INSTRUCTIONS
Copyright © SANHUA 2022
5 / 5
II-VSD2001-EN –R2206
Subject to change without notice
6.Wiring guide
Symbol
Function
Description
Symbol
Function
Description
A+
RS485
MODBUS RTU
parameter settings
A
BK
(
Black
)
Bipolar stepper motor is 4-
wires
Unipolar stepper motor is
5-wires
B-
RS485
B
GN
(
Green
)
GND
Comm. GND
A
WH
(
White
)
S+
Voltage or current input selected
by jumper switch
B
RD
(
Red
)
S-
Analog-
COM
Com terminal
CLS
Force close
form a switch with GND
24+
Power 24V+
24VAC or 24VDC
OPN
Force open
form a switch with GND
24-
Power 24V-
GND
Analog ground
Connect with OPN and CLS
Note :
1.
Cable wire range : 28 ~12 AWG (0.2 ~ 0.8 mm²).
2.
Do not tun on the power before completing the wiring, cut off the power before changing the wiring.
3.
Pay attention to not reverse the EEV connection. EEV1 with the analog signal 1 and the EEV 1
parameters.
4.
Do not connect 24V- wire and GND wire together.
5.
If you want to use 1 analog signal to control 2 x EEV in parallel, please connect the 0-10V signal on both
analog inputs. Check that the 0-10V supplier voltage
doesn’t deform the signal.
—
—