AIRFLOW SET TING

CAUTION:

 Refer to local and national Ventilation and Indoor Air Quality standards to ensure the proper airflow rate.

Ensure the HVAC unit air filter is clean and installed. Turn the ES24V to the “ON” position and wait approximately 10 
seconds for the HVAC unit fan to turn on and the motorized damper to open. (Note, ensure that the Motorized Damper 
is enabled on the ES24V; refer to ES24V IOM on page 6-7). Using a manometer or anemometer, measure and record 
the airflow through the fresh air duct (refer to the measuring device instructions and the airflow/air velocity table on 
page 5. Keep in mind, lower velocities are preferred to decrease noise and increase filter effectivity). Once complete, 
turn the ES24V to the “OFF” position and calculate the required continuous CFM based on the ventilation code.

ASHRAE 62.2-2010
Required Continuous CFM = ((0.01 * Floor Area in ft²) + 7.5(# of be 1))

Example:
2,000 sqaure foot dwelling
3 bedrooms

= 50 CFM continuous

ASHRAE 62.2-2013 & 2016
Required Continuous CFM = ((0.03 * Floor Area in ft²) + 7.5(# of be 1))

Example:
2,000 sqaure foot dwelling
3 bedrooms

= 90 CFM continuous

Now that the required continuous CFM is known, calculate the required run time / hour.

Run Time / Hour = 60 * (Required Continuous CFM / Actual Measured CFM)

Example (based on ASHRAE 62.2-2010 example above):
50 Required Continuous CFM
150 Actual Measured CFM

= 20 minutes / hour

Set the ES24V to the correct Run Time / Hour and High / Low Temperature & Humidity limits per the ES24V IOM on 
pages 6-7.

FIGURE 3

ES24V 

- (20VA NOT AVAILABLE FOR DIRECT 

CONNECTION OF MOTORIZED DAMPER)

SENSOR

C

TS

TS

R

G

SENSOR

R
C
G

G

C

R

TRANSFORMER

COMMON

Refer to the ES24V – Envirosense Ventilation Control IOM on pages 8-9 for ES24V wiring connections  and operation.

Содержание MDX-ES24VK

Страница 1: ...purpose of this manual is to aid in the proper installation and operation of fans manufactured by S P These instructions are intended to supplement good general practices and are not intended to cover detailed instruction procedures because of the wide variety and types of fans manufactured by S P Installation Operation and Maintenance Manual ...

Страница 2: ......

Страница 3: ...igorous standards of production All the components have been checked and tested at the end of the manufacturing process We recommend that you check the following after receiving this product 1 The correct size has been received 2 The correct model has been received 3 The details on the rating label correspond to the electrical supply voltage frequency etc Remove the unit from packaging and inspect...

Страница 4: ...2 Make sure the temperature and humidity sensors are installed into the insulated fresh air duct between the wall cap and motorized damper if necessary ...

Страница 5: ...te an air tight path from the building exterior to the ventilated space WIRING CAUTION Ensure that power is turned off and locked out before making any wiring connections The MDX ES24VK operates from a standard 24V 60Hz AC electrical supply There are multiple wiring scenarios available depending on the installer preferences The diagrams below show 3 common scenarios where the ES24V is connected ei...

Страница 6: ...red continuous CFM based on the ventilation code ASHRAE 62 2 2010 Required Continuous CFM 0 01 Floor Area in ft 7 5 of bedrooms 1 Example 2 000 sqaure foot dwelling 3 bedrooms 50 CFM continuous ASHRAE 62 2 2013 2016 Required Continuous CFM 0 03 Floor Area in ft 7 5 of bedrooms 1 Example 2 000 sqaure foot dwelling 3 bedrooms 90 CFM continuous Now that the required continuous CFM is known calculate ...

Страница 7: ... To inspect the unit disconnect from electrical supply Remove the motorized damper from the fresh air ductwork and inspect the damper blade for damage and proper function If any debris is evident on the damper blade clean with a damp not wet cloth DO NOT USE any detergents or abrasive materials for cleaning Reinstall motorized damper to the fresh air ductwork and reseal joints WARRANTY S P USA S P...

Страница 8: ...Install the sensors at a location so that they will be exposed to the fresh air intake ex the fresh air ductwork Drill 2 3 4 diameter holes spaced appropriately and install the sensors with the provided hardware NOTE the sensor wires can be extended up to 300 feet without deviation Use appropriate duct tape to seal joints openings as necessary DIMENSIONS in SCREEN DIAGRAM OPERATING MODES OFF Mode ...

Страница 9: ...C to 55 C High Limit Temperature settings range 65 105 F 18 C to 40 C Low Limit Temperature settings range 20 60 F 6 C to 16 C Heater Temperature settings range 32 F 62 F 0 C 16 C Temperature resolution 1 F or 0 5 C Temperature Accuracy 1 F or 0 5 C Humidity measurement range 10 95 High Limit Humidity settings range 55 90 Low Limit Humidity settings range 10 50 Humidity resolution 1 Humidity Accur...

Страница 10: ...owers Avenue Jacksonville Florida 32217 T 904 731 471 1 F 904 737 8322 www solerpalau usa com S P Canada Ventilation Products Inc 6710 Maritz Drive Unit 7 Mississauga ON L5W 0A1 Canada T 416 744 1217 F 416 744 0887 www solerpalaucanada com ...

Отзывы: