61
Holding registers (Read and write)
Register Discrete input
Data type
Range
Default Comments
40001
Addressing
16bits
1-247
1
Channel
40002
Baud Rate
16bits
48 : 4800
96 : 9600
192 : 19200
384 : 38400
192
Bus speed
40003
Parity
16bits
0 : EVEN
1 : ODD
2 : Non parity
0
Parity
40011
SetPoint HR
16bits
60-100
70
Set Point for HR version
(%) MF4 mode
40012
SetPoint VOC/CO2
16bits
800-2000
1200
Set Point for VOC and
CO2 versions (ppm) MF4
mode
40013
Relay SetPoint
Hysteresis HR
16bits
0-20
5
Relay hysteresis for HR
set point (%)
40014
Relay SetPoint
Hysteresis VOC/CO2
16bits
0-500
200
Relay hysteresis for VOC
and CO2 set point (ppm)
40015
Light guide intensity
16bits
0-100
80
Led diffusor intensity (%)
MF4 mode
40021
Temp Measurement
Tuning
16bits
-30-30
0
Temperature reading
adjustment (°C)
40022
VOC/CO2
Measurement Tuning
16bits
-200-200
0
VOC and CO2 reading
adjustment (ppm)
40023
HR Measurement
Tuning
16bits
-10-10
0
HR reading adjustment
(%)
40024
Green LED
illumination stop HR
16bits
0-60
60
Green LED end for HR
version (%)
40025
Red LED
illumination start HR
16bits
80-100
80
Red LED start for HR
version (%)
40026
Green LED
illumination stop
VOC/CO2
16bits
400-800
800
Green LED end for VOC/
CO2 version (%)
40027
Red LED illumination
start VOC/CO2
16bits
800-2000
1200
Red LED start for VOC/
CO2 version (%)