Mounting & Cabling 

 

If mounting direct to wall - ensure the wall surface is flat to prevent base distortion! 

 

Ensure the rear base is installed in the correct orientation as shown! 

 

Where cable glands/conduits are used for wire entry, use 20mm (3/4 inch) max separated by at least 20mm! 

 

Any parts that form part of the connections/installation must have a minimum fire-retardant rating of UL94v-2! 

 

Damage to PCBs when creating cable entry points or attempting to remove the circuit board may void any warranty! 

 

The monitor is designed for either surface mounting or mounted on a one or two gang electrical box.

 

 

Restrain the hazardous live wiring from accidental loosening

 

to prevent wires from moving after installation and touching 

parts of opposite polarity or at low voltages! 

 

Isolate the equipment from all hazardous live power sources before opening the cover! 
 

 
 

     

 

 

 

 

1.

 

Carefully remove the front cover from the unit by using an M3 socket wrench. 

2.

 

Using the rear base - mark mounting holes to the wall or align with an appropriate gang/pattress box. 

3.

 

Fixing straight to wall 

 

drill 0.2” (5mm) hole, insert plugs and use the four screws (No.4 Pozi) 

provided. 

4.

 

There are pre-fractured areas for cable entry on the rear of the base and pilot holes positioned on the top and bottom 

of the enclosure suitable for entry points up to ¾” (20mm).

 

5.

 

After executing the mounting/connections 

 secure the front cover with all M4 bolts and insert security caps provided. 

 

Содержание Merlin Detector i-S

Страница 1: ...170322 1 Merlin Gas Detector i S Installation Operation Maintenance Please read this manual carefully and retain for future use For specific requirements that may deviate from the information in this...

Страница 2: ...Power Input 6 Wiring Alarm Relays 7 Alarm Relay Setting Switch Latch On Off 7 Wiring 0 10V Analogue Output 7 CO2 Selection Switches 7 Audible Buzzer Switch 8 Factory Set Condition 8 Operation 8 Initia...

Страница 3: ...nufacturer s Warranty Warranty coverage The manufacturer warrants to the original consumer purchaser that this product will be free of defects in material and workmanship for a period of three 3 years...

Страница 4: ...is also relevant to toxic gas detection Recommended heights may vary based on air flow and temperature conditions in addition to the proposed application and location Locations for detectors will var...

Страница 5: ...wo gang electrical box Restrain the hazardous live wiring from accidental loosening to prevent wires from moving after installation and touching parts of opposite polarity or at low voltages Isolate t...

Страница 6: ...d any warranty Wiring Power Input Standalone Power 12 24V power inputs can be either AC or DC Terminals are pluggable type to ease connections Merlin GDP Power Connection Power is supplied via the GDP...

Страница 7: ...a red dot on the screen when the alarm relay has latched The alarm will beep every 10 seconds to alert the user that the detector entered an alarm state To reset the Detector press and hold the touch...

Страница 8: ...tors are shipped pre calibrated and configured Buzzer On Off Switch On Alarm Relay Setting Switch On CO2 Selection Pre Alarm 800ppm Alarm 1000ppm 0 2000ppm 0 10V Output Range Operation Initial Power U...

Страница 9: ...rly using a slightly damp cloth Never use detergents or solvents to clean your device Never spray air fresheners hair spray paint or other aerosols near the device Never paint the device Paint will se...

Страница 10: ...uld always be given to any applicable national local law and industry codes Generally the gas concentration should be greater than the alarm threshold of the device Always remove the regulator valve a...

Страница 11: ...Evaluated Operating 10 50 C 20 90 RH non condensing Storage 0 50 C 30 80 RH no condensation Altitude Rating 2000m Wiring Typical Min 2 5mm2 75 C min Tinned copper Approvals Electrical Safety and Elec...

Страница 12: ...om any unforeseen damage caused by transit installation Every effort is made to ensure the accuracy of this document however S S Northern can assume no responsibility for any errors or omissions in th...

Отзывы: