ENGLISH
53
4. Line up electronic component TIMER RTC ECOWATT with J4 connector pins
5. Fit the accessory pressing down
7.2. PROGRAMMING
During programming process must defi ne following parameters:
•
T1, T2, T3:
Start time for each period frame (OFF,00:00-23:59).
•
Period T1, Period T2, Period T3:
Minutes of each time period related to start time defi ned (until 480 minutes).
•
Set point T1, Set point T2, Set point T3:
Set point in % during period frame over operation mode previously selected
(e.g. if
PI PRTC mode is selected and set point T1 is 50%, during period frame the fan will reduce the speed accordingly
with a minus 50% of the pressure set point defi ned).
Example:
MONDAY
TUESDAY
…
SATURDAY
SUNDAY
1:00
T3 = 480 min
SetpointT3 = 25%
T3 = 480 min
SetpointT3 = 25%
T3 = 480 min
SetpointT3 = 25%
T3 = 480 min
SetpointT3 = 25%
2:00
3:00
4:00
5:00
6:00
7:00
8:00
T1 = 60min
SetpointT1 = 50%
T1 = 60min
SetpointT1 = 50%
9:00
T2 = 120 min
SetpointT1 = 50%
T2 = 120 min
SetpointT1 = 50%
10:00
T1 = 60min
SetpointT1 = 50%
T1 = 60min
SetpointT1 = 50%
11:00
12:00
13:00
14:00
T2 = 120 min
SetpointT1 = 50%
T2 = 120 min
SetpointT1 = 50%
15:00
16:00
22:00
23:00
T3 = 480 min
SetpointT3 = 25%
T3 = 480 min
SetpointT3 = 25%
T3 = 480 min
SetpointT3 = 25%
T3 = 480 min
SetpointT3 = 25%
0:00