Ventilation unit with heat recuperation
DUOVENT
®
COMPACT RV
11
5. INSTALLATION
The unit can only be installed by a professional installation company authorized in accordance with the Trade Licensing Act.
5.1 PLACE OF INSTALLATION
The unit can only be installed in accordance with the "Environmental Protocol", in which the characteristics of all devices that can be placed in
this space are clearly defined, and it is not possible to place devices that would affect these conditions in any way. The unit has a limited load
capacity and is not intended for storing and depositing any materials, especially objects of considerable weight. This could deform the housing
of the unit or severely damage it. These damages are not covered by the warranty. After connecting the unit to the HVAC piping, it is necessary
to check the insulation of the HVAC piping in parts with a risk of condensation. Condensate formed in the air duct can, in unfavourable
conditions, spill into the interior of the unit, where it is not separated and may flow out of the unit. The result of this process can be damage to
adjacent building structures.
Service space for operation and repairs of
DUOVENT
®
COMPACT RV
S
A
location of
Digireg
®
control box
L, L1
5.1.1 DISTANCES FROM BUILDING STRUCTURES (SERVICE SPACE)
Observe the minimum recommended distances from all obstacles to ensure easy maintenance and operation of the unit. If the unit is fitted with
Digireg
®
or regulation system, it is necessary to ensure free space from the system distribution box of at least 800 mm and the space for free
opening of the doors. It is also necessary to ensure distances on the side of connecting the air duct to the unit. All media and I&C connections,
or other constructions, must not prevent the full opening of all openings (doors) used for operation and maintenance of the unit.
Unless
otherwise agreed in the order, the control system distribution box will be placed in the position according to the above figures. ATYPICAL
LOCATION OF THE SWITCHBOARD MUST BE SPECIFIED IN THE ORDER. There must be free access to the distribution box; the quality of
access must not be impaired by small or protruding objects in the way, slippery floors, etc. The distribution box must not be surrounded in such a
way as to impair the transfer of heat to the surrounding area. it is allowed to store and store objects in the vicinity of the distribution box, a
minimum space to remain free must be marked. It is not allowed to place any objects on the distribution box.
B
+
1
5
0
S
800
Size
A
[mm]
B
[mm]
L
[mm]
L1
[mm]
L (for MX)
[mm]
L1 (for MX)
[mm]
S
[mm]
800
1800
3000
4200
6000
7800
678
835
992
1149
1306
1463
678
992
1149
1306
1463
1620
1306
1620
1620
1934
2091
2091
1620
1934
1934
2248
2405
2405
1620
1934
1934
2248
2405
2405
1934
2248
2248
2405
2405
2719
676
833
990
1147
1304
1461