background image

S&C Instruction Sheet 681-510    9

Operation

Pre-Operation Checks

 WARNING

Do not operate this switchgear if the SF

6

-gas 

pressure gauge is in the Red zone.

 Failure to follow 

this precaution can result in a flashover and 

equipment damage.

STEP  1.  

Make sure that the SF

6

-gas pressure gauge is in 

the green zone (or the green and yellow-striped 
zone) by lifting the viewing window cover under 
way one. See Figure 8.

Note: 

If the SF

6

-gas pressure gauge is in the green and 

yellow-striped zone, the switchgear can be operated but 
the tank must be repaired (if necessary) and refilled with 
SF

6

 gas as soon as possible. 

STEP  2.  

Open the viewing window cover and confi rm 
the position of the load-interrupter switch or 
fault interrupter by visually observing the 
position of the blades. 

For most Vista switchgear model fault inter-

rupters, confirm the position of the trip flags. 
For “-R1” suffix models, confirm the position of 
the disconnect switch blade through the viewing 
window. See Figures 9 and 10. 

Also, inspect the current-carrying components inside 

the tank specifically for dislodged hardware, signs of 
arcing, and significant blade misalignment. 

 WARNING

DO NOT operate the energized load interrupter 

switch or fault interrupter with dislodged hardware 
or obvious signs of arcing or significant blade 
misalignment. Equipment damage and personal 
injury may result.

Figure 9. Window cover lifts for viewing of switch or fault-
inter rupter blade positions.

Figure 8. SF

6

-gas pressure gauges.

Figure 10. Confirm blade position of load-interrupter switch or 
fault interrupter.

 WARNING

ALWAYS confirm the position of switches or fault 

interrupters by VISUALLY OBSERVING blade 

position.

Blade positioning for 15-kV, 12-kA models with 

“-R1”  suffix

Blade positioning for most Vista models.

Gauge for most Vista 
switchgear models.

Gauge for 15-kV, 12.5-kA 
models with “-R1” suffix.

TRIP indicator
for three-pole fault interrupt-
ers (can be seen through the 
viewing window)

TRIP indicators
for single-pole fault 
interrupters
(can be seen through 
the viewing window)

Содержание Vista Series

Страница 1: ...ns from Rapid Ambient Temperature Changes 8 Operation Pre Operation Checks 9 Operating from Closed to Open Position 11 Operating from Open to Grounded Position 12 Operating from Grounded to Open Posit...

Страница 2: ...roper Application WARNING The equipment in this publication must be selected for a specific application The application must be within the ratings furnished for the equipment Ratings for this gear are...

Страница 3: ...ot followed NOTICE NOTICE identifies important procedures or requirements that can result in product or property damage if instructions are not followed Following Safety Instructions If you do not und...

Страница 4: ...Always Consider Circuits and Components Live G 6700 C DANGER Never Drill Into Tank Hazardous Voltage Contains Pressurized SF6 Gas G 6682 D DANGER Keep Away Hazardous Voltage Mr Ouch G 6699 E WARNING C...

Страница 5: ...upter is grounded 7 BACKFEED Bushings cables load interrupter switches and fault interrupters may be energized by backfeed 8 DE ENERGIZING TESTING AND GROUNDING Before touching any bushings or compone...

Страница 6: ...al or single pole load switching and fault interruption through 12 5 kA symmetrical for other possible ratings refer to the nearest S C Sales Office Fault interruption is initiated by a programmable o...

Страница 7: ...en Manual operating handle Viewing window under the VOLTAGE indicator Trip indicators for single pole fault interrupters can be seen through the viewing window TRIP indicator for three pole fault inte...

Страница 8: ...nal gas pressure gauge for Vista switchgear models rated 15 kV 12 5 kA sym short circuit that have catalog numbers ending with R1 suffix Green zone Red zone Green Yellow zone Orange zone Gauge Needle...

Страница 9: ...isconnect switch blade through the viewing window See Figures 9 and 10 Also inspect the current carrying components inside the tank specifically for dislodged hardware signs of arcing and significant...

Страница 10: ...Closed and Open positions Operation Selector Operation Selector Figure 12 Rotating the OPERATION selector out of the way Operating disk Operating disk STEP 3 If the OPERATION selector is blocking the...

Страница 11: ...rrupter See Figures 15 and 16 STEP 4 When operating from the Closed to Open position the operating handle must be rotated all the way to the Stop position as shown on the label to open and recharge th...

Страница 12: ...ndicator optionsuffix L1 or L2 as instructed under the Checking for Voltage Using Optional Voltage Indicator section on page 17 or use an alternate method STEP 3 Insert the manual operating handle int...

Страница 13: ...pages 9 and 10 are completed STEP 2 Insert the manual operating handle into the notch of the operating mechanism STEP 3 Rotate the manual operating handle in the clockwise direction to a stop in the...

Страница 14: ...ting handle into the notch of the operating mechanism STEP 3 Rotate the manual operating handle in the clockwise direction to a stop in the Closed position to close the load interrupter switch or faul...

Страница 15: ...3 and 24 When operating from the Closed to the Open position the operating handle must be rotated all the way to the Stop position as shown on the label to recharge the mechanism See Figure 25 For thr...

Страница 16: ...ctor and the left side hole of the locking collar See Figure 27 Locking In Closed Open or Grounded Position To lock a load interrupter switch or fault interrupter into position insert a padlock throug...

Страница 17: ...window STEP 2 Test the VOLTAGE indicator complete voltage indication circuit and phasing circuit if furnished for proper operation as follows a Shine a flashlight approximately 4 inches 102 mm above t...

Страница 18: ...test circuit If the dot or any of the flashing lightning bolts still do not appear the VOLTAGE indicator may be damaged Test for voltage using an alternate method See Figures 34 and 35 PHASE indicato...

Страница 19: ...either There is no voltage at the bushing The VOLTAGE indicator is malfunctioning Flashing lightning bolt indicates presence of voltage at the associated bushing A blank LCD panel indicates an absence...

Страница 20: ...40 c Place the other test probe on each of the phasing pins in turn of the two ways to be phased and measure the phase to ground voltage See Figure 38 d If the voltage measured at each phasing pin is...

Страница 21: ...ting that the cables are in phase c Keep the test probe on Phasing Pin 1 of the second way and move the other test probe to Phasing Pin 2 of the first way Measure the phase to phasevoltage SeeFigure42...

Страница 22: ...rrupterswitchandfault interrupter grounding means are removed STEP 2 Make certain the load interrupter switches and fault interrupters are in the correct positions Open or Closed STEP 3 If a pad mount...

Страница 23: ...itches and fault interrupters from all power sources including backfeed test for voltage and properly ground 4 Always assume the bushings are energized unless proved otherwise by test by visual eviden...

Страница 24: ...enclosure must be refinished by the user before the finish has weathered for example to match other equipment a special precaution must be taken The entire surface must be sanded to provide a tooth t...

Страница 25: ...g or performance requirements for the switch gear A dc withstand design test is specified for new equip ment because the switchgear may be subjected to dc test voltage when connected to the cable The...

Страница 26: ...0 Hertz Impulse BIL 12 15 5 95 30 15 24 27 125 40 20 36 38 150 40 20 The dc cable thumping voltage is 50 of the dc cable test voltage because of voltage doubling that will occur at the open end of the...

Страница 27: ...1 Clamp the two current carrying probes of the resistance measuring device to the bushing conductors of the current carrying path to be measured See Figure 46 In this example the resistance is being t...

Отзывы: