5. REMOTE CONTROL ADJUSTMENTS - INSTALLER
The remote control allows:
- Adjust the airflows (1
st
speed, 2
nd
speed, 3
rd
speed)
- Timer for adjusting the filter maintenance period (6, 9, 12 or 15 months) (factory
setting 9 months)
- Adjust the balance of supply / extraction airflows
5.1 Adjustment of the airflows
To adjust the airflow turn the potentiometer carefully clock wise with a small screw driver.
The potentiometer has 16 positions (from 0 to F). To each of these positions are assigned
an output voltage to the fans. As higher the output voltage as higher the airflow and
viceversa.
F
actory setting: 1
st
speed =
3
; 2
nd
speed =
7
and 3
rd
speed =
F
.
Adjustment of the filter maintenance period
It is possible to set the period to 6, 9, 12 or 15 months (9 months factory setting). The
filter clogging depends on the pollution of the area where the unit is installed. We
recommend checking the time in which the filter clogs and adjusting this period. It is
advisable to do this after the second filter change. Of course, after the installation, the
extract air is dusty and not representative. During the second filter check, if you notice
that the filters are clean you can increase the time (12 or 15, months), if you notice that the
filters are very dirty you should decrease the time (6 months).
Open the box and adjust the timing as shown. To do this, set the micro contacts 1 and 2
as shown in the drawings below to adjust the month.
(3
rd
) high speed
adjustment
(2
nd
) middle speed
adjustment
(1
st
) low speed
adjustment
Filters alarm timing
0
100
200
300
400
500
0
100
200
300
400
500
600
0
10
20
30
40
50
60
4V
6V
8V
10V
p
sf
[Pa]
p
sf
[mmcda]
q
v[m
3
/h]
CAD HE 450 EC H BASIC
5. REMOTE CONTROL ADJUSTMENTS - INSTALLER
The remote control allows:
- Adjust the airflows (1
st
speed, 2
nd
speed, 3
rd
speed)
- Timer for adjusting the filter maintenance period (6, 9, 12 or 15 months) (factory
setting 9 months)
- Adjust the balance of supply / extraction airflows
5.1 Adjustment of the airflows
To adjust the airflow turn the potentiometer carefully clock wise with a small screw driver.
The potentiometer has 16 positions (from 0 to F). To each of these positions are assigned
an output voltage to the fans. As higher the output voltage as higher the airflow and
viceversa.
F
actory setting: 1
st
speed =
3
; 2
nd
speed =
7
and 3
rd
speed =
F
.
Adjustment of the filter maintenance period
It is possible to set the period to 6, 9, 12 or 15 months (9 months factory setting). The
filter clogging depends on the pollution of the area where the unit is installed. We
recommend checking the time in which the filter clogs and adjusting this period. It is
advisable to do this after the second filter change. Of course, after the installation, the
extract air is dusty and not representative. During the second filter check, if you notice
that the filters are clean you can increase the time (12 or 15, months), if you notice that the
filters are very dirty you should decrease the time (6 months).
Open the box and adjust the timing as shown. To do this, set the micro contacts 1 and 2
as shown in the drawings below to adjust the month.
(3
rd
) high speed
adjustment
(2
nd
) middle speed
adjustment
(1
st
) low speed
adjustment
Filters alarm timing
5. REMOTE CONTROL ADJUSTMENTS - INSTALLER
The remote control allows:
- Adjust the airflows (1
st
speed, 2
nd
speed, 3
rd
speed)
- Timer for adjusting the filter maintenance period (6, 9, 12 or 15 months) (factory
setting 9 months)
- Adjust the balance of supply / extraction airflows
5.1 Adjustment of the airflows
To adjust the airflow turn the potentiometer carefully clock wise with a small screw driver.
The potentiometer has 16 positions (from 0 to F). To each of these positions are assigned
an output voltage to the fans. As higher the output voltage as higher the airflow and
viceversa.
F
actory setting: 1
st
speed =
3
; 2
nd
speed =
7
and 3
rd
speed =
F
.
Adjustment of the filter maintenance period
It is possible to set the period to 6, 9, 12 or 15 months (9 months factory setting). The
filter clogging depends on the pollution of the area where the unit is installed. We
recommend checking the time in which the filter clogs and adjusting this period. It is
advisable to do this after the second filter change. Of course, after the installation, the
extract air is dusty and not representative. During the second filter check, if you notice
that the filters are clean you can increase the time (12 or 15, months), if you notice that the
filters are very dirty you should decrease the time (6 months).
Open the box and adjust the timing as shown. To do this, set the micro contacts 1 and 2
as shown in the drawings below to adjust the month.
(3
rd
) high speed
adjustment
(2
nd
) middle speed
adjustment
(1
st
) low speed
adjustment
Filters alarm timing
Position Potentiometer
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
Assigned Voltage (V)
2,5
3
3,5
4
4,5
5
5,5
6
6,5
7
7,5
8
8,5
9
9,5
10
5. REMOTE CONTROL ADJUSTMENTS - INSTALLER
The remote control allows:
- Adjust the airflows (1
st
speed, 2
nd
speed, 3
rd
speed)
- Timer for adjusting the filter maintenance period (6, 9, 12 or 15 months) (factory
setting 9 months)
- Adjust the balance of supply / extraction airflows
5.1 Adjustment of the airflows
To adjust the airflow turn the potentiometer carefully clock wise with a small screw driver.
The potentiometer has 16 positions (from 0 to F). To each of these positions are assigned
an output voltage to the fans. As higher the output voltage as higher the airflow and
viceversa.
F
actory setting: 1
st
speed =
3
; 2
nd
speed =
7
and 3
rd
speed =
F
.
Adjustment of the filter maintenance period
It is possible to set the period to 6, 9, 12 or 15 months (9 months factory setting). The
filter clogging depends on the pollution of the area where the unit is installed. We
recommend checking the time in which the filter clogs and adjusting this period. It is
advisable to do this after the second filter change. Of course, after the installation, the
extract air is dusty and not representative. During the second filter check, if you notice
that the filters are clean you can increase the time (12 or 15, months), if you notice that the
filters are very dirty you should decrease the time (6 months).
Open the box and adjust the timing as shown. To do this, set the micro contacts 1 and 2
as shown in the drawings below to adjust the month.
(3
rd
) high speed
adjustment
(2
nd
) middle speed
adjustment
(1
st
) low speed
adjustment
Filters alarm timing
Содержание CAD HE 450 H BASIC
Страница 1: ...CAD HE 450 H BASIC...
Страница 2: ......
Страница 3: ...3 ESPA OL 4 ENGLISH 20 FRAN AIS 36 ITALIANO 51 NEDERLANDS 67 CESKY 82...
Страница 98: ......
Страница 99: ......