Ventilation units with heat recuperation
DUOVENT
®
MODULAR DV/RV
32
Location of mixing (MX/C) and bypass damper (BP) for
DUOVENT
®
MODULAR DV
units:
BP bypass flap
mixing flap (MX or C)
ODA flap
ETA
SUP
EHA flap
Mixing mode (MX)
- ODA + EHA damper open to 100 %, MX damper open according to the required amount of mixing air.
Circulation mode (C)
- damper ODA + EHA completely closed, damper C open to 100 %.
Control torques and types of bypass and mixing flap actuators:
5.2.9 MIXING FLAP OF DUOVENT
®
MODULAR RV
DUOVENT
®
MODULAR RV units are not fitted with the regeneration exchanger bypass, but can be fitted with circulation or mixing flap (marked as
MX or C in the unit code). The mixing flap allows you to efficiently mix part of the exhaust air with fresh air or allows the unit to have a 100 %
recirculated air circulation mode. This mode serves particularly for pre-heating or pre-cooling to the required temperature. Inlet and outlet fans are
in operation in the circulation and mixing mode.
Location of the mixing (MX/C) flap for DUOVENT
®
MODULAR RV:
EHA flap
ETA
SUP
ODA flap
mixing flap
(MX or C)
Unit type
flap type
min. control torque
[Nm]
possible types of BELIMO
actuators
DUOVENT
®
MODULAR DV 8500
BP
20
SM24 A-SR
DUOVENT
®
MODULAR DV 10100/12000/14500
BP
40
GM24 A-SR
DUOVENT
®
MODULAR DV 8500/10100/12000/14500
MX/C
10
NM24 A-SR