![S&P CADB-N-D Скачать руководство пользователя страница 25](http://html1.mh-extra.com/html/sandp/cadb-n-d/cadb-n-d_installation-manual_3148775025.webp)
25
7.2. MAINTENANCE SPACE
CADB/CADT-N-D Horizontal and vertical with and without By-pass
CADB/CADT-N-D Horizontal and vertical with and without By-pass
MODEL
A
(mm)
B
(mm)
C
(mm)
D
(mm)
E
(mm)
Ø
(mm)
CADB/CADT-N-DI/DC 05
975
650
480
180
178
200
CADB/CADT-N-DI/DC 08
1150
850
480
180
228
250
CADB/CADT-N-DI/DC 12
1500
1050
620
250
278
315
CADB/CADT-N-DI/DC 18
1600
1150
620
250
303
355
CADB/CADT-N-DI/DC 23
1750
1300
650
265
340
355
CADB/CADT-N-DI/DC 30
1950
1500
650
265
390
400
CADB/CADT-N-D/DC 45
2050
1600
720
300
415
450
CADB/CADT-N-DI/DC 55
2700
2000
820
325
515
500
CADB/CADT-N-DI/DC 80
2850
2150
990
410
553
710
A
B
C
MODEL
A
(mm)
B
(mm)
C
(mm)
D
(mm)
E
(mm)
Ø
(mm)
CADB/CADT-N-D 05
650
650
360
180
178
200
CADB/CADT-N-D 08
850
850
360
180
228
250
CADB/CADT-N-D 12
1050
1050
500
250
278
315
CADB/CADT-N-D 18
1150
1150
500
250
303
355
CADB/CADT-N-D 23
1300
1300
530
265
340
355
CADB/CADT-N-D 30
1500
1500
530
265
390
400
CADB/CADT-N-D 45
1600
1600
600
300
415
450
CADB/CADT-N-D 55
2000
2000
650
325
515
500
CADB/CADT-N-D 80
2150
2150
820
410
553
710
A
B
C+100
C
B/2 + 100
B/2 + 100
Pressure tappings (Fig.2)
Both pressure tappings (d) as the caps (e) and the screws (f) necessary for installation are supplied in a plastic bag.
These pressure tappings (d) should be installed on the panel in the area of filters. Using the pre drilled holes.
The pressure tappings (d) have to be installed. If the tappings (d) are not used, the holes have to be closed with the plastic caps (e) to avoid
leakages.
d) Pressure tapping
e) Cap
f) Screw: to fix the pressure tappings
Содержание CADB-N-D