112/
150
5.6.
Mains Monitor Menu
5.6.1. Overview
The Mains Monitor menu includes the parameters defining the max. variation thresholds of the mains ratings
if compared to the rated values (Rated Mains Voltage,
C500
; Rated Mains Frequency,
C501
) during the
equipment operation.
The mains frequency/voltage values are monitored, which must not exceed or drop below the ranges set in
the parameters of the Mains Monitor menu. Alarm trip can be disabled by setting
C502
= NO: in that case,
when the mains is out of range, the regenerative drive is temporarily disabled but no alarm trips. Parameters
P570
to
P575
set the activation/deactivation of each control.
The default values of certain parameters may be automatically assigned to the values imposed by the
regulations in force concerning mains voltage and frequency variations. By setting
P576
to a value other
than zero, the parameters affected by the selected regulations as well as their access rights will be
automatically updated. Parameter
P576
may be changed within
12 hours
from the latest modification.
Afterwards, the setting in
P576
becomes permanent.
5.6.2. List of Programmable Parameters P550 to P576 and I500
Parameter
FUNCTION
User Level
MODBUS
Address
DEFAULT
VALUES
P576
Default Mains Settings
ENGINEERING
281
0: No Default
I500
Default Lock Command
ENGINEERING
283
0: No Command
P550
Max. Voltage Trip Threshold
ENGINEERING (*)
670
120% Vn (*)
P551
Max. Voltage Release Ratio
ENGINEERING
671
0.920
P552
Max. Voltage Trip Time
ENGINEERING (*)
672
0.150 s (*)
P553
Max. Voltage Reset Time
ENGINEERING
673
0.100 s
P554
Min. Voltage Trip Threshold
ENGINEERING (*)
674
80% Vn (*)
P555
Min. Voltage Release Ratio
ENGINEERING
675
1.125
P556
Min. Voltage Trip Time
ENGINEERING (*)
676
0.150 s (*)
P557
Min. Voltage Reset Time
ENGINEERING
677
0.010 s
P558a
Instantaneous Overvoltage Trip
Threshold
ENGINEERING (*)
696
0.100 s
P559a
Instantaneous Overvoltage Release
Ratio
ENGINEERING
697
140% Vn (*)
P560a
Instantaneous Overvoltage Trip Time
ENGINEERING (*)
698
0.970
P561a
Instantaneous Overvoltage Reset Time
ENGINEERING
699
0.010 s (*)
P558
Instantaneous Undervoltage Trip
Threshold
ENGINEERING (*)
678
60% Vn (*)
P559
Instantaneous Undervoltage Release
Ratio
ENGINEERING
679
1.060
P560
Instantaneous Undervoltage Trip Time
ENGINEERING (*)
680
0.010 s (*)
P561
Instantaneous Undervoltage Reset
Time
ENGINEERING
681
0.010 s
P562
Max. Frequency Trip Threshold
ENGINEERING (*)
682
0,30 Hz (*)
P563
Max. Frequency Release Ratio
ENGINEERING
683
0.998
P564
Max. Frequency Trip Time
ENGINEERING (*)
684
0.080 s (*)
P565
Max. Frequency Reset Time
ENGINEERING
685
0.100 s
P566
Min. Frequency Trip Threshold
ENGINEERING (*)
686
–0.30 Hz (*)
P567
Min. Frequency Release Ratio
ENGINEERING
687
1.002
P568
Min. Frequency Trip Time
ENGINEERING (*)
688
0.080 s (*)
P569
Min. Frequency Reset Time
ENGINEERING
689
0.100 s