Optidrive E3 Set-up Guide
P a g e
|
63
20
IP66 Switched Units
Integral Forward-Stop-Reverse Switch
To disable / re-enable the Forward-Stop-Reverse switch:
•
Make sure the drive is in the
STOP
condition (not running or tripped)
•
Set the correct value into
P-14
to enable advanced parameter access e.g.
101
or
201
•
Go to
P-00
•
Press and hold the
STOP
button for approx. 1s
•
The display will show
Lc-OFF
(default setting)
Lc-OFF
means integrated switch is enabled
Lc-On
means integrated switch is disabled
ALtErn
means integral switch is enabled but function as per table below
•
Use the
UP
or
DOWN
buttons to select the setting required
•
Press the
STOP
button to exit and save the setting
Lc-On
– Internal switch disabled
Lc-OFF
– Internal switch enabled and works as per E3 IP66 ‘indoor rated’.
ALtErn
– Internal switch enabled and new mode as per table below
Switch position
P-00 & STOP for 1s Setting
Lc-On
Lc-OFF
ALtErn
DI 1
DI 2
DI 1
DI 2
DI 1
DI 2
Left (Reverse)
0
0
1
1
0
1
Middle (Stop)
0
0
0
0
0
0
Right (Forward)
0
0
1
0
1
0