2.7. ALARM INDEX
Through the LED located in the “A” button on the remote control it is possible to supervise the status of the unit. This
LED will show the alarm in case of a failure or missfunction on the unit. Depending on the risk level of the generated
alarm the unit will stop for safety reasons.
Priority
Alarm
LED
Action
1
Extract fan error
1 red blink
unit stops
2
Supply fan error
2 red blinks
unit stops
3
Supply air temperature <5ºC
4 red blinks
unit stops. Every 2 hours the unit starts for
5 minutes to check if conditions allow normal
operation.
4
Humidity sensor
5 red blinks
normal operation
5
ODA sensor error (fresh air)
7 red blinks
normal operation
6
SUP sensor error (supply air)
8 red blinks
normal operation
7
ETA sensor error (extract air)
9 red blinks
normal operation
8
EHA sensor error (exhaust air)
10 red blinks
normal operation
9
Filter alarm
Red, continous
after 60 days the unit stops if fi lter is not
changed an alarm reseted
2.8. GENERAL DATA
Height
850 mm
Width
550 mm
Depth
170 mm
Connection
Ø 95 mm
Weight
20 kg
Material
EPP body; front cover plate painted in white
Drain
¾” (drainpipe)
Power supply
230 V AC, 50 Hz
Maximum consumption
55 W
Airfl ow
120 m³/h
Radiated noise LwA
52,2 dB(A)
Ambient temperature
from +10°C to +50°C
Exterior temperature
until -18°C
Extract temperature
from +10°C to +50°C
Speed control
according to the adjusted speed on the remote control
Fans
2 units, forward curved with EC motor
Filters
supply G4 /extraction G4
Thermal effi ciency
83%
Protection
IP21
Protección
IP21