background image

14

6.4. RANGE SPECIFICATIONS

D Versions: without heater battery

Model

Complete unit

Fan

Air connections 

diameter

(mm)

Nominal 

airfl ow

(m

3

/h)

Effi ciency*

(%)

Electrical 

supply

Speed 

(r.p.m.)

Maximum 

current

(A)

CADB-HE D 04 ECOWATT

200

450

87

1/230V, 50Hz

3700

0,95

CADB-HE D 08 ECOWATT

250

800

86,4

1/230V, 50Hz

2650

1,3

CADB-HE D 12 ECOWATT

315

1.200

85,3

1/230V, 50Hz

2550

1,6

CADB-HE D 16 ECOWATT

315

1.600

85,5

1/230V, 50Hz

2845

2,0

CADB-HE D 21 ECOWATT

400

2.100

86,5

1/230V, 50Hz

1580

2,2

CADB-HE D 27 ECOWATT

400

2.700

83,8

1/230V, 50Hz

2450

3,6

CADT-HE D 33 ECOWATT

400

3.300

88,4

3/400V, 50Hz

2600

2,0

CADT-HE D 45 ECOWATT

400x600

4.500

88,9

3/400V, 50Hz

2200

3,0

CADT-HE D 60 ECOWATT

500x700

6.100

87,9

3/400V, 50Hz

2200

3,0

CADT-HE D 100 ECOWATT

1100x650

10.000

87,9

3+N/400V, 50Hz

2160

5,8

* Wet effi ciency referring to nominal airfl ow, outdoor conditions (-5ºC / 80% RH) and indoor (20ºC / 50% RH).

DC Versions: with built-in hot water coil

Model

Complete unit

Fan

Hot water coil

Air

connections 

diameter 

(mm)

Nominal 

airfl ow 

(m

3

/h)

Effi ciency*

(%)

Electrical supply Speed 

(r.p.m.)

Maximum 

current

(A)

Heat power 

T

WATER

 80/60ºC

(kW)

Heat power

T

WATER

 50/45ºC

(kW)

CADB-HE DC 04 ECOWATT

200

450

87

1/230V, 50Hz

3700

0,95

2,7

1,6

CADB-HE DC 08 ECOWATT

250

800

86,4

1/230V, 50Hz

2650

1,3

5,1

3,1

CADB-HE DC 12 ECOWATT

315

1.200

85,3

1/230V, 50Hz

2550

1,6

7,1

4,3

CADB-HE DC 16 ECOWATT

315

1.600

85,5

1/230V, 50Hz

2845

2,0

8,6

5,3

CADB-HE DC 21 ECOWATT

400

2.100

86,5

1/230V, 50Hz

1580

2,2

12,6

7,8

CADB-HE DC 27 ECOWATT

400

2.700

83,8

1/230V, 50Hz

2450

3,6

16,2

10,0

CADT-HE DC 33 ECOWATT

400

3.300

88,4

3/400V, 50Hz

2600

2,0

18,2

11,1

CADT-HE DC 45 ECOWATT

400x600

4.500

89,0

3/400V, 50Hz

2200

3,0

25,6

15,5

CADT-HE DC 60 ECOWATT

500x700

6.100

88,9

3/400V, 50Hz

2200

3,0

34,7

21,1

CADT-HE DC 100 ECOWATT

1100x650

10.000

87,9

3+N/400V, 50Hz

2160

5,8

58,9

35,4

* Wet effi ciency referring to nominal airfl ow, outdoor conditions (-5ºC / 80% RH) and indoor (20ºC / 50% RH).

DI Versions: with built-in electric battery

Model

Complete unit

Fan

Electrical heater battery

Air 

connections 

diameter

(mm)

Nominal 

airfl ow 

(m

3

/h)

Effi ciency*

(%)

Electrical supply

Speed 

(r.p.m.)

Maximum 

current

(A)

Electrical 

supply

Power 

(kW)

Maximum 

current

(A)

CADB-HE DI 04 ECOWATT

200

450

87

1/230V, 50Hz

3700

0,95

1/230V, 50Hz

1

4,5

CADB-HE DI 08 ECOWATT

250

800

86,4

1/230V, 50Hz

2650

1,3

1/230V, 50Hz

2

9,1

CADB-HE DI 12 ECOWATT

315

1.200

85,3

1/230V, 50Hz

2550

1,6

1/230V, 50Hz

3

11,4

CADB-HE DI 16 ECOWATT

315

1.600

85,5

1/230V, 50Hz

2845

2,0

1/230V, 50Hz

3,5

15,9

CADT-HE DI 21 ECOWATT

400

2.100

86,5

1/230V, 50Hz

1580

2,2

3/400V, 50Hz

6

9,1

CADT-HE DI 27 ECOWATT

400

2.700

83,8

1/230V, 50Hz

2450

3,6

3/400V, 50Hz

6

9,1

CADT-HE DI 33 ECOWATT

400

3.300

88,4

3/400V, 50Hz

2600

2,0

3/400V, 50Hz

7,5

11,4

CADT-HE DI 45 ECOWATT

400x600

4.500

89,0

3/400V, 50Hz

2200

3,0

3/400V, 50Hz

9

13,7

CADT-HE DI 60 ECOWATT

500x700

6.100

88,9

3/400V, 50Hz

2200

3,0

3/400V, 50Hz

12

18,2

CADT-HE DI 100 ECOWATT

1100x650

10.000

87,9

3+N/400V, 50Hz

2160

5,8

3/400V, 50Hz

24

36,4

* Wet effi ciency referring to nominal airfl ow, outdoor conditions (-5ºC / 80% RH) and indoor (20ºC / 50% RH).

Содержание CADB HE ECOWATT Series

Страница 1: ...EN CADB T HE ECOWATT 2018...

Страница 2: ......

Страница 3: ...27 6 6 4 1 1 04 to 27 models Manual adjustment by REB ECOWATT accessory 27 6 6 4 1 2 33 to 100 models Manual adjustment by REB ECOWATT accessory 28 6 6 4 2 VAV Control variable air ow with CO2 sensor...

Страница 4: ...proof of the product s conformity with current EU regulations 3 GENERAL INSTRUCTIONS A hazard analysis of the product has been carried out as provided in the Machine Directive This manual contains inf...

Страница 5: ...ied without pallets The unit can be handled by a pallet transporter a forklift or a crane The handling machines will be adapted to the load and the lifting conditions In all cases the lifting will be...

Страница 6: ...Model A B C 4 1558 798 8 894 1788 948 12 869 1738 1088 16 994 1988 1278 21 1169 2338 1678 27 1169 2338 1678 33 1169 2338 1678 The model 04 does not have central support The installer must make sure t...

Страница 7: ...t the ceiling structure and the securing elements can bear the weight of the unit taking into account that it is a dynamic load Models 04 to 33 Model Weight kg 4 139 8 175 12 182 16 227 21 325 33 412...

Страница 8: ...e securing elements can bear the weight of the unit taking into account that it is a dynamic load Model Weight kg 45 577 60 710 For all con gurations Once secured the device in correct position the in...

Страница 9: ...by 3 pieces a Drainpipe b Female screw c Joint ring posar aquesta frase a sota d aquest punt a Horizontal versions of CADB T HE 04 to 33 b Horizontal versions of CADB T HE 45 and 60 c Vertical version...

Страница 10: ...tical versions LV RV for outdoor installation In addition these versions have feet that allow direct placement on the ground In horizontal version models 04 to 33 ensure the suf cient space below the...

Страница 11: ...33 TPP HE V 21 27 CADB T HE D DI DC 27 TPP HE H 21 27 33 TPP HE V 21 27 CADT HE D DI DC 33 TPP HE H 21 27 33 TPP HE V 33 CADT HE D DI DC 45 TPP HE H 45 TPP HE V 45 CADT HE D DI DC 60 TPP HE H 60 TPP H...

Страница 12: ...0 400 860 400 250 400 950 173 12 1050 425 1700 500 400 1000 400 315 400 900 180 16 1240 450 1950 600 500 1190 425 315 400 1150 225 21 27 1640 550 2300 800 700 1590 525 400 500 1300 323 33 1640 650 230...

Страница 13: ...0 400 315 227 21 970 1270 1750 400 500 400 325 33 1170 1270 1750 400 500 400 412 45 1120 1580 2100 400 600 600 400 577 60 1500 1630 2250 400 800 700 500 710 100 2050 1630 2250 400 1000 1100 650 842 6...

Страница 14: ...5 1 230V 50Hz 1580 2 2 12 6 7 8 CADB HE DC 27 ECOWATT 400 2 700 83 8 1 230V 50Hz 2450 3 6 16 2 10 0 CADT HE DC 33 ECOWATT 400 3 300 88 4 3 400V 50Hz 2600 2 0 18 2 11 1 CADT HE DC 45 ECOWATT 400x600 4...

Страница 15: ...n damage it The following table indicate the size and type o thread used on water coils for DC versions CADB T HE MODEL THREAD 04 08 12 16 21 27 and 33 1 2 45 60 and 100 1 To ensure the installation o...

Страница 16: ...the pressure provided by the fan The horizontal sections should have a minimum slope of 2 Condensation connection 6 6 ELECTRICAL CONNECTIONS The CADB T HE ECOWATT range are supplied without a complet...

Страница 17: ...g fans with EC motors 230V supply voltage OUTDOOR SWITCH ELECTRICAL SUPPLY 230V 1 50Hz Control connector Speed regulation 0V Stop 10V max speed Make the bridge between OUT and IN for Vmax Control conn...

Страница 18: ...18 Horizontal version CADB T HE 33 LH RH In this size the units have plug fans equipped with EC motors with power supply to three phase 400V...

Страница 19: ...motors with power supply to three phase 400V OUTDOOR SWITCH ELECTRICAL SUPPLY 400V III 50Hz Control connector Speed regulation 0V Stop 10V max speed Make the bridge between OUT and IN for Vmax Contro...

Страница 20: ...he resistances must be carried out by the electric installer 6 6 2 Connecting the By pass All heat recovery units of the CADB T HE ECOWATT range have an internal by pass The by pass damper is supplied...

Страница 21: ...rm an external electrical operation control board The installer is responsible for the correct operation of the electrical control specially re garding those safety requirements to avoid re risk due t...

Страница 22: ...22 CADB HE DI 08 2kW 230V CADB HE DI 12 3kW 230V D HEATER REGULATOR E ON OFF SWITCH F RELAY G LINE PROTECTION H TEMPERATURE PROBE TG K330 J FLOW DETECTOR KM FAN RELAY X TIMER MCR 1...

Страница 23: ...23 CADB HE DI 16 3 5kW 230V CADB HE DI 21 27 6kW 400V D HEATER REGULATOR E ON OFF SWITCH F RELAY G LINE PROTECTION H TEMPERATURE PROBE TG K330 J FLOW DETECTOR KM FAN RELAY X TIMER MCR 1...

Страница 24: ...24 CADB HE DI 33 7 5kW 400V CADB HE DI 45 9kW 400V D HEATER REGULATOR E ON OFF SWITCH F RELAY G LINE PROTECTION H TEMPERATURE PROBE TG K330 J FLOW DETECTOR KM FAN RELAY X TIMER MCR 1...

Страница 25: ...2kW 400V t s s t Khd Khd Khd E E E dd y D z E s ZD ZD dW dW Z Z CADT HE 100 24kW 400V D HEATER REGULATOR E ON OFF SWITCH F RELAY G LINE PROTECTION H TEMPERATURE PROBE TG K330 J FLOW DETECTOR KM FAN RE...

Страница 26: ...AV mode Recommended accessories depending on the unit size and the control mode Model Accessories for VAV via CO2 Accessories for COP Accessories for CAV Converter Sensor Converter Sensor Electronic r...

Страница 27: ...ons with electrical resistances The direct stop of the fans without a temporized stop would cause a high temperatu re rise of the resistances and the consequent risk of re inside the unit 6 6 4 1 1 04...

Страница 28: ...ls Manual adjustment by REB ECOWATT accessory Simultaneous control of the supply and extract fans Supply fan Extract fan ZK K Z h h D Z K z Kt D Z K z Kt h h ZK K Z E ZK Z Z z D Z K s Z z Kt Z E D ZZK...

Страница 29: ...ed 0 10V The 0V signal corresponds to the fan stop while the signal of 10V corresponds to fan maximum speed To perform the speed regulation in VAV with speed control with external sensor of CO2 or si...

Страница 30: ...onnection of the different components 1 Connect the pressure transmitter TDP D accessory to the speci c pressure taps there are in the heat recovery unit Ensure that pressure taps and Same sign in the...

Страница 31: ...the pressure must be constant in the duct system The value of this pressure must be determined by experimenting during the system start up process All CADB HE are equipped with EC motors single phase...

Страница 32: ...32 AERO REG CONTROL Accessory TDP D Accessory EXTRACTION DUCTS SYSTEM SUPPLY DUCTS SYSTEM TDP D Accessory EXTRACTION DUCTS SYSTEM SUPPLY DUCTS SYSTEM AERO REG CONTROL Accessory...

Страница 33: ...he position of the pressure taps depends on the model HORIZONTAL MODELS Horizontal models CADB T HE 04 to 33 LH RH on the side of inlet conection panel Horizontal models CADB T HE 45 to 60 LH RH on su...

Страница 34: ...carefully the bypass g 2 4 Disconnect the electrical connector that feeds the bypass 5 Turn the bypass according to image g 3 and 4 6 Reconnect the electrical power connector of bypass 7 Place the by...

Страница 35: ...35 Horizontal Factory con guration LH RH Examples of some of the con gurations that is possible to obtain from factory con guration EXHAUST AIR FRESH AIR Conf LV Conf LH Conf RV Conf RH...

Страница 36: ...E 08 LH BA DX HE 08 LH BA AFC HE 08 LH FBL HE 08 H FB CA HE 08 H RH BA AF HE 08 RH BA DX HE 08 RH BA AFC HE 08 RH CADB HE D DI DC 12 LH BA AF HE 12 LH BA DX HE 12 LH BA AFC HE 12 LH FBL HE 12 H FB CA...

Страница 37: ...X HE 21 27 RV BA AFC HE 21 27 RV CADT HE D DI DC 33 LV BA AF HE 33 LV BA DX HE 33 LV BA AFC HE 33 LV FBL HE 33 V FB CA HE 33 V RV BA AF HE 33 RV BA DX HE 33 RV BA AFC HE 33 RV CADT HE D DI DC 45 LV BA...

Страница 38: ...ing frame verify that the locating lip in the frame is positioned in the top side Centering frame locating lip 3 Put the self adhesive sealing strip delivered in a bag included with the module around...

Страница 39: ...its own weight Fix the module to the heat recovery unit permanently The access to xing points is performed by the side of the unit removing one of the side panes from the CADB or from the module maint...

Страница 40: ...el to the CADB HE 6 Particularities of the modules with coils In the installation of external modules accessories with water coil or refrigerant coil the assembly of the module should be done in the w...

Страница 41: ...LV RV 2 400 83 2 2 42 9 22 3798 16 1 BA AF HE 45 3 400 88 2 5 41 29 3 5045 13 2 BA AF HE 60 4 400 56 1 9 42 7 31 5345 10 3 6 9 2 2 Cold water coils for for 4 pipes installation Model Air Fresh Air Exh...

Страница 42: ...04 320 56 1 8 16 18 33 4 8 1 8 33 1 2 0 7 BA DX HE 08 600 47 1 7 33 6 3 5 64 6 1 1 2 BA DX HE 12 900 105 2 4 33 2 6 5 3 92 4 7 1 7 BA DX HE 16 1 200 117 2 5 33 7 6 7 2 134 4 8 1 8 BA DX HE 21 1 600 76...

Страница 43: ...f CADB T HE 45 and 60 The access to lters can be done by the side panels Vertical con gurations of CADB T HE 45 60 and 100 The access to lters can be done by two sides of the unit removing the speci c...

Страница 44: ...3 G4 AFR HE 400 33 M5 AFR HE 400 33 F7 AFR HE 400 33 F9 CADT HE D DI DC 45 600x400 AFR HE 450 45 G4 AFR HE 450 45 M5 AFR HE 450 45 F7 AFR HE 450 45 F9 CADT HE D DI DC 60 700x500 AFR HE 500 60 G4 AFR H...

Страница 45: ...the heat exchanger from the side panels Alternatively it is possible to disassemble the heat exchanger from the bottom panels However it is necessary to perform a major number of operations to procee...

Страница 46: ...ased remove it Clean the heat exchanger with blowing with compressed air Vertical models CADB T HE 04 to 100 Due to the dimensions and weight of heat exchanger the cleaning of it has to be perform in...

Страница 47: ...Contact the S P post sales service Reset by pushing the button RESET all the thermal protectors of the resistance Insuf cient performance of the exchanger Fins dirty Clean the exchanger Formation of f...

Страница 48: ...S P SISTEMAS DE VENTILACI N S L U C Llevant 4 Pol gono Industrial Llevant 08150 Parets del Vall s Barcelona Espa a Tel 34 93 571 93 00 Fax 34 93 571 93 01 www solerpalau com Ref 7081014900...

Отзывы: