7
2.3. INSTALLATION
Ceiling:
30 mm
To avoid the vibration transmission and noise to the duct, we
recommend to use fl exible connections.
Supply/Extract Air:
Installation of fl exible silencers type LAF
95 (article code: 5209358600 / LAF 95 0,5M or 5209358500 /
LAF 95 1M)
Outdoor/Exhaust Air:
connection with fl exible duct thermally
insulated type GP ISO ECOSOFT (article number: 5209346600
GP-ISO 100/25 6M ECOSOFT)
lateral view
The drain pipe should be installed with a drop of min.
1% to assure a good drainage and has to be connected
to a with water fi lled siphon.
Please assure that the access opening to the unit is big
enough to allow maintenance or replacing the unit.
It is recommended to install the ALTAIR in the heated zone of the house.
The minimum temperature should not be less than +10ºC.
In climate zones where outdoor temperatures are often under -10ºC it
is recommended to install a pre-heater.
The ALTAIR heat recovery unit is designed for indoor installation.