Ventilation unit with heat recuperation

 

DUOVENT

®

 COMPACT RV

 

10

 

3.5 DECLARATION OF CONFORMITY

 

This product type has been tested by the authorised person no. 227, Výzkumný ústav pozemních staveb 

– Certifikační společnost s.r.o., Pražská 

16, 102 21 Praha 10 Hostivař, and a certificate has been issued to it. For a unit of the above type is issued a "Declaration of Conformity” within 
the meaning of Act No. 22/1997 Coll. as amended.

 

4. TRANSPORT, STORAGE, ACCEPTANCE

On the loading surface of the vehicle, the unit must be sufficiently secured against slipping and tipping over. The unit is wrapped in PE foil and 
placed on transport the pallet. The unit is fixed to the transport pallet by means of textile or plastic tie-ups.

 

During loading and unloading by the fork-lift the unit must be lifted suspended on the transport pallet. When transporting the unit supplied without 
the transport pallet it is necessary to support the unit on the underside over the entire surface to prevent damage and 

to pay attention to the 

condensate outlet opening on the underside of the unit

. During lifting by a crane, it is necessary to pass the ropes through the transport pallet 

or under the unit to prevent their slipping. THE UNIT CAN BE HANDLED ONLY BY SUPPORTING OR TYING UNDER THE UNIT FLOOR - THE 
UNIT CANNOT BE LIFTED BY THE CEILING OF THE UNIT OR OTHER PARTS (SUCH AS A/C FLANGES, EXCHANGER OUTLETS ETC.)

 

Ensure proper balancing of the transported unit. The ropes above the unit must be stretched to prevent damage. The outdoor variants of the units 
are fitted with transport profiles for safe passing of slings under the unit bottom.

 

The units must be stored in dry and dust-free areas where the ambient temperature does not fall below + 5 °C. The unit must be protected during 
storage against mechanical damage, dirt and corrosion caused by permanent condensation of water vapour on the surface of the unit. During 
storage, it is necessary to protect the units against snow, rain and other weather conditions (store in a covered warehouse).

 

When accepting the unit, it is necessary to check whether the product was delivered in the agreed design and extent, whether it was not 
damaged during transport, whether there is no condensed water under the plastic wrap (if there is moisture under the packaging, unpack the 
unit and dry in a covered dry place) . In case of damage during transport, the transferee must record the extent of damage in the Delivery Note, 
obtain and send photo documentation to S&P 

UK Ventilation Systems Ltd.

 Failure to comply with this procedure exposes the transferee to the

 

risk of rejection of the complaint by 

S&P UK Ventilation Systems Ltd

.

CAUTION!

 

The unit shall not be transported above

 

persons!

 

CAUTION!

 

The holes in the frame and legs are not

 

intended for the unit hinging.

 

CAUTION!

 

Units with direct evaporator (marked DX and DXr in the unit code) 
must be equipped with a mixing flap (marked MX in the unit code),

 

which ensures, if necessary, min. condenser/evaporator inlet 
temperature of +10 °C.

 

CAUTION!

 

For units with a direct evaporator (marked DX and DXr in the unit code), the 

design air flow through the unit must be observed 

when

 

operating the direct evaporator/condenser. It is acceptable to reduce the flow in cooling and heating mode by a maximum of 20 % of the 
design air flow. For proper operation of the direct evaporator, it is necessary to observe the necessary heat or cold consumption from the

 

heat exchange surface of the evaporator/condenser. If the design amount of energy is not consumed, the condensing unit / heat pump may 
report a fault in the pressure protections (LP, HP) of the cooling circuit and the condensing unit / heat pump may cycle in ON/OFF mode.

 

Содержание DUOVENT COMPACT RV Series

Страница 1: ...DUOVENT COMPACT RV Ventilation unit with heat recuperation www solerpalau co uk...

Страница 2: ...t evaporator 17 5 2 7 Connection of condensate drain 17 5 2 8 Bypass mixing flap 19 5 2 9 Inlet and outlet flap 20 5 2 10 Frequency converter of rotation exchanger 20 5 2 11 Basic accessories 22 5 2 1...

Страница 3: ...ny DUOVENT COMPACTRV incl controlsystemDVAV DCAV DCOP must be commissioned only by the Seller or by the person authorised by the Seller Failure to comply with this condition will result in the termina...

Страница 4: ...pliance by a responsible person The user must ensure that children do not play with the device Cleaning and maintenance of the appliance must not be carried out by children without supervision 2 GENER...

Страница 5: ...unit with mixing flap enabling 100 air circulation For the circulation mode the unit must be fitted with KL input flaps KL input and discharge flap with preparation for mounting the actuator filtering...

Страница 6: ...ON OF FAULT RESET BUTTON OF EL HEATER NOTICE ON LOCATION OF THE CONDENSATE DRAINAGE NECK IN THE BOTTOM OF THE UNIT NOTICE ON CONNECTION OF FAN MOTOR PROTECTIONS WARNING OF THE NECESSITY OF INSULATION...

Страница 7: ...water exchangers evaporator X E 150 B E E 20 Type A mm B mm D mm E mm L mm L for MX mm X mm Y mm DUOVENT RV 800 678 678 470 160 1306 1620 108 104 DUOVENT RV 1800 835 992 600 300 1620 1934 110 5 117 5...

Страница 8: ...include Investor details Information on the installation company or designer Detailed technical data of all components of the unit fan recuperator heater cooler filter Overall dimensions of the unit a...

Страница 9: ...5 51 resp SN 332000 5 51 ed 3 SN 332000 1 ed 2 The ambient temperature must be between 20 and 40 C The unit can transport air without solid fibrous sticky aggressive chemical and explosive additives T...

Страница 10: ...be protected during storage against mechanical damage dirt and corrosion caused by permanent condensation of water vapour on the surface of the unit During storage it is necessary to protect the units...

Страница 11: ...mmended distances from all obstacles to ensure easy maintenance and operation of the unit If the unit is fitted with Digireg or regulation system it is necessary to ensure free space from the system d...

Страница 12: ...rsonal injury The technical characteristics of this manual must not be changed The motors of the unit must not be changed The unit can be connected to the three phase electric grid with alternating vo...

Страница 13: ...age these can be removed only after the attachment of both flanges on the one hand to the unit and on the other to the air distribution systems 5 2 3 CONNECTION OF ELECTRIC HEATER The unit equipped wi...

Страница 14: ...NNECTION The unit fitted with the water heater unit code DCA or DCB is connected to the heating media by means of three way mixing unit see Types of ESU control units The water heater outlets are loca...

Страница 15: ...t exchangers the heating water pipes must not act on the necks of the heat exchangers due to their weight and expansion We recommend the antifreeze mixture as a heat transfer medium for all outdoor un...

Страница 16: ...r can then be disconnected from the cooling water distribution system and removed from the unit Max operating water pressure of water coolers 1 6 MPa Hydrogen exponent of heating water pH 7 9 Heating...

Страница 17: ...refrigerant circuit for direct cooling must be carried out by a specialist company It is mandatory to perform a Refrigerant leak test on the refrigerant circuit This test is performed only by a techn...

Страница 18: ...me of overpressure siphon type SF P 400 PR bottom edge of the condensate tray unit floor level 360 158 height of floor panel lower edge above the floor level incl anti vibration pads of thickness 5 mm...

Страница 19: ...1100 Pa Siphons are used individually for each condensate drain on the unit The condensate drain behind the individual siphons of one unit assembly can be connected to one pipe Never connect the unit...

Страница 20: ...UOVENT COMPACT RV 800 the frequency converter is located inside the rear panel in the ETA section and is accessible after opening the operator side door In DUOVENT COMPACT RV 1800 7800 the frequency c...

Страница 21: ...he frequency converter for sizes DUOVENT COMPACT RV 1800 7800 without mixing with one or two exchanger positions frequency converter Location of the frequency converter for sizes DUOVENT COMPACT RV 18...

Страница 22: ...the unit The siphon must be fitted to the unit gas tightly via the enclosed rubber sleeve Max usable vacuum 1100 Pa Overpressure siphon SF P 400 PR the siphon must be completely filled with water to p...

Страница 23: ...t must never be loaded by tension and twisting of the connected piping Mixing units should be mounted on separate hinges using heating sleeves on the wall pipes or on an auxiliary structure When place...

Страница 24: ...nspection or service activities The connection and earthing of electrical equipment must comply in particular with SN 33 2000 5 51 ed 3 SN 33 2000 5 54 ed 3 and the BP and B decrees on professional co...

Страница 25: ...onfigured temperature Regulation to a constant temperature of the exhaust air uses one temperature sensor in the exhaust pipe the supplied air is heated or cooled to the required set temperature withi...

Страница 26: ...ngs The cable routes of safe and mains voltage must be separated due to electromagnetic compatibility requirements It is necessary to build 2 cable routes at a distance of at least 20 30 cm from each...

Страница 27: ...er pressure sensor optional S8 Thermostat as protection against freezing of the direct evaporator S9 Supply fan pressure sensor mandatory monitors fan operation S10 Intake air temperature sensor S11 R...

Страница 28: ...ter cartridges Flap movability Tight connection to distribution lines Closing of all doors and service holes Any faults must be rectified before starting the unit for the first time 7 2 TRIAL OPERATIO...

Страница 29: ...ts may only be connected to the mains in accordance with the applicable regulations The device must be installed in such a way that under normal operating conditions it cannot come into contact with a...

Страница 30: ...e electric motor bearings If you need to replace the entire unit or fan open the door by opening the locks by turning 90 The fan is located on rubber silent blocks Loosen the 4 nuts lift and remove th...

Страница 31: ...ion exchanger ATTENTION TO OVALITY including the adjustment of the sealing elements 8 2 4 PERIODIC INSPECTIONS Perform periodic inspections at least once a year as part of a summer service inspection...

Страница 32: ...n the event that we find any part is defective the product will be repaired or at the company s discretion replaced without charge provided that the product has been installed in accordance with the e...

Страница 33: ...S OF FAN EC ELECTRIC MOTOR PLASTIC PARTS OF THE CONTROL SYSTEM A B C D E TRANSFORMER CONTROL BOARD SECURING ELEMENTS MAIN SWITCH GLANDS 6 FILTERS WITH PLASTIC FRAME 1 FLAP ACTUATORS a b Open the unit...

Страница 34: ...TS OF THE CONTROL SYSTEM 1 2 3 4 5 voltage transformer control board Securing elements Maim switch Glands a b c d Open the cabinet cover Disconnect cables Remove parts 1 2 3 4 5 Tools used 4 FILTERS W...

Отзывы: