8.1. External ON/OFF control signal
16
System control logic
1. The cooling demand is managed by dry contact sent to the CDU (terminals CLA/CLB) see page 15
2. The speed of compressor controls the LP to reach the set point tuned by the installer (A02/B02) see page 25
3. The low pressure is function of the evaporating temperature required for the showcase. (Tev = Tair_sc –
T).
4. Electronic Expansion Valve (EEV) of the CDU controls the HP to reach the HP target.
This HP optimal target is calculated in accordance with ambient outside temperature and the LP set point.
5. Showcase EEV controls the superheat at the evaporator side
Defrost control logic
1. CDU compressors and fans should stop before the evaporator defrost.
2. Dry contact signal is sent to the CDU when defrost is requested Defrost (terminal CLA/CLB) see page 15.
3. Compressors will stop gradually depending current speed.
4. For installation with several evaporators, one EEV evaporators side must stay opened to avoid High Pressure
failure during stopping session. See wiring example page 18