DUOVENT® MODULAR DV/RV

ErP2018 
Ventilation units with heat recuperation

INSTRUCTION MANUAL

 

Содержание DUOVENT MODULAR DV

Страница 1: ...www solerplau co uk DUOVENT MODULAR DV RV ErP2018 Ventilation units with heat recuperation INSTRUCTION MANUAL...

Страница 2: ...in 29 5 2 8 Bypass and mixing flap of MODULAR DV 31 units 31 4 5 5 2 9 Mixing flap of MODULAR RV units 32 5 2 10 Inlet and outlet flap 33 5 2 11 Basic accessories 33 5 2 11 1 Condensate traps 33 5 2 1...

Страница 3: ...arranty conditions The device must be installed by a professional air handling service company The DUOVENT MODULAR DV RV device including the DVAV DCAV DCOP control system must be put into operation e...

Страница 4: ...e that children do not play with the device Cleaning and maintenance of the appliance must not be carried out by children without supervision 2 GENERAL The DUOVENT MODULAR DV RV unit is manufactured i...

Страница 5: ...circulation with preparation for mounting the actuator if the unit is equipped with MaR system the actuator is included in the delivery KL inlet and outlet damper with preparation for mounting the act...

Страница 6: ...with preparation for mounting the actuator if the unit is equipped with MaR system the actuator is included in the delivery C mixing damper enabling 100 air circulation with preparation for mounting t...

Страница 7: ...ECT COOLER FAN FILTER The unit is also equipped with labels with warnings HEATING COOLING MEDIA INPUT HEATING COOLING MEDIA OUTPUT NOTICE ON LOCATION OF FAULT RESET BUTTON OF EL HEATER NOTICE ON LOCAT...

Страница 8: ...RV 8 WARNING DO NOT OPERATE THE UNIT WHILE CONSTRUCTION WORK IN PROGRESS AIR FLOW CALCULATION PLATE LOCATED AT FAN SUCTION PRESSURE ORIFICE PORT WARNING LABELS Labels to identify the type of air strea...

Страница 9: ...AIR EHA DUOVENT MODULAR DV UNITS NECK VARIANTS AV2 FRESH AIR ODA CIRCULATION AIR RCA WASTE AIR EHA DUOVENT MODULAR RV UNITS NECK VARIANTS AV WASTE AIR EHA EXHAUST AIR ETA CIRCULATION AIR RCA SUPPLY AI...

Страница 10: ...L3 18 18 18 18 A DETAIL OF CONNECTING FLANGE INTEGRATED IN WALL PANEL 31 D Exchanger outlets 62 A 150 B 314 F 188 E 30 E X E E X 29 31 Type A mm B mm D mm E mm F mm L mm L1 mm L2 mm L3 mm X mm Y mm X1...

Страница 11: ...Y 18 18 18 18 A DETAIL OF CONNECTING FLANGE INTEGRATED IN WALL PANEL 31 D Exchanger outlets 150 B 62 A 314 F 188 E 30 E X E E X 31 29 Type A mm B mm D mm E mm F mm L mm L1 mm L2 mm L3 mm X mm Y mm X1...

Страница 12: ...1 L2 L3 A 18 1 18 18 DETAIL OF CONNECTING FLANGE INTEGRATED IN WALL PANEL 31 D Exchanger outlets 150 B 62 A 314 F 188 E 30 E X E E X 31 29 Type A mm B mm D mm E mm F mm L mm L1 mm L2 mm L3 mm X mm Y m...

Страница 13: ...Type power current max input current power Digireg m3 h V Hz W A kW A m3 h kW kg 8500 8500 DCA 64 2 8500 DCB 45 5 3 400V 50Hz M3 Vx 8500 4178 2952 6 4 3 94 3 9000 860 950 8500 DCA DCC 64 2 65 8 8500...

Страница 14: ...unit can be used in rooms normal according to IEC 60364 5 51 resp SN 332000 5 51 ed 3 SN 332000 1 ed 2 The ambient temperature must be between 20 and 40 C The unit can transport air without solid fib...

Страница 15: ...amps and screws The unit is always shipped in 3 separate blocks The connection of individual blocks is carried out only after transport to the destination in the building air conditioning engine room...

Страница 16: ...ane it is necessary to pass the ropes under the unit so that they do not slip The unit can be manipulated only by supporting or tying behind the floor of the unit the unit cannot be lifted behind the...

Страница 17: ...These damages are not covered by the warranty After connecting the unit to the HVAC piping it is necessary to check the insulation of the HVAC piping in parts with a risk of condensation Condensate f...

Страница 18: ...e space of DUOVENT MODULAR RV units unit design without mixing flap MX or C in code L A S I C control box Digireg B 150 B 150 Size A mm B mm L mm S mm RV 8500 1620 1620 2348 1700 RV 10100 1777 1777 23...

Страница 19: ...nnected to a three phase AC mains supply 400 V 50 Hz or single phase 230 V 50 Hz AC networks according to the specific design of the unit For installation in accordance with EC regulations DUOVENT MOD...

Страница 20: ...K No 2 BLOCK No 3 BLOCK No 1 BLOCK No 2 BLOCK No 3 The illustration above applies to AV2 unit positions Mirror images of these images apply to the positions of AV units see chap 3 2 The blocks must be...

Страница 21: ...ividual blocks roof connecting strip Before connecting the unit to the HVAC piping check the markings and directions of the air flow in the unit Marking of air currents ODA SUP ETA EHA see chap 3 2 Al...

Страница 22: ...y S P UK Ventilation Systems Ltd SYSTEMS service worker Hoses with a reserve for S7 hoses terminate with a coupling Hoses from the inlet points of the inlet filter Hoses with a reserve for S6 terminat...

Страница 23: ...design of connectors on the border of the 1st and 2nd transport block power supply of ODA and EHA input damper actuators design of connectors on the border of the 2nd and 3rd transport block power sup...

Страница 24: ...the electric heater of the unit which will cause the heating rods to overheat and the intervention of the emergency thermostat The solution is to increase the air flow to the required minimum level ac...

Страница 25: ...supply switchboard Faults found must be rectified immediately These inspections are carried out at least once a year or more often according to local conditions by an authorized professional service...

Страница 26: ...ErP2018 xV 1 1 2 DV RV 8500 IBW B DUOVENT 8500 ErP2018 xV IBW A DUOVENT 10100 ErP2018 xV IBW B DUOVENT 10100 ErP2018 xV 1 1 2 1 1 2 1 1 2 DV RV 10100 IBW A DUOVENT 12000 ErP2018 xV 2 DV RV 12000 IBW B...

Страница 27: ...service must be protected against freezing by draining water from all parts of the unit Residual water from the exchanger can be expelled with compressed air When starting the unit at an outdoor air t...

Страница 28: ...side from the air inlet on the front surface of the exchanger see following image cooling water inlet cooling water outlet air flow direction air flow direction cooling water inlet cooling water outl...

Страница 29: ...f the design of the connection sockets of one direct evaporator circuit 5 2 7 CONDENSATE DRAIN CONNECTION To ensure the drainage of condensate from the interior of the unit the drain spout must be con...

Страница 30: ...eating cable and external insulation to prevent condensate from freezing in the siphon and the entire condensate route The heating cable is not part of the delivery of S P UK Ventilation Systems Ltd S...

Страница 31: ...unit must not be connected by piping and then into one siphon In winter the outdoor units must be tempered by a condensate route including anti freeze siphons e g electric heating cables After mountin...

Страница 32: ...hanger bypass but can be fitted with circulation or mixing flap marked as MX or C in the unit code The mixing flap allows you to efficiently mix part of the exhaust air with fresh air or allows the un...

Страница 33: ...tes the flow of cooling water to the water cooler at a constant cooling water inlet temperature designation in the type symbol indicates pump type and Kv value of mixing valve The control is provided...

Страница 34: ...is often clogged the entire heating circuit must be cleaned Even during normal operation of the device it is necessary to check the filter regularly When cleaning the filter all water lines must be cl...

Страница 35: ...ate supply cable which is not part of the delivery of the device 6 1 ELECTRIC HEATER CONNECTION The cables of the electric heater are led to the terminal board of the electric heater and properly mark...

Страница 36: ...supply air temperature The main sensor is placed in a ventilated area the supply air sensor is placed in the outlet of the unit in a place with sufficient air mixing If the room temperature is higher...

Страница 37: ...stem with a copper conductor with a cross section of at least 6 mm2 due to the impedance of the earth conductor for high frequency interference We recommend to fit the power supply with surge protecto...

Страница 38: ...Ventilation units with heat recuperation 38 DUOVENT MODULAR DV RV S4 D plate exchanger D rortoattaintigngexchanger DIDX DCC DCDCC DC DCDX DIDCC DI D HVAC function variants...

Страница 39: ...ilter cartridges Flap movability Tight connection to distribution lines Closing of all doors and service holes Any faults must be rectified before starting the unit for the first time 7 2 TRIAL OPERAT...

Страница 40: ...DUOVENT MODULAR DV RV units comply with the applicable regulations for electrical equipment Before carrying out any work on the device always disconnect the device from the power supply Always use th...

Страница 41: ...ed to perform a visual inspection every 5 years Remove dust from the impeller with a dry not wire Brush or by blowing with compressed air Check the condition of the bearings of electric motor estimate...

Страница 42: ...with M6 screws service door of the unit access to the second parallel arranged fan after disassembly of the first fan and removal of the dividing wall shown inlet part of the MODULAR unit in the outle...

Страница 43: ...OF THE REGENERATION ROTATION EXCHANGER The heat recovery exchanger is protected by filters and can therefore only be contaminated very lightly Nevertheless it is recommended to perform a visual inspe...

Страница 44: ...is necessary to perform the following actions 1 Open the unit door and disconnect the rotor electric motor 2 Remove the complete service side of the unit block including the partitions and the Digire...

Страница 45: ...especially their permeability and tightness especially the tightness of the attachment to the unit and the tightness of the ball seating in the case of overpressure siphons fill the siphons with wate...

Страница 46: ...applicable standards and national and local building standards IF CLAIMING UNDER WARRANTY Please return the completed product carriage paid to your local authorised distributor All returns must be ac...