............................................................................   18 

§3.12 Setting Low Battery Voltage Warning Timing ............................................................     19 
§3.13 Setting Battery Test Time ...........................................................................................     20 
§3.14 Setting Battery Test Schedule .....................................................................................     21 
§3.15 Setting Backup Time During Power Outage ...............................................................     22 
§3.16 Setting RING Signal ....................................................................................................     23 
§3.17 Setting Adjustment for Output Voltage .......................................................................     24 
§3.18 Setting Clock ................................................................................................................   25 
§3.19 Setting Number of UPS Units in Parallel Connection ................................................     26 
§3.20 Setting Operation System............................................................................................     27 
§3.21 Setting Input Phase .....................................................................................................     28 
§3.22 Resetting Values of Settings ........................................................................................     29 
§3.23 Restarting UPS ............................................................................................................   30 

 

§4. Operating UPS ..........................................................................................................................   31 

§4.1 Running Battery Test .....................................................................................................   32 
§4.2 Reading Battery Test Result ...........................................................................................   34 
§4.3 Starting or Stopping UPS ...............................................................................................   35 
§4.4 Switching to Bypass Operation ......................................................................................   36 

 

§5. Maintenance Menu (For Service Technician) ...........................................................................   37 

 

§6. Menu List ..................................................................................................................................   38 

 

§7. Status Description ....................................................................................................................   41 

 

§8. Notes on UPS Measurements Information ..............................................................................   42 
 

Содержание A11J

Страница 1: ...LCD Panel Operating Manual M0009235E...

Страница 2: ...ing Frequency 10 3 4 Setting Voltage for Measurement Display 11 3 5 Setting PC Interface 12 3 6 Setting Baud Rate 13 3 7 Setting UPS Operation Upon Power Recovery 14 3 8 Setting Buzzer Condition 15 3...

Страница 3: ...rning LED WARNING Red Lights Caution warning malfunction or end of battery discharge Output LED OUTPUT Green Lights When supplying power by inverter operation Blinks When supplying power by bypass ope...

Страница 4: ...s 8 to 29 Setting setting Change various UPS settings Settings Input output voltage frequency display Interface interface baud rate Operation startup condition buzzer sound off operation overload oper...

Страница 5: ...een may be different from the text and position described in the operating manual STATUS Note S E T T IN G S E T OP E R AT I O N Press to return to previous level Press to move to next level S E T T I...

Страница 6: ...ous malfunction Output Stop HV Bypass output stopped excessive voltage FIN Temp Error Fin temperature error serious malfunction Over Load Overload DSP Error Controller error serious malfunction Vo V F...

Страница 7: ...NT OUTPUT MEASUREMENT BATTERY MEASUREMENT CHARGER MEASUREMENT TEMPERATURE MEASUREMENT Vin V Iout A LF Watt kW Fout Hz ChgRate RunTm Min Ichg A MEASUREMENT T Amb C POWER Failure Times BATTERY Life Year...

Страница 8: ...er recovery operation Set UPS operation to perform when utility power recovers after UPS stops due to end of battery discharge in power outage Auto Auto start 3 7 14 Any Condition Always start STOP St...

Страница 9: ...5 ChA Total Unit Number of units in ChA system parallel connection Set the number of UPS units connected in the UPS system 1 3 1 unit 2 3 19 26 2 2 units 3 3 units 4 4 units 5 5 units 6 6 units 7 7 un...

Страница 10: ...e Settings group Settings Home menu STATUS MEASUREMENT SETTING MAINTENANCE CONTROL SETTING SET IN OUT SET IN OUT Voltage SET I F SET OPERATION SET BATTERY SET FUNCTION SET SYSTEM FREQ Range Frequency...

Страница 11: ...he UPS tends to switch to the asynchronous operation To connect to output of the engine power generator select 5 During the asynchronous operation if the UPS switches to the bypass operation this will...

Страница 12: ...lues screen the value shown is the current value which is indicated by 4 When a value has been changed and accepted it is indicated by After you restart the UPS the indication becomes current value Ti...

Страница 13: ...sp la y 200V 200V S Values 100V 100V Display 200V 100V 1 2 3 Details on settings and values Value Description 200V 200V S If rated input voltage and output voltage are both 200V type This is the defa...

Страница 14: ...ATION SET BATTERY SET FUNCTION SET SYSTEM Baud Rate In te rf ac e WS Values Terminal Interface Standalone 1 2 3 Details on settings and values Value Description Standalone Standalone Select this value...

Страница 15: ...NTROL SETTING SET I F SET I F Baud Rate SET OPERATION SET BATTERY SET FUNCTION SET SYSTEM Ba ud R at e 9600 Values 2400 Baud Rate 4800 1 2 3 Details on settings and values Value Description 9600 Baud...

Страница 16: ...ass power is used BATT 30 More than 30 The UPS restarts automatically when battery charge reaches 30 if the utility power recovers BATT 50 More than 50 The UPS restarts automatically when battery char...

Страница 17: ...tery operation battery testing battery voltage error low battery voltage overload bypass operation battery life end warning battery life end serious malfunction minor malfunction end of discharge requ...

Страница 18: ...L SET I F SET BATTERY SET FUNCTION SET SYSTEM OFF Operation 1 Sec Values Unique SELECT OK BACK Cancel Example Shut down UPS in 3 Sec 3 seconds Confirm Accept SE TT IN G SET IN OUT SETTING SET OPERATIO...

Страница 19: ...eep on pressing until you see it again 2 To return to the previous level press 3 When you switch to the values screen the value shown is the current value which is indicated by 4 When a value has been...

Страница 20: ...ription OFF Stop When the button is OFF the UPS stops and power is not supplied BYPASS Bypass power supply When the button is OFF power switches to bypass power supply continues Default SET OPERATION...

Страница 21: ...the battery s remaining capacity is less than 5 minutes issue warning 10 Min 10 minutes When the battery s remaining capacity is less than 10 minutes issue warning The time minutes is only an approxim...

Страница 22: ...Details on settings and values Value Description 2 Min 2 minutes Run battery test for 2 minutes 5 Min 5 minutes Run battery test for 5 minutes 10 Min 10 minutes Run battery test for 10 minutes 20 Min...

Страница 23: ...ery 90 days 30 Days 30 days Run battery test automatically every 30 days None No Do not run battery test automatically This function is available only when Auto is set in 3 3 Setting Frequency If 50Hz...

Страница 24: ...minute Provide backup for 1 minute and then stop output supply 3 Min 3 minutes Provide backup for 3 minutes and then stop output supply 5 Min 5 minutes Provide backup for 5 minutes and then stop outp...

Страница 25: ...T I F SET SYSTEM RING Output None Values 1 2 3 Details on settings and values Value Description None Do not output RING signal Output Output RING signal when the UPS starts If Output is selected it is...

Страница 26: ...l on the plus side about 1V 2 Set 2 levels on the plus side about 2V 3 Set 3 levels on the plus side about 3V Adjustment can be made by specifying the number of levels with each level being about 1V T...

Страница 27: ...the previous level press 3 When you switch to the values screen the value shown is the current value which is indicated by 4 When a value has been changed and accepted it is indicated by current value...

Страница 28: ...Unit 1 Values 2 1 2 3 Details on settings and values Value Description 1 One UPS unit is used The default is different depending on the UPS model 2 2 UPS units are connected 3 3 UPS units are connect...

Страница 29: ...operation system where there is one UPS unit Parallel operation system where total capacity of UPS units in parallel connection is used as connectable load capacity in operation If N 1 is selected wh...

Страница 30: ...se this value SELECT OK BACK Cancel Default STATUS Example Set input phase to 3Ph 4W 3 phases 4 wires Confirm Accept SE TT IN G SET IN OUT INPUT Phases 3Ph 4W SET OPERATION SET BATTERY SET FUNCTION SE...

Страница 31: ...TUS Example Resetting the settings Confirm SE TT IN G SET IN OUT SET OPERATION SET BATTERY SET FUNCTION SETTING SET DEFAULT SET SYSTEM SETTING SET DEFAULT Reset For the following settings resetting th...

Страница 32: ...then start it is different For details refer to UPS Operation in the A11J Instruction Manual Before you stop the UPS be sure to stop the load devices first What is restarting Stop load devices Stop U...

Страница 33: ...K Normal termination STATUS Test status Test Condition Test result Possible Test can start 4 2 34 Impossible Test cannot start Testing Test in progress Last Test Time Date of last test YY MM DD HH MM...

Страница 34: ...scription Test Condition Test condition Possible Test can start Impossible Test cannot start Testing Test in progress Last Test Time Date and time of last battery test YY MM DD HH MM YY MM DD HH MM If...

Страница 35: ...MAIN MCCB is set to OFF UPS s OFF operation is performed Battery test is canceled by power management software Note on battery test Cases where battery test is not possible While inverter stops During...

Страница 36: ...Condition Last Test Time YY MM DD HH MM Last Result BA TT ER Y TE ST St ar t Battery test s displayed content Item Content Display Description Display Description Test Condition Test condition Possib...

Страница 37: ...until you see it again 2 To return to the previous level press 3 If Wait appears use to go back and try again If the operation still fails contact your supplier or SANYO DENKI SETTING BYPASS CONTROL...

Страница 38: ...peration with instant interruption You can also switch the UPS operation to the bypass operation using Forced Bypass inside the front panel of the UPS Note that during the bypass operation if you set...

Страница 39: ...rvice technician to perform maintenance of the UPS Even though details are described in 6 Menu List do not use the menu to perform any operation This term is used to indicate service technicians from...

Страница 40: ...or malfunction LF CHG Load factor Charging rate Total Unit Err Total number of units error serious malfunction LF Tim m Load factor Charging duration minutes LCD Error LCD panel error Byp Fuse Error B...

Страница 41: ...iming Set when to issue battery voltage low warning Voltage When battery voltage threshold is detected 2 Min When 2 minutes left in battery capacity 3 Min When 3 minutes left in battery capacity 5 Min...

Страница 42: ...erent depending on UPS model 10Min 10 minutes 15Min 15 minutes 25Min 25 minutes 30Min 30 minutes 35Min 35 minutes 45Min 45 minutes 60Min 60 minutes 120Min 120 minutes 180Min 180 minutes 360Min 360 min...

Страница 43: ...number of load devices Bypass SW ON Bypass switch ON The forced bypass switch Forced Bypass is set to Bypass Req To Restart Restart is necessary Values for settings are changed but they require resta...

Страница 44: ...s However the operating time of which the battery charging rate will be correctly indicated differs depending on the specifications of the UPS configuration of the battery 4 The value indicated by Chg...

Отзывы: