6. INSTALLATION
6.1. INTRODUCTION
Horizontal models size 04, 08, 16 and 21
These models are designed to be installed hanging from the ceiling or located behind a false ceiling.
The 04, 08, 16 and 21 models have four metal brackets, one on each lower corner. Using studded rods
(Ø 8 mm), it can be secured to the ceiling and levelled.
The installer must make sure that the ceiling structure and the securing elements can bear the weight
of the device, taking into account that it is a dynamic load.
To prevent the transmission of vibrations from the unit to the rest of the installation, it is necessary
that the installer use specifi c isolation elements, such as antivibration devices in the supports, fl exible
sleeves between the unit and the ducts, and fl exible couplings between the water connections and the
pipelines.
Model
Weight (kg)
4
147
8
183
16
235
21
333
Vertical models size 40 and 54
Vertical models size 40 and 54 are supplied with a perimetral bed. This bed must be in contact with the
ground or with a fl at surface. It is essential that the weight of the equipment is distributed between all
points of support to prevent unit deformation.
The installer must make sure that the ceiling structure and the securing elements can bear the
weight of the unit, taking into account that it is a dynamic load.