background image

Merlin Gas Detectors   

 

 

 

 

 

 

Product Data Sheet 

 

 

 

 

Rev: 09 Date: 19-01-18

  

4  

Technical Specification 

 

 

Power supply   7-30VDC, 80mA max 

Gas Sensor   Semiconductor type sensor 

Typical measuring range 

 300-10000 ppm 

Methane

 

 300-10000 ppm 

LPG

 

 10-10000 ppm 

CO

 

 100-10000 ppm 

Hydrogen

 

Power Up - warm up time    1 minute 

Low level alarm  

(pre-alarm) 

 Methane 8%LEL by volume 

 LPG 0.16% by volume 

 Carbon monoxide 30ppm 

 Hydrogen 8%LEL by volume 

High level alarm 

 Methane 10%LEL by volume 

 LPG 0.2% by volume 

 Hydrogen 10%LEL by volume 

 Carbon monoxide  

 30 ppm for 2 hours          

 50 ppm for 1 hour 

 100 ppm for 10 minutes        

 300 ppm for 1 minute 

Volt free relay output   240VAC 500mA, 30VDC 2A switching current (resistive load) 

Net weight/Dimensions   180g/135mm(W)x95mm(H)x38mm(D) 

Installation standard   Wall mountable 

   CE 

Standard Approval   Complies with EN50194 and EN50291 

 

 

 

 

 

 

 

 

 

 

 

 
 