WARNINGS

READ AND SAVE THESE INSTRUCTIONS.

 

FAILURE TO COMPLY WITH INSTRUCTIONS COULD RESULT IN 

PERSONAL INJURY AND/OR PROPERTY DAMAGE!

CAUTION:

1. 

For General Ventilating Use Only. Do Not Use To Exhaust Hazardous Or Explosive Materials And Vapors

2. 

The MDX-ES24VK is suitable for operation within indoor environments only.

WARNING:

 TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK OR INJURY, OBSERVE THE FOLLOWING: 

1.  Use this unit only in the manner intended by the manufacturer. If you have questions, contact the manufacturer.
2.  Before servicing or cleaning unit, switch power off at service panel and lock the service disconnecting means to 

prevent power from being switched on accidentally. When the service disconnecting means cannot be locked, 
securely fasten a prominent warning device, such as a tag, to the service panel.

3.  Installation work and electrical wiring must be done by qualified person(s) in accordance with all applicable 

codes and standards, including fire-rated construction.

4.  Sufficient air is needed for proper combustion and exhausting of gases through the flue (chimney) of fuel 

burning equipment to prevent back drafting. Follow the heating equipment manufacturer’s guideline and safety 
standards such as those published by the National Fire Protection Association (NFPA), and the American 
Society for Heating, Refrigeration and Air Conditioning Engineers (ASHRAE), and the local code authorities.

5.  When cutting or drilling into wall or ceiling, do not damage electrical wiring and other hidden utilities.
6.  Ducted fans must always be vented to the outdoors.

PRE-INSTALLATION INSPECTION

The MDX-ES24VK has been manufactured in accordance with rigorous standards of production. All the components 
have been checked and tested at the end of the manufacturing process. We recommend that you check the following 
after receiving this product:

1.  The correct size has been received.
2.  The correct model has been received.
3.  The details on the rating label correspond to the electrical supply: voltage, frequency etc.

Remove the unit from packaging and inspect for shipping damage within 5 days of receipt. If the product is found to be 
damaged, immediately contact your local authorized supplier. 

DO NOT OPERATE THE UNIT IF DAMAGED. 

These 

instructions should be considered as a supplement to EPA standard practices, as well as all state and local building 
code regulations.
Before installing the product check the following points:

1.  The damper blade opens and closes freely.
2.  There are no obstructions to the airflow.

ENVIRONMENT

The MDX-ES24VK is suitable for operation within indoor environments only. The MDX-ES24VK is suitable for the 
supply of both conditioned and un-conditioned airstreams within the temperature ranges (inclusive of duct airstream’s 
temperature) of -40°C up to +60°C.

MOUNTING

Choose a mounting location which allows convenient wiring and maintenance accessibility. The MDX-ES24VK can 
be mounted in any orientation, horizontal or vertical, and is suitable for supply/fresh air applications. The motorized 
damper will be installed between the fresh air wall cap/roof cap/soffit vent (with insect screen) and the HVAC unit 
return duct. The ES24V fresh air control can be mounted:

•  On the insulated ductwork between the wall cap and the motorized damper, or  

(Note, the 24V power wires (R & C) will need to be extended from the HVAC unit power supply or a 
separate 120V-24V transformer)

•  On the HVAC unit (Note, the temperature (26AWG cable) and humidity (6P6C phone cable) sensor wires 

will need to be extended.)

Содержание MDX-ES24VK

Страница 1: ...purpose of this manual is to aid in the proper installation and operation of fans manufactured by S P These instructions are intended to supplement good general practices and are not intended to cover detailed instruction procedures because of the wide variety and types of fans manufactured by S P Installation Operation and Maintenance Manual ...

Страница 2: ......

Страница 3: ...igorous standards of production All the components have been checked and tested at the end of the manufacturing process We recommend that you check the following after receiving this product 1 The correct size has been received 2 The correct model has been received 3 The details on the rating label correspond to the electrical supply voltage frequency etc Remove the unit from packaging and inspect...

Страница 4: ...2 Make sure the temperature and humidity sensors are installed into the insulated fresh air duct between the wall cap and motorized damper if necessary ...

Страница 5: ...te an air tight path from the building exterior to the ventilated space WIRING CAUTION Ensure that power is turned off and locked out before making any wiring connections The MDX ES24VK operates from a standard 24V 60Hz AC electrical supply There are multiple wiring scenarios available depending on the installer preferences The diagrams below show 3 common scenarios where the ES24V is connected ei...

Страница 6: ...red continuous CFM based on the ventilation code ASHRAE 62 2 2010 Required Continuous CFM 0 01 Floor Area in ft 7 5 of bedrooms 1 Example 2 000 sqaure foot dwelling 3 bedrooms 50 CFM continuous ASHRAE 62 2 2013 2016 Required Continuous CFM 0 03 Floor Area in ft 7 5 of bedrooms 1 Example 2 000 sqaure foot dwelling 3 bedrooms 90 CFM continuous Now that the required continuous CFM is known calculate ...

Страница 7: ... To inspect the unit disconnect from electrical supply Remove the motorized damper from the fresh air ductwork and inspect the damper blade for damage and proper function If any debris is evident on the damper blade clean with a damp not wet cloth DO NOT USE any detergents or abrasive materials for cleaning Reinstall motorized damper to the fresh air ductwork and reseal joints WARRANTY S P USA S P...

Страница 8: ...Install the sensors at a location so that they will be exposed to the fresh air intake ex the fresh air ductwork Drill 2 3 4 diameter holes spaced appropriately and install the sensors with the provided hardware NOTE the sensor wires can be extended up to 300 feet without deviation Use appropriate duct tape to seal joints openings as necessary DIMENSIONS in SCREEN DIAGRAM OPERATING MODES OFF Mode ...

Страница 9: ...C to 55 C High Limit Temperature settings range 65 105 F 18 C to 40 C Low Limit Temperature settings range 20 60 F 6 C to 16 C Heater Temperature settings range 32 F 62 F 0 C 16 C Temperature resolution 1 F or 0 5 C Temperature Accuracy 1 F or 0 5 C Humidity measurement range 10 95 High Limit Humidity settings range 55 90 Low Limit Humidity settings range 10 50 Humidity resolution 1 Humidity Accur...

Страница 10: ...owers Avenue Jacksonville Florida 32217 T 904 731 471 1 F 904 737 8322 www solerpalau usa com S P Canada Ventilation Products Inc 6710 Maritz Drive Unit 7 Mississauga ON L5W 0A1 Canada T 416 744 1217 F 416 744 0887 www solerpalaucanada com ...

Отзывы: