25
1
2
3
4
5
6
on
off
7
8
4. Set DIP switch 8 to “on.”
NOTE
When using the weekly programme 3, see page 27,
one of the sensors must be activated:
• Set humidity sensor (integrated as standard) = DIP
switch 1 to “on.”
• Set VOC sensor (optional accessory) = DIP switch
2 to “on.”
• Set 0-10 V entrance (external signal) = DIP switch
3 to “on.”
5. Screw on cover (21) fi rmly with screws Torx 10 (20).
6. Set up power supply for ventilation system.
7.
So that the ventilation system runs with the
weekly programme that has been set, keep
the symbol pressed for 5 seconds.
When the automatic mode is activated
(weekly programme), the A symbol lights
up below on the control panel.
7. INDIVIDUAL USER SETTINGS
7.1. SETTING TIMER FOR FILTER ALARM
The factory setting for the timer for the fi lter alarm is 12
months. Changing the fi lter is highly dependent on the
pollution of the outdoor air (e.g. pollen count, construc-
tion site activity). The timer for the fi lter alarm can be set
to 6 months, 9 months or 15 months.
M+P-26A-2044
0
A
B
12V
16
1
2
3
4
5
6
on
off
1
2
3
4
5
6
on
off
1. Remove back cover of control panel (16).
2. Set DIP switch 3 and 4 to desired timer.
1
2
3
4
5
6
on
off
6 months
1
2
3
4
5
6
on
off
9 months
1
2
3
4
5
6
on
off
12 months
(Factory setting)
1
2
3
4
5
6
on
off
15 months