Santak CASTLE On-Line Series Скачать руководство пользователя страница 31

 

- 24 - 

 

     

NOTE:

 

all the power connection should be cut off before any 

maintenance .  

UPS can be Start on with Mains or without Mains. 

 

Turning On UPS With Mains 

 

Press ON/OFF button more than 1s, UPS begin to start, at the starting, 

UPS will go into self-test mode. 

   

                                         

 

 

After self-test, UPS will go into online mode, indicator and LCD as below: 

 

                                     

 

            (Online mode)   

 

       

Indicator status: 

                    Indicator light: 

       

indicator unlighted:

 

 
 

NOTE: if UPS input Mains power abnormal, UPS will transfer to battery 

mode. 
     

UPS supply power to load, Icon 

 

indicate UPS is Charging.   

     

After  UPS  turning  on,  if  battery  indicator  light,  the  output  power  is 

supplied by battery. 

 

 

Содержание CASTLE On-Line Series

Страница 1: ...3C15KS 3C20KS...

Страница 2: ......

Страница 3: ...ur electrical equipment This manual contains important instructions that you should follow during installation and maintenance of the UPS and batteries Please read all instructions before operating th...

Страница 4: ...on openings on the UPS s housing Ensure the air vents on the front side and rear of the UPS are not blocked Recommended at least 50cm of space on each side 6 Use dry cloth for cleaning 7 Use dry chemi...

Страница 5: ...Batteries have a high short circuited current and pose a risk of shock Take all precautionary measures specified below and any other measures necessary when working with batteries A remove all jewelle...

Страница 6: ...install store UPS in place where the relative humidity lower than 20 or higher than 90 C Do not install store UPS in place where there is flammable or corrosive gas place with large amounts of conduct...

Страница 7: ...2 3 UPS POWER CONNECTION 6 2 4 EBM CONNECTING AND INSTALLATION 8 2 5 UPS CONNECT TO COMPUTER PORT 9 2 6 UPS PARALLEL FUNCTION OPTIONAL 10 2 7 EPO OPTIONAL 14 2 8 MAINTENANCE SWITCH OPTIONAL 15 2 9 US...

Страница 8: ...oltage which permanently supplies the loads Computers and periphery are thus powered entirely by the mains voltage In the event of power failure the maintenance free batteries power the inverter In th...

Страница 9: ...2 1 1 Symbol and Explanation Some or all of the following symbols may be used in this manual It is advisable to familiarize yourself with them and understand their meaning 1 2 Front view 3C15KS 3C20KS...

Страница 10: ...range 208Vac 476Vac Line to Line 120Vac 275Vac phase to phase Current 30A max 39A max Frequency range 40Hz 70Hz Power factor 0 99 Bypass Mode Voltage Range 187Vac 264Vac Line to Line Current 86A 114A...

Страница 11: ...55 Relative humidity 20 to 90 Altitude 1000m The max current is under 176Vac input full rating load and empty battery charging Waring this is a product for commercial and industrial application in th...

Страница 12: ...ended at least 50cm of space on each side 4 If it is necessary to connect the inductance load such as a monitor or a laser printer to the UPS the start up power should be used for calculating the capa...

Страница 13: ...GER In order to avoid the Mains power switch current overload when UPS carries with rating load the Mains power switch rating current must be more than the bypas switch rating current bypass mode max...

Страница 14: ...inal 4 Connect the protective bonding conductors to the rear panel right earthing terminal 5 Connect the output cable to the output terminal 6 Connect the input cable to the input terminal if EBM is r...

Страница 15: ...st the straps to proper position Fix the input cable output cable EBM cable tightly 9 Re screw the terminal cover 2 4 EBM Connecting and Installation The norminal DC voltage of battery pack for Castle...

Страница 16: ...inish EBM connecting 2 The default battery pack consists16 pieces battery UPS EBM connect to the wrong quantity will cause serious hazards Make sure UPS connect to the correct quantity battery pack Th...

Страница 17: ...e reliability of the power system is higher For occasions where reliability is highly depended on N X is the optimal mode As long as the UPS is equipped with parallel cables up to 3 UPSs can be connec...

Страница 18: ...is less than 20 meters The difference between the wires of input and output of the UPSs is required to be less than 20 The distance between the UPSs in parallel is more than20 meters The difference be...

Страница 19: ...12 page 4 Each parallel UPS need an independent battery pack Recommend to install maintenance switch if need UPS parallel function it can help to simplify parallel UPS maintenance...

Страница 20: ...13 3C15KS 3C20KS...

Страница 21: ...t battery mode together 3 Turn off Parallel UPS Press the button of one UPS more than 4s buzzer beeping two times the parallel function has been closed then press the button of one UPS more than 1s le...

Страница 22: ...pass mode switch line mode input switch and battery input switch After verify no hazards service person can begin to maintain UPS without interrupting power supply to your equipment The more detail an...

Страница 23: ...ll provide installation Before installation UPS must be turned off AS400 card It owns isolated dry contact relay outputs for UPS status such as Mains Utility failure Battery low UPS alarm OK or on Byp...

Страница 24: ...rs conectivity card box and monitor Installation and further information please refer the card user Manual If require WinPower sofare and AS400 NMC CMC USB RS232 Any detail and further information ple...

Страница 25: ...w santak com 2 Choose the operation system you need and follow the instruction described on the website to download the software When your computer restarts the WinPower software will appear as a gree...

Страница 26: ...ne mode press Test Function button not less than 2s and not more than 10s UPS will enter Battery self test mode 3 LED Indicator Consists online mode indication ONLINE battery statue indication BAT byp...

Страница 27: ...75 5 76 95 6 96 When UPS output is short circuited SHORT indication icon will display As below When UPS overloaded OVER indication icon will display as below 2 UPS information input voltage input freq...

Страница 28: ...35 3 36 55 4 56 75 5 76 95 6 96 When battery voltage is low LOW icon will display as below When battery fault FAULT icon will display as below If charger is normal working CHARGING icon will light up...

Страница 29: ...22 6 UPS working mode display Icon Information description UPS is working in online mode UPS is charging battery UPS is working in bypass mode UPS is working in ECO mode...

Страница 30: ...turn off battery input switch turn bypass switch to ON position inspect battery quantity according to the LCD display information if the quantity LCD dis play is different from the actual quantity pl...

Страница 31: ...at the starting UPS will go into self test mode After self test UPS will go into online mode indicator and LCD as below Online mode Indicator status Indicator light indicator unlighted NOTE if UPS inp...

Страница 32: ...tery mode buzzer beeps every 4s to indicate user UPS is working in battery mode If want to disable buzzer beeping enter silence mode press test function button more than 2s Under without mains power i...

Страница 33: ...mode the bypass mode indicator will light up the buzzer beeps every 2 minutes Press test function button more than 2s enter silence mode If require UPS to stop output disconnect the main power turn of...

Страница 34: ...ld be made Battery replacement should be performed by qualified person Replace batteries with the same quantity and same type of batteries Do not replace the battery individually All the batteries sho...

Страница 35: ...to battery or battery low voltage Connect UPS to battery and turn on battery switch If battery low voltage charge battery via external charger UPS No output Light constantly 22 Overload Check the load...

Страница 36: ...tly Battery LED indictor light circularly 0b Battery voltage is low When audible alarm sounding every second battery is almost empty Emergency supply period shorter than nominal value Batteries not fu...

Страница 37: ......

Страница 38: ...SANTAK ELECTRONIC SHENZHEN CO LTD No 8 Baoshi Rd Block 72 Baoan Shenzhen Guangdong China www eaton com www santak com 614 01998XS1 01...

Отзывы: