manualshive.com logo in svg
background image

2    S&C Instruction Sheet 466-501 

VacuFuse

®

 II Self-Resetting Interrupter—Quick Operation Guide

Outdoor Distribution (12.47 kV through 27.0 kV)

STEP  2.  

Wait about one minute 45 seconds until the VacuFuse II interrupter drops out.

If the VacuFuse II Self-Resetting Interrupter stays in its cutout mounting, confirm the 

POSITION indicator at the base of the VacuFuse II interrupter displays a green target. 
In this case, the VacuFuse II interrupter may not be powered and cannot drop out. Refer 
to the “Troubleshooting” section of S&C Instruction Sheet 466-500 to determine the 
appropriate action to take.

If the VacuFuse II Self-Resetting Interrupter is in its cutout mounting with the  

vacuum interrupter in the 

Closed

 position and operating the manual operating lever  

to the 

Open

 position does not work, or the VacuFuse II interrupter is to be removed 

from its cutout mounting in the 

Closed

 position for any other reason, follow the instruc-

tions in the “Removing the VacuFuse II Interrupter from the Cutout Mounting using 
Loadbuster®—The S&C Loadbreak Tool” section of S&C Instruction Sheet 466-500.

 WARNING

DO NOT attempt to open a VacuFuse II Self-Resetting Interrupter that is in the 

Closed position without using a loadbreak tool, such as S&C’s Loadbuster tool. An 

arc started by opening a VacuFuse II Self-Resetting Interrupter under load without 
a loadbreak tool can cause equipment damage, serious injury, or death.
Instructions for using S&C’s Loadbuster tool can be found in S&C Instruction Sheet 
466-500.

STEP  3.  

Removal using gloved hands:

 Remove the VacuFuse II interrupter from its 

mounting with gloved hands, as shown in Figure 5.

STEP  4.  

Removal using the Talon Handling Tool:

 Attach a Talon tool to a short 

hotstick. Insert the curled prong of the Talon tool into the lifting eye of the 
trunnion, and raise the VacuFuse II interrupter out of its mounting.

If the VacuFuse II Self-Resetting Interrupter Is Found Open

 WARNING

The VacuFuse II Self-Resetting Interrupter is designed to protect distribution 
transformers from internal and external fault current. A VacuFuse II interrupter found 
in the 

Open and Drop Out position should not be closed using the manual operating 

lever until the cause of the fault current has been determined and repaired. Closing 
without repairing the fault could result in equipment damage, injury, or death.

 WARNING

VacuFuse II Self-Resetting Interrupters must be dropped out from the cutout mounting 
to be considered open. 
VacuFuse II Self-Resetting Interrupters are different from other cutout-mounted 
devices, including the VacuFuse® Self-Resetting Interrupter. VacuFuse II interrupters 
have a voltage-harvesting power supply that allows up to 1 mA of current to go through 
them, even when the vacuum interrupter is open. 
Failure to consider the current through the VacuFuse II interrupter when the vacuum 
interrupter is open may lead to serious injury or death.

After responding to an overcurrent event, the VacuFuse II interrupter’s vacuum inter-
rupter will open and the POSITION indicator will show a green target. If the overcurrent 
event persists after the reclosing event, the interrupter will lock out and drop out from 
the cutout mounting. Note that non-reclosing VacuFuse II interrupters will lock out and 
drop out from the cutout mounting every time the device responds to an overcurrent 
event. Follow these steps if the VacuFuse II Self-Resetting Interrupter has operated and 
is in the 

Open and Drop Out

 position:

STEP  1.  

Remove the VacuFuse II interrupter from its mounting, if required by utility 
practice, following the steps in the “Removing the VacuFuse II Interrupter from 
the Cutout Mounting” section.

STEP  2.  

Determine and resolve the cause of the fault. After the fault has been resolved 
and repairs completed, install the VacuFuse II interrupter and close it into the 
mounting as described in the “Installing a VacuFuse II Interrupter into the 
Cutout Mounting” section. 

If Maintenance Is to Be Performed on the Transformer

STEP  1.  

Open the vacuum interrupter inside the VacuFuse II interrupter by moving the 
manual operating lever to the 

Down

 position using the straight prong of the 

Talon Handling Tool or a distribution prong. See Figure 4.

STEP  2.  

After the VacuFuse II Self-Resetting Interrupter opens and drops out (after 
approximately 1 minute and 45 seconds), remove the unit from its mounting, if 
required by utility practice. Follow the steps in the “Removing the VacuFuse II 
Interrupter from the Cutout Mounting” section. This creates a visible open gap 
showing the transformer is isolated from the feeder. Depending on utility 
practice, additional grounds may be required.

STEP  3.  

Follow your utility’s standard practice for transformer maintenance. After 
maintenance is complete, install the VacuFuse II interrupter and close it into 
the mounting as described in the “Installing a VacuFuse II Interrupter into the 
Cutout Mounting” section.

Opening and Closing the VacuFuse II Interrupter

 WARNING

The VacuFuse II Self-Resetting Interrupter is designed to protect distribution 
transformers from internal and external fault current. A VacuFuse II interrupter found 
in the 

Open and Drop Out position (POSITION indicator displaying a green target) 

should NOT be closed until the cause of the fault current has been determined and 
repaired. Closing without repairing the fault could result in equipment damage, injury, 
or death.

The vacuum interrupter inside the VacuFuse II interrupter can be opened using the yellow 
manual operating lever on the side of the VacuFuse II interrupter, with or without power. 
The interrupter must be closed in the cutout mounting with sufficient voltage present 
for at least 45 seconds before the vacuum interrupter can be closed by moving the lever 
to the 

Up

 position. 

The VacuFuse II Self-Resetting Interrupter will drop out of the cutout mounting after 

one minute when the vacuum interrupter is in the 

Open

 position and the READY TO 

CLOSE LED is lit. 

To open: 

Pull the yellow manual operating lever down firmly using the straight prong of 

the Talon tool or a distribution prong. Remove the tool right away. The vacuum interrupter 
inside the VacuFuse II interrupter will open, and the POSITION indicator will show the 
green target. See Figure 2 on page 1. After one minute and 45 seconds of the vacuum 
interrupter in the 

Open

 position, the VacuFuse II interrupter will drop out. 

To close:

 Push the pull-ring of the manual operating lever up firmly using the straight 

prong of the Talon tool or a distribution prong. The vacuum interrupter inside the 
VacuFuse II interrupter will close after 45 seconds of sufficient voltage present at the 
cutout mounting, and the POSITION indicator will show the red target. See Figure 2.  
If the VacuFuse II interrupter is inadvertently closed into a fault, the vacuum interrupter 
will trip open independently of any force still applied to the manual operating lever.

To reset the manual operating lever after manually closing into fault current:

 

When the VacuFuse II interrupter trips in response to a fault, the lever does not move, 
leaving the lever in the 

Up

 position when the vacuum interrupter is in the 

Open

 position. 

The lever can be “reset” by operating it into the 

Down

 position while the vacuum 

 interrupter is in the 

Open

 position.

Removing the VacuFuse II Interrupter from the Cutout Mounting

 WARNING

DO NOT attempt to remove a VacuFuse II interrupter from its cutout mounting 
with the vacuum interrupter in the 

Closed position. The vacuum interrupter is in 

the 

Closed position when the POSITION indicator at the base of the VacuFuse 

II interrupter displays a red target. Removing the VacuFuse II interrupter from its 
cutout mounting with the vacuum interrupter in the 

Closed position may cause 

arcing, equipment damage, serious injury, or death.

STEP  1.  

Open the vacuum interrupter by pulling down on the yellow manual operating 
lever. Confirm the POSITION indicator at the base of the VacuFuse II  
interrupter displays a green target. See Figure 2 on page 1. 

Figure 4. A VacuFuse II Self-Resetting 

Interrupter. 

Manual 
operating 
lever

Hinge-end 
contact

Jaw-end 
contact

Pull-ring

Trunnion

Figure 5. Guiding or removing the trunnion 

from the hinge using gloved hands. 

Trunnion

Отзывы: