ASSEMBLY INSTRUCTIONS
SINUS PENTA
MODULAR INVERTERS
16/
47
N. 10 connections with unipolar, twisted pair cables, type AWG17-18 (1mm
2
), for AC low voltage supply to
the electronic boards (N. 11 connections if an optional braking unit is connected).
Connections required:
-
from power supply unit 1 to the driver boards for each inverter leg 1 (from the power supply unit to the
driver board in inverter leg U1, from this driver board to the next in inverter leg V1, from this driver board to
the next in inverter leg W1) (+24V supply to IGBT driver boards)
-
from driver board in inverter leg W1 to optional braking unit BU[*] (+24V supply to braking unit)
-
from power supply unit 2 to the driver boards for each inverter leg 2 (from the power supply unit to driver
board in inverter leg U2, from this driver board to the next in inverter leg V2, from this driver board to the
next in inverter leg W2) (+24V supply to IGBT driver boards)
-
from power supply unit 1 to the splitter boards (+24V supply to splitter boards) (from the power supply unit
to the splitter board in inverter leg U1, from this splitter board to the next in inverter leg V1, from this splitter
board to the next in inverter leg W1
-
from splitter board in inverter module W1 to control unit (+24V supply to control unit)
N. 13 optical fibre connections, 1mm, standard single plastic material (typical damping: 0.22dB/m), with
connectors type Agilent HFBR-4503/4513 (N. 15 connections if an optional braking unit is installed).
Figure 8: Single optical fibre connector
Connections required:
-
from control unit to splitter board in inverter leg U1 (fault U signal)
-
from control unit to splitter board in inverter leg V1 (fault V signal)
-
from control unit to splitter board in inverter leg W1 (fault W signal)
-
from control unit to optional braking unit BU[*] (Braking unit fault signal)
-
from control unit to optional braking unit BU[*] (Braking unit gate signal)
-
from splitter board in inverter module U1 to inverter leg U1 (fault U1 signal)
-
from splitter board in inverter module V1 to inverter leg V1 (fault V1 signal)
-
from splitter board in inverter module W1 to inverter leg W1 (fault W1 signal)
-
from splitter board in inverter module U1 to inverter leg U2 (fault U2 signal)
-
from splitter board in inverter module V1 to inverter leg V2 (fault V2 signal)
-
from splitter board in inverter module W1 to inverter leg W2 (fault W2 signal)
-
from control unit to bus voltage reading board mounted on inverter leg V1 (VB signal)
-
from control unit to bus voltage reading board mounted on inverter leg U1 (sense U signal)
-
from control unit to bus voltage reading board mounted on inverter leg V1 (sense V signal)
-
from control unit to bus voltage reading board mounted on inverter leg W1 (sense W signal)
NOTE
The braking units are optional.
NOTE
[*] The internal wiring for the dual configuration of the braking units is given in
section 2.5.