Optidrive E3 Set-up Guide
P a g e
|
29
9
Keypad Control
Keypad Control
The Keypad on the Optidrive E3 can be used to control the starting (running), stopping and speed of the
motor. In keypad control, the drives control terminals remain active and various configurations can be
implemented.
Optidrive E3 uses a macro approach to simplify the configuration of the analogue and digital inputs when in
keypad control.
See the Getting Started section of this guide for basic Keypad Control information.
This section of the guide gives information of the way the control terminals function in keypad control.
Parameter P-12
Selects the main drive control source and determines the primary control of the drives output frequency.
P-12 = 1:
Keypad control (forward only)
P-12 = 2:
Keypad control (forward and reverse)
Parameter P-15
Assigns the functionality to the digital and analogue inputs (terminals 2, 3, 4 and 6).
To access P-15:
Set parameter P-14 = 101 to access parameters P-01 to P-50
Set parameter P-14 = 201 to access parameters P-01 to P-60
P-15 = 0 (Default)
P-15
Digital input 1
Terminal 2
Digital input 2
Terminal 3
Digital input 3
Terminal 4
Analogue input 1
Terminal 6
0
Open: Stop (disable)
Closed: Run (enable)
Open: No function
Closed: Increase speed
Open: No function
Closed: Decrease speed
Open: Forward
Closed: Reverse
NOTE:
Analogue input 1 used as a digital input.
NOTE:
Parameter P-15 = 9, 10, 11, 12 & 13 has the same functionality as P-15 = 0.
P-15 = 1
P-15
Digital input 1
Terminal 2
Digital input 2
Terminal 3
Digital input 3
Terminal 4
Analogue input 1
Terminal 6
1
Open: Stop (disable)
Closed: Run (enable)
No function
PI Control feedback
No function
NOTE: Digital input 3 (terminal 4) is used as an analogue input.
P-15 = 2
P-15
Digital input 1
Terminal 2
Digital input 2
Terminal 3
Digital input 3
Terminal 4
Analogue input 1
Terminal 6
2
Open: Stop (disable)
Closed: Run (enable)
Open: No function
Closed: Increase speed
Open: No function
Closed: Decrease speed
Open: Keypad speed ref
Closed: Preset speed 1 (P-20)
NOTE:
Analogue input 1 used as a digital input.