Trouble shooting guide  

If you faced to a problem in a use of our heat pump water heater system, please check the 
following things prior to calling for a support. 

 
For those problems not listed in the list above, an inspection provided by a skilled engineer 
is required. Please contact the distributor. 
 

Caution: 

Do not shut the electricity supplied to the heat pump system even if you go away from 
home and do not use hot water for a long while. 
If the system is equipped with freeze protect heaters, also do not shut the power supply to 
the heaters. 
Failure to do so may cause a crack on the pipes due to the pipes getting frozen. 
 
 

Status 

Considerable Causes 

Action to Take 

No hot water 
comes out of 
water tap 
 
Temperature 
of hot water is 
too low 

Small or no hot water is left in 
the storage tank. 

- Stop using hot water and wait for about 1 
hour 
- Consider a change of the electricity 
supply off-peak mode (Length of power-
supply hours may be too short for the 
water heating cycle to cover the hot water 
consumption) 

Air removing procedure from the 
heat pump system may be 
insufficient. 

- Open the water drain plugs on the Heat 
Pump Unit to remove air from water circuit. 
(Be careful for burning) 

Filter on cold inlet connector may 
be blocked. 

- Check the filter and remove if there is any 
blockage 

Water flow speed may be 
dropped due to the heat pump 
piping bend, blockage or crush. 

- Check for any piping bend or crush and 
remove if any 

Pipes may be frozen. 

- If frozen area is found on the piping, melt 
the ice on the pipe and provide a heat 
insulation 

Stop valve is closed. 

- Open the valve 

Air absorption is not sufficient 
due to a blockage on the 
evaporator. 

-Remove the object being blocking the air 
flow through the evaporator  
(e.g. fallen leaves, grass, snow, etc.) 

Содержание GAUS-160EQTB

Страница 1: ...AUS 160EQTB Heat Pump Unit GS3 45HPA AU This appliance is not to be used by persons including children with reduced physical sensory or mental capabilities or lack of experience and knowledge unless t...

Страница 2: ...S This water heater may be protected by one or more patents or registered designs in the name of Sanden Australia Pty Ltd TRADE MARKS Registered trademark of Sanden Australia Pty Ltd Note Every care h...

Страница 3: ...s currently available It s even more efficient when connected to off peak power and the noise level is so low it will operate unobtrusively throughout the night How it works The Heat Pump Water Heater...

Страница 4: ...Sanden Heat Pump Owner s Manual Page 4 of 20...

Страница 5: ...Sanden Heat Pump Owner s Manual Page 5 of 20 LPG...

Страница 6: ...the unit not being guaranteed Anywhere the lowest temperature reached is under minus 20 degrees centigrade Indoors Applies only to the heat pump unit Anywhere not completely flat unstable or where dr...

Страница 7: ...Sanden Heat Pump Owner s Manual Page 7 of 20...

Страница 8: ...relevant standards Only a licensed person will have insurance protecting their workmanship for six years The unit has been specifically designed for domestic hot water heating and is not suitable for...

Страница 9: ...r no hot water is left in the storage tank Stop using hot water and wait for about 1 hour Consider a change of the electricity supply off peak mode Length of power supply hours may be too short for th...

Страница 10: ...1 HP inlet temperature thermistor wire short circuit E004 HP discharge over temperature 1 E022 HP outlet temperature thermistor wire short circuit E005 HP discharge over temperature 2 E023 HP discharg...

Страница 11: ...places on the heat pump unit Close the plugs after no air is confirmed in the water Connect the power to the heat pump unit and leave a hot water tap open in the home for three minutes Close the house...

Страница 12: ...power supply is cut off i e if it is connected to off peak power However the system will automatically start operation once the electricity becomes available System operation if connected to off peak...

Страница 13: ...ver terminal block cover and screw clamp fitting Connect the power supply line to the terminal block Hold the power supply line below the terminal block with the screw clamp fitting Attach the termina...

Страница 14: ...aminants Water with a pH less than 6 0 may be treated to raise the pH It is recommended that an analysis of the water from a rainwater tank be conducted before connecting this type of water supply to...

Страница 15: ...y 4 5 kW 1 Power consumption Mid Winter Season 0 91 kW 1 1 03kW 2 COP Mid Winter Season 5 0 1 4 4 2 Circuit Breaker Size 20A Design Pressure High Low 14 9 0MPa Protection Raining Class IPX4 Max Operat...

Страница 16: ...Sanden Heat Pump Owner s Manual Page 16 of 20 Hot water storage tank unit REFER Drawing provided with tank GAUS 315EQS Model No GAUS 315EQT GAUS 250EQTB GAUS 160EQTB...

Страница 17: ...ting valve isolation valves check valves electrical switches pumps or fuses 6 The Heat Pump Water Heater System must be sized to supply the hot water demand in accordance with the guidelines in the Sa...

Страница 18: ...Subject to any statutory provisions to the contrary this warranty excludes any and all claims for damage to furniture carpets walls foundations or any other consequential loss either directly or indi...

Страница 19: ...Product Details Heat Pump Serial Number from label on right end ____________________________ Hot Water Tank Serial Number label on tank ________________________________ Date of Purchase Installation...

Страница 20: ...Sanden Heat Pump Owner s Manual Page 20 of 20 SANDEN Heat Pump 40950 44732 Owners Manual AU...

Отзывы: